List of Equipment with specifications

Category /
S.No Name of Quantity Specifications
Equipment
Should be suitable for generation of both active and reactive power
(Wh and Varh) and shall depict multiple of generators with Automated
voltage regulators and Synchronization with Grid system, generator
transformer, and step up transformer, unit auxiliary transformer with
switchgears and numeric Relays and CB protections.

Simulator The protection system shall include simulation of faults for tripping on
1 training kit Over current, Under Voltage, Under frequency, Over voltage,
1
for Power generator differential protection, Stator and Rotor earth faults, check
Plant synchronization, Bus bar protection scheme, LV and HV measuring
instruments, and SCADA system.

The kit shall also include digital interfaced instrument A-V-W-VAR-


Wh-V, A, Cos (φ), Isolated source transformer and cables of different
lengths, trolley and Instruction manual, system software and warranty
for two years.
Simulation of 220 kV Transmission line and 110 kV Transmission
Lines with taps duly depicted by ‘pi’ model with concentrated
parameters. It shall have inbuilt resistors, capacitors and inductors of
high quality and front panel:

Line 1 : simulated for transmitted power of 16MVA


Line 2: simulated transmitted power 20 MVA;

The simulator shall be suitable to study the thee-phase transmission


lines to transport energy. Study of the lines working at no-load and at
load, change of voltage, voltage drops, losses in line, fluxes of active
and reactive power, phasing, parallel connected lines and LILO (loop
in Loop out system) and allocation and coordination of FACT
(Flexible AC transmission system) devices for voltage improvement
Transmission and control of the system.
2 line Simulator 1

The equipment should use current power and with provision of a UPS
for 30 mints backup.

The Kit shall include incoming and outgoing switches, No load and
Loaded line with and without phasing, injection of VOLT-VAR Control
with reactor and Capacitor bank simulation, all measurements and
line protection relays. It shall represent Zone wise protection of
Distance Relays, Over current, Under voltage, over voltage, Under
frequency, over frequency, CB fault and trip circuit supervision, Bus
bar Protection etc. complete.

The kit shall also include digital interfaced instrument A-V-W-VAR-


Wh-VA, Cos(φ), and cables of different lengths, trolley and
Instruction manual, system software and two years warranty.
The simulator shall represent a 110/ 20kV substation and 220/20 KV
substation with 2 Nos 110 or 220 kV incoming lines, Line bays , 2
Nos 10\16\ or 20 MVA Transformer Bay ,and 2 Nos 20 kV Feeder
bays with all standard switchgear and protection equipment and one
Station transformer, AC and DC distribution boards ,Battery system,
Float cub boost charger for battery bank It shall have an in-built
Inductor and resistor ,step capacitor for three phase loading.

The Kit shall be suitable to simulate Yy0, Yy6, Dy5, DYn 11vector
groups for the transformers, paralleling of transformers, O/C and E/F
protective relays for HV and MV, Transformer Differential protection,
REF, CB fail, OT, WT and Fire protection system.

The MV line is represented by T model with concentrated


parameters:

-Resistance per phase, Inductance per phase, Earth capacitance.


-3phase or single-phase mains voltage: max voltage: 400V.The Kit
shall also simulates a cabin to lower the voltage from 220-110 kV
Distribution to 20- 20/v 3 –20 kV and a 3-phase line overhead distribution at 20 -
3 Simulator for 20/v 3 – 20 kV for 30 km long. The experiences that shall be
1
MV and LV performed are :
system - No-load lines
- Load lines with determination of changes of voltage, losses and line
efficiency; Line voltage drop as function of load, Line loss as function
of load balanced and unbalanced 3-phase systems;

- Lines working in short-circuits


- Phasing
- Improvement of power factor capacitor load/ capacitor bank
insertion.
- Convenience to transport energy at high voltage
- Increase of voltage owing to a capacitive load
- Reduction of voltage owing to a Reactive Load/reactor insertion.
- Various Implementation of protections of max current, max power
and energy.

The kit shall have three phase numeric relays, in built digital I/O for
remote breaker operation. The simulator kit shall also include digital
interfaced instrument A-V-W-VAR-Wh-V,A, Cos(φ), and cables of
different lengths, trolley and Instruction manual, system software
and warranty for two years.
For implementing protection relay system with latest generation of
fully digital relays, for Under voltage, Picture thermal for lines and
transformers, overcurrent, Residual overcurrent, Overvoltage,
Simulating Kit
Residual overvoltage, Maximum directional current, Directional
for training on
earth fault , Distance protection, negative sequence, differential
Relay
protection, over fluxing and for Breaker Failure. The simulation kit
Protection
4 shall cater to Seimens, ABB, MICOM, SEL and GE relays.
and relay 1
coordination
The Simulation kit shall depict Relay protection of both Radial and
in radial and
Ring Networks.
Ring network
.
systems
The trip curves and all the functions of relays should be
programmable from PC with selectivity in current and in time. The
software should be able to set the parameters of the relay and
acquire real-time voltage, current and power of the circuit in which it
is inserted. To be provided with handbook covering implementation of
the protections of the line and downstream electrical machines from
the mathematical model.

All programming operations, modification, displaying measurements,


shall be possible directly from the front panel or also using a personal
computer with the included software. The relays should be capable of
storing the faults occurred and the curve of the currents in the
moments before the break.

The measurements of phase and residual currents, the


measurements of phase and residual voltage and the logical state of
the inputs shall be available on the display on the communication
interfaces. To be provided with all required software and interface
with protective relay trainers.

Indicative ratings shall be 400 V, 8 Amp, 2000 VA; DC Rating 300 V,


8 Amp, 80 Watts with Response time < 10 ms, Resolution 0.01.,
Operating temperature 0 - 50 ° C, RH 5%-95%, altitude 3000 meters.

Software for The software shall be suitable for design and simulation of micro grid
5 Simulation and comprising Solar PV, Wind and Bio-mass combinations and shall
1
Analysis of offer optimum solution combining technical feasibility, what if kind of
Micro grids sensitivity analysis and economics.
Simulation kit
for integration
of Generation- Simulation kit that interfaces the above Generation-Transmission and
Transmission- distribution simulation kits with suitable hardware and system
Distribution software .The Kit shall comprehensively depict the load flows and
( optional- not impact of active and reactive load changes in the Distribution network
6 for bid on transmission and Generation system and cascaded effect on the
56
evaluation but relay settings when downstream relay settings are tampered.
for
procurement The system shall include supply of related integrated software and all
later if accessories.
required by
us)