Annexure - 1
Project SUG Facilities
Fire Water Demand Calculation for Doc. No. JO-MP/AE-734-PR-804
SUG Facilities Fire Fighting system Sheet No. 1 OF 2
I HYDRANT System Demand : Full Unit
l) P-212 , P-213 & P-04 area 25.000 9.000 225.000 1 225.000 13.500
s)Shipping Tanks (T-3 and T-4) 12.200 13.400 2 1260.972 1 1260.972 75.658
Foam
L (M) / Foam Appln.
HEIGHT Appln. Total Water Total Flow
DIA No. Area (M2) Density
(M) Density Flow (lpm) (M3/Hr.)
(M) (gpm/ft2)
(lpm/m2)
a) New Wash Tank SG-T-201 - shell 28.042 15.240 1 1342.572 0.15 6.11 8205.633 492.338
New Wash Tank SG-T-201 - roof 28.042 15.240 1 617.583 0.15 6.11 3774.591 226.475
b) Existing Tank SG-T-001 - shell 24.994 15.850 1 1244.506 0.15 6.11 7606.265 456.376
Existing Tank SG-T-001 - roof 24.994 15.850 1 490.623 0.15 6.11 2998.624 179.917
III Water Requirements for Foam System Demands: Various Locations and Equipment
Foam
L (M) / Foam Appln.
HEIGHT Appln. Total Water Total Flow
DIA No. Area (M )
2
Density
(M) Density Flow (lpm) (M3/Hr.)
(M) (gpm/ft2)
(lpm/m2)
a) New Wash Tank SG-T-201 28.042 15.240 1 617.583 0.12 4.89 2929.083 175.745
b) Existing Tank SG-T-001 24.900 15.800 1 486.955 0.12 4.89 2309.536 138.572
Total Largest Water Demand shall be for Tank T-201 on fire (II (a) + III (a) 5238.619 894.558
m3/hr
FOAM SYSTEM
Foam Qty. Reqd. = Foam Solution Rate x % Foam Requirement x System Running Time
100
Minimum Foam Discharge Time 55 min (Ref: Table 3-2.4.3 NFPA 11)
(For Type II Discharge outlet)
Basis:
1 Tank Type Fixed Roof Cone type
2 Considering largest tank on fire at a time T-201
3 Type of Foam FP 70 (Flouroprotein)
4 Foam Conc. % 3
5 Fluid in Tank Crude Petroleum
c Min. No. of Foam Chambers as per Contract 3 nos. (Section 15550, Point No. 1.04 D)
K Factor for the above Foam Chamber Capacity & Pressure by DH Fire Protect, Model FC,
K = Q / ( P ) 0.5 = 380
Basis:
1 Tank Type Fixed Roof Cone type
2 Considering largest tank on fire at a time T-201
3 Type of Foam FP 70 (Flouroprotein)
4 Foam Conc. % 3
5 Fluid in Tank Crude Petroleum
c Min. No. of Foam Chambers as per Contract 3 nos. (Section 15550, Point No. 1.04 D)
K Factor for the above Foam Chamber Capacity & Pressure by DH Fire Protect, Model FC,
K = Q / ( P ) 0.5 = 302
Actual
Max. Velocity Minimum ID Line size Line ID
Equipment Water Requirement (m3/hr) velocity
(m/s) reqd (mm) considered (mm)
(m/s)
12" NB,
a) Tank SG-T-201 718.81 3.500 269.51 303.280 2.764
Sch 40
8" NB,
2 359.41 3.500 190.57 202.740 3.093
Sch 40
10" NB,
b) Tank SG-T-001 636.29 3.500 253.57 254.510 3.474
Sch 40
6" NB,
Foam Supply for Tank T-201 181.19 3.500 135.31 154.080 2.699
Sch 40
6" NB,
Foam Supply for Tank T-001 143.93 3.500 120.60 154.080 2.144
Sch 40
4" NB,
Foam riser to Tank T-201 90.59 3.500 95.68 102.260 3.064
Sch 40
4" NB,
Foam riser to Tank T-001 71.97 3.500 85.28 102.260 2.434
Sch 40
tank dia 24.9936 m
tank ht 15.8496 m
appl. Density
dist of ring header from tank outside 1 m
water reqd
riser 2 nos