Professional Documents
Culture Documents
net/publication/4108253
CITATIONS READS
0 542
3 authors, including:
Zoran Gajic
ABB Grid Automation Products
51 PUBLICATIONS 250 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Zoran Gajic on 06 April 2016.
φA φB φC
Figure 3. Typical inrush current for HV reactor
3. Inrush phenomena
3.1 General
The energizing of a shunt reactor will, to some degree,
behave in the same way as energizing of a power
transformer. We will have a transient inrush current.
Figure 4. Phase L1 current at an unsymmetrical
Due to the air gap, the reactor core keeps no remanence.
energizing of 150 MVAr, 400 kV reactor
This makes the inrush phenomena smoother. However,
the damping of the inrush current is slow due to the low
Restricted earth fault protection typically only uses the
losses in the shunt reactor. Therefore the primary
zero sequence currents for its operation. However, due
current might have, long lasting dc component.
to the phase CT saturation the calculated zero sequence
The presence of dc component with long time constant
current on the reactor HV side (i.e. 3Io) will be
might lead to saturation of the CT some periods after
corrupted. As a consequence there will be a
energizing of the reactor. This consecutively might lead
considerable amount of differential current when this
to maloperation of different types of protections. It is
summated current is compared with the neutral point
therefore necessary to consider this phenomenon when
current (see Figure 5 below).
designing the relay protection system for shunt reactors.
Inrush currents in phase L1 and L2 recorded from an
un-synchronized energizing of a 150 MVAr, 400 kV
shunt reactor are shown in Figure 3. From the figure we
can observe that phase L1 have a considerable current
drop around 9th cycle, while phase L2 current drop
occurs around 24th cycle.
The sudden drop of the inrush current in phase L1 and
L2 do not correspond to a similar drop in the phase L1
and L2 voltage, which leads to the conclusion that we Figure 5. 3I0 and IN as function of number of cycles
have a saturation phenomenon of the CT. The reason to
the saturation is the long primary DC time constant. The
saturation of the CT will be different in the different 3.2 Harmonics
phases and it might lead to maloperation of differential The saturation of the CT creates a lot of harmonics that
protection, restricted earth fault protection and the protection must be able to handle. From figure 6
directional and nondirectional earth fault protection. below, it can be shown that the predominant harmonics
are 2:nd and third harmonics, but also the 4:th
harmonics have high magnitudes.
Figure 6. Harmonic content from energizing of a 150
MVAr, 400 kV reactor in percentage of rated reactor
current.
4 Typical Reactor Protection Schemes Figure 7. Typical shunt reactor protection possibilities
Reactor protections have in the past been dedicated with modern IEDs
protections with a few functions. We can distinguish
between two traditionally used types of protections: The survey of the philosophy for the different protection
Type1: functions can be summarized as follows:
• restricted earth fault protection Phase differential function detects all types of shunt
• instantaneous and time delayed phase faults but has no possibility to detect turn-turn faults. It
overcurrent (constant and/or inverse time can be set quite sensitive due to a fact that there is no
delayed) need for biasing. The need for phase differential
• earth fault overcurrent protection measured at protection for a given reactor depends on reactor size
neutral point of reactor (constant and/or and importance of the unit
inverse time delayed) Restricted earth fault protection operates for all types of
Type2: faults that give zero sequence current. It is used in
• differential protection applications where the star connection is done internally
• instantaneous and time delayed phase in the reactor. It can be set very low, but consideration
overcurrents (constant and/or inverse time of the error in the comparison of the summarized phase
delayed) currents and the neutral current should be considered.
• earth fault protection measured at HV side of Phase overcurrent protection is used as backup for the
the reactor (constant and/or inverse time phase differential protection or as main protection for
delayed) phase-phase faults when restricted earth fault protection
is only used.
