Steel Vicwest HB30V-Z275 Steel Deck PDF
Steel Vicwest HB30V-Z275 Steel Deck PDF
COMPOSITE FLOOR
HB30V
Z275 GALVANIZED
LIMIT STATES
DESIGN METRIC
DEPTH FROM MAXIMUM FACTORED PHYSICAL
Note SECTION MODULUS Moment of Inertia
NEUTRAL REACTIONS
1. Load Tables are NOMINAL MASS WITH
MIDSPAN SUPPORT MIDSPAN FULL
AXIS TO PROPERTIES
CORE AREA OF ZF75 BOTTOM OF EXTERIOR INTERIOR STEEL PROFILE
based on the design Sm Ss Im If
THICKNESS STEEL GALVANIZED DECK Y b (kN) (kN)
of ONE-WAY (mm3 x 103) (mm3 x 103) (mm4 x 103) (mm4 x 103)
(mm) (mm2) (kg/m2) (mm)
composite slabs
carrying uniformly 0.76 1005.1 8.11 18.18 19.17 848.6 1028.1 41.58 5.8 13.1 (PER METRE WIDTH)
distubuted loads on a 0.91 1207.4 9.74 24.10 25.16 1081.0 1234.7 41.67 10.8 24.9 In accordance
simple span basis. with CSA
1.22 1606.7 12.83 37.27 37.87 1582.1 1641.8 41.86 14.9 36.7
For complete design Specification
criteria see the 1.52 2009.7 16.04 47.94 48.44 2035.1 2052.2 42.04 18.4 47.3
S136-07
VICWEST Hi-Bond
Composite Floor SLAB THICKNESS 141 151 166 176 PHYSICAL
Designer's Manual. h(mm)
Slab Weight, W1(kN/m2) 2.38 2.60 2.94 3.16 PROPERTIES
2. A uniform loading in
Concrete Volume, (m3/m2) 0.099 0.109 0.124 0.134 COMPOSITE SLAB
excess of 10 kPa Base Steel Nominal (PER METRE WIDTH)
(200 psf) is often an Thickness IC d IC d IC d IC d
indication of Composite
(mm)
concentrated or Moment of
moving loads. Such 0.76 13086 99.4 15951 109.4 21018 124.4 24951 134.4 Inertia,
conditions may 0.91 13846 99.3 16864 109.3 22196 124.3 26330 134.3 I C (mm4 x 103)
require additional
1.22 15235 99.1 18533 109.1 24353 124.1 28859 134.1 Effective Depth,
reinforcing steel.
Contact VICWEST d (mm)
1.52 16521 99.0 20076 109.0 26349 124.0 31202 134.0
for additional design
Base Steel
information
Nominal 1 2 3 1 2 3 1 2 3 1 2 3
LOAD TABLE
3. Slab Thickness h, is Thickness Span Span Span Span Span Span Span Span Span Span Span Span Span
from underside of (mm) (mm)
steel deck to top of 1600 16.2 16.2 16.2 17.8 17.8 17.8 20.0 20.0 20.0 20.0 20.0 20.0 Maximum
concrete. Maximum 1800 13.5 13.5 13.5 14.8 14.8 14.8 16.9 16.9 16.9 18.2 18.2 18.2 Specified
0.76
span is not to exceed 2000 11.5 11.5 11.5 12.6 12.6 12.6 14.3 14.3 14.3 15.5 15.5 Uniformly
32h. 2200 9.9 9.9 9.9 10.9 10.9 10.9 Distributed Load
4. Properties and loads 2200 10.7 10.7 10.7 11.8 11.8 11.8 13.4 13.4 13.4 14.5 14.5 14.5
are based on Grade in kN/m 2 (kPa)
2400 9.4 9.4 9.4 10.4 10.4 10.4 11.8 11.8 11.8 12.7 12.7 12.7
230 steel (Grade 33 2600 8.4 8.4 8.4 9.2 9.2 9.2 10.5 10.5 11.3 11.3
steel) with a 0.91
2800 7.6 7.6 8.3 8.3 9.5 9.5 10.2 Shear Bond
minimum yield stress 3000 6.9 6.9 7.5 Coefficents
of 230 MPa (33,000
3200 k 1 = 11.1084
psi) and a maximum
2600 9.7 9.7 9.7 10.7 10.7 10.7 12.2 12.2 12.2 13.1 13.1 13.1 k 2 = 55.8868
stress under
2800 8.8 8.8 8.8 9.6 9.6 9.6 11.0 11.0 11.0 11.9 11.9 11.9 k 3 = 0.1034
Factored loads of 207
