SCORE:
The UNDER ZERO SAC has a freezing unit for storing vaccines that operate with a cascade
cycle at the following conditions:
- Refrigerants: R134a and R404a
- T out= 30 °C
- Tcab= -40 °C
- Thermal capacity= 2 tons
- Temperature difference in the heat exchanger= 10 °C
Calculate:
a) Draw the cycles in the respective Mollier Diagram (2 p)
b) Dimensioning the capillary tubes for both stages (1 p)
c) Total compression power (1 p)
d) COP of the system (1 p)
SOLUCIÓN
T. condenser: 40 °C
T. evaporator: -50 °C
Thermal Capacity: 7.02 KW
TEST 1
Refrigeration & Air Conditioning
T.cond1 = 40°C
CONDENSADOR
COMPRESOR
E. EXPAN.
Refrigerante
ETAPA 1 R134a
EVAPORADOR
T.evap1 = 0°C
COMPRESOR
E. EXPAN.
Refrigerante
ETAPA 2 R404A
EVAPORADOR
T.evap2 = -50°C
100
s = 1.65
DTU, Department of Energy Engineering
Energy Sy stems, Refrigeration 100 0.007
40.00 s in [kJ/(kg K)]. v in [m^3/kg]. T in [ºC] 0.008
90
M.J. Skovrup & H.J.H Knudsen. 08-08-19
90 0.009
0
0.010
s = 1.7
80
30.00
80
70
70 0.015
60
20.00 3
.00
v= 0 4 60
0.020
.00
50
v= 0 50
.006
40
v= 0 40 0.030
10.00 .008
v= 0
30
9.00
0.040
8.00 .010 30
v= 0
0.050
.75
7.00
1.95
20
.85
1.90
s= 1
.80
6.00 5 20
Pressure [Bar]
s= 1
0.01 0.060
s=
s= 1
s=
v=
5.00 0.070
10
2.00
. 020 10 0.080
v= 0
s=
4.00 0.090
0.100
030
0
2.05
.
3.00 v= 0 0
s=
. 040
-10
v= 0 0.150
2.10
-10
s=
2.00
.060
v= 0 0.200
2.15
-20
.080
v= 0 -20
s=
100
v= 0.
2.20
0.300
-30
s=
1.00
0.90 150 -30 0.400
2.25
0.80 v= 0.
00
v= 0.2
s=
0.70 0.500
-40
0.60 0.600
-40
0.50
x= 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 -40 -20 0 20 40 60 80 100 120 140
s= 1.00 1.20 1.40 1.60
140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560
Enthalpy [kJ/kg]
Thermal capacity:
Q1= 7.03 Kw = 24000 BTU/Hr
ETAPA 2:
𝑸𝟏 = 𝒎𝒓𝟐 ∗ (∆𝒉𝟒−𝟏 )
7.03 = 𝑚𝑟2 ∗ (338 − 186)
𝟎. 𝟎𝟒𝟔𝟐 𝑲𝒈⁄𝒔𝒆𝒈 = 𝒎𝒓𝟐
𝑪𝑶𝑷 = 𝟐. 𝟐𝟑 𝑲𝑾⁄𝑲𝑾
DIMENSIÓN DE LAS TUBOS CAPILARES
CC = 24000 BTU/HR