The restricted earth fault protection and the differential Phase overvoltage protection is sometimes used to
protection are considered as the main protection for detect line overvoltage conditions that may cause
internal fault in the reactor and shall trip the reactor damage to the reactor when it operates at higher voltage
immediately without any time delay. levels than the reactor rated voltage. Consultation with
The phase overcurrent protection is used as main reactor manufacturer is needed. A more common use is
protection in the type1 scheme and as backup to monitor the voltage on the system and to energize the
protection in scheme 2. reactor at a pre-defined “overvoltage level”. If the
The earth fault protection is used as backup protection reactor is already energized at the same time as the
in the type 1 scheme and as back up protection in the overvoltage level is activated, the overvoltage function
type 2 scheme. In both types of schemes, the earth fault can be used to protect the system from dangerous
protection acts as main protection for circuit breaker overvoltage i.e. disconnect the line and reactor.
pole disagreement. Phase undervoltage protection can be used for
Modern IEDs (Intelligent Electronic Device) give monitoring of the system voltage and de-energize the
benefit of realizing several protection functions within reactor when the system voltage drops below a certain
the same hardware box and consequently give better level.
possibilities to adopt the protection design to system Zero sequence overvoltage protection operates for all
requirements and customer philosophies. An example of types of external and internal faults with earth involved.
rector protection scheme utilized by a modern IED is By using logical elements in the IED and combining
shown in Figure 7. information from measuring the neutral point current, it
is possible to create a simple and sensitive earth fault
protection that is selective to external earth faults. As
well it is possible to detect turn-turn faults with this 6. Conclusions
scheme when the primary system is well balanced The paper has highlighted some important issues of the
Directional zero sequence overcurrent protection gives application of shunt reactors and their influence on the
possibilities to have a instantaneous high set stage and a reactor protection scheme. Field recordings from
time delayed low set stage which gives good backup for unsynchronized energizing of a 150 MVAr, 400 kV
the phase differential protection or restricted earth fault reactor have been highlighted and commented. Even
protection though synchronized energizing is used, the protection
Zero sequence overcurrent protection that measures the must be stable against the phenomenon that occurs
neutral point current can be used as a system backup when unsynchronized energizing occurs due to an
protection with low setting and long time delay. If the eventual failure in the synchronizing equipment.
current is combined with measuring the zero sequence
voltage, a sensitive backup protection for internal faults References:
can be achieved. 1. T Gönen “Electric Power Transmission System
Thermal overload protection is a protection that Engineering, Analysis and Design”
calculates the reactor thermal content by using a heat 2. Z Gajic, B Hillström, ABB Sweden, F Mekic ABB
content model. This gives a better adaptation to the real USA “HV Shunt Reactor Secrets for Protection
thermal capability of the reactor compare to using Engineers” 30th Western Relaying Conference
simple overcurrent protections. However, the overload Wasington October 21-23 2003
of reactor will only occur when the system voltage is 3. Carlson, Å., “Shunt Reactor Manual”, ABB Power
high and during those conditions there is a need for the Technology Products/Transformers, Ludvika-
shunt reactor to be energized. Therefore this function Sweden, 2002-08-20
shall be carefully used. Winding contact thermometer 4. ABB Transformatori, “Pamphlet Shunt Reactors”,
can be used instead. Roma-Italy
5. Switchgear Committee of the IEEE Power
5. Capabilities of modern IEDs in reactor Engineering Society, “IEEE Application Guide for
The modern numerical technique makes it possible to Shunt Reactor Switching”, IEEE Std C37.015-1993
handle the highlighted issues that occur in reactor 6. IEEE Power Systems Relaying Committee, “IEEE
applications due to very good filtering technique, Guide for the Protection of Shunt Reactors”,
possibility to perform current input signal harmonic ANSI/IEEE C37.109-1988
analyses, use adaptive logic etc. Figure 7 below shows 7. Nylen, R., “Shunt Reactor and SVC Protection
the difference in magnitude for the fundamental current Application Guide”, ABB Relays, Västerås-
IL1 obtained after digital Fourier filtering and the Sweden, 1988-11-17
corresponding phase current obtained as the true RMS 8. Elmore, W. A., editor, Protective Relaying: Theory
filtering. As can be seen, the RMS (true RMS) current and Applications, Marcel Dekker, Inc., 1994.
has much higher magnitude due to a presence of a lot of 9. IEEE Transaction on Power Apparatus and
harmonics. Therefore the phase overcurrent that uses Systems, Vol PAS-103, No 8, August 1984 “Shunt
Digital Fourier Filtered (DFF) quantities can be set Reactor Protection Practices”
more sensitive than relays that use RMS filter for its
operation. Similar results can be obtained if similar
analysis is performed for the neutral point current as
well.