MPa (29,700 psi). 3000 8.0 8.0 8.0 8.8 8.8 8.8 10.0 10.0 10.0 10.8 10.8 10.8 k 4 = 0.0397
3200 7.3 7.3 7.3 8.0 8.0 8.0 9.1 9.1 9.1 9.9 9.9 9.9
1.22
5. Load values are 3400 6.7 6.7 6.7 7.4 7.4 7.4 8.4 8.4 9.1
based on Normal 3600 6.2 6.2 6.2 6.9 6.9
Weight Concrete 3800 5.8
(density of 2300 4000
kg/m3) (145 pcf) with 3200 8.3 8.3 8.3 9.1 9.1 9.1 10.4 10.4 10.4 11.2 11.2 11.2
a minimum 3400 7.7 7.7 7.7 8.4 8.4 8.4 9.6 9.6 9.6 10.4 10.4 10.4
compressive strength 7.1 7.8 8.9 9.6
3600 7.1 7.1 7.8 7.8 8.9 8.9 9.6 9.6
of 20.7 MPa (3,000 1.52 3800 6.6 6.6 6.6 7.3 7.3 7.3 8.3 8.3 9.0 9.0
psi) and a Modular
4000 6.2 6.2 6.9 6.9 7.8
Ratio n=9
4200 5.9 5.9 6.4
4400
Continued on back
In accordance with ongoing efforts to improve our products and their performance, Vicwest
reserves the right to change without notice the specifications contained herein.
The contents herein are for general information and illustrative purposes only and are not intended to
serve as any type of advice. Every effort is made to ensure the accuracy of the information included in
this brochure and it is believed that the information contained herein is accurate and reliable as of the
date of publication. Vicwest, however, does not warrant or represent the accuracy or reliability of any
information included in this brochure. Any reliance on any information without consultation with Vicwest VW00147EN10/10
or a duly authorized representative shall be at the user's own risk. ©2010, Vicwest – All rights reserved
HI-BOND
COMPOSITE FLOOR
HB30V
Z275 GALVANIZED
LIMIT STATES
DESIGN
IMPERIAL
PHYSICAL DEPTH FROM MAXIMUM FACTORED
SECTION MODULUS Moment of Inertia Note
NEUTRAL REACTIONS
PROPERTIES NOMINAL MASS WITH
MIDSPAN SUPPORT MIDSPAN FULL
AXIS TO
Continued from
STEEL PROFILE CORE AREA OF ZF75 BOTTOM OF EXTERIOR INTERIOR
STEEL GALVANIZED Sm Ss Im If DECK Y b front
THICKNESS (pounds) (pounds)
(inches) (inches2) (lb/ft2) (inches3) (inches3) (inches4) (inches4) (inches)
(PER FOOT WIDTH) .030 0.475 1.662 0.3381 0.3566 0.6214 0.7529 1.637 397 898 6. No additional
In accordance with ongoing efforts to improve our products and their performance, Vicwest
reserves the right to change without notice the specifications contained herein.
The contents herein are for general information and illustrative purposes only and are not intended to
serve as any type of advice. Every effort is made to ensure the accuracy of the information included in
this brochure and it is believed that the information contained herein is accurate and reliable as of the
date of publication. Vicwest, however, does not warrant or represent the accuracy or reliability of any
information included in this brochure. Any reliance on any information without consultation with Vicwest VW00147EN10/10
or a duly authorized representative shall be at the user's own risk. ©2010, Vicwest – All rights reserved