WIND LOAD CALCULATION AS PER IS-875 FOR GABLE FRAMES

MADE BY : ALEX IMMANUEL


$ INPUT $ CALCULATION $ OUTPUT AS PER IS875-1987(REAFFIRMED 2003)

BUILDING DATA
LENGTH OF THE BUILDING 40 meters ROOF SLOPE 1 : 10
WIDTH OF THE BUILDING 30 meters WIND SPEED 39 m/s
EAVE HEIGHT 10 meters TERRAIN CATEGORY 1
BAY SPACING 5 meters BUILDING CATEGORY B

BUILDING PERMEABILITY CONDITION MEDIUM(B/W 5% TO 20 %) (OF WALL AREA)


LOADING ON FRAME MEMBERS
(NOTE: ALL VALUES IN KN/m)

7.00 4.37 4.37 7.00

Y 0.97 LOAD 3.64 -3.64 LOAD -0.97


CASE 1 CASE 2

2.15 -0.49
-0.49 2.15

5.82 LOAD -1.21 1.21 LOAD -5.82


Y CASE 3 CASE 4

6.31 6.31 1.46 1.46

LOAD LOAD
CASE 5 CASE 6
Y -4.85 4.85 0.00 0.00

K1 K2 K3 INTERNAL PRESSURE CO-EFFICIENT


1.00 1.03 1.00 0.5
H/W 0.33 h/w≤0.5 GCpi
DESIGN WIND VELOCITY 40.17 m/s L/W 1.33 1<l/w≤1.5 -0.5
WIND PRESSURE 0.970 kN/m²

CLICK ON '+' ON THE LEFT TO VIEW ( STADD USER CAN COPY THE DETAILS SHOWN BELOW IN STADD EDITOR FOR REFERENCE)
* (+i) TRANSVERSE WIND PRESSURE
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL 0.700 0.20 x0.97x5= 0.97 kN/m (pressure)
* LEFT ROOF -0.943 -1.44 x0.97x5= -7.00 kN/m (suction)
* RIGHT ROOF -0.400 -0.90 x0.97x5= -4.37 kN/m (suction)
* RIGHT WALL -0.250 -0.75 x0.97x5= -3.64 kN/m (suction)
*
* (-i) TRANSVERSE WIND SUCTION
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL 0.700 1.20 x0.97x5= 5.82 kN/m (pressure)
* LEFT ROOF -0.943 -0.44 x0.97x5= -2.15 kN/m (suction)
* RIGHT ROOF -0.400 0.10 x0.97x5= 0.49 kN/m (pressure)
* RIGHT WALL -0.250 0.25 x0.97x5= 1.21 kN/m (pressure)
*
* (+i) LONGITUDINAL WIND PRESSURE
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL -0.500 -1.00 x0.97x5= -4.85 kN/m (suction)
* LEFT ROOF -0.800 -1.30 x0.97x5= -6.31 kN/m (suction)
* RIGHT ROOF -0.800 -1.30 x0.97x5= -6.31 kN/m (suction)
* RIGHT WALL -0.500 -1.00 x0.97x5= -4.85 kN/m (suction)
*
* (-i) LONGITUDINAL WIND SUCTION
* GCPe (GCPe - GCPi) WIND LOAD

* LEFT WALL -0.50 0.00 x0.97x5= 0.00 kN/m (suction)


* LEFT ROOF -0.80 -0.30 x0.97x5= -1.46 kN/m (suction)
* RIGHT ROOF -0.80 -0.30 x0.97x5= -1.46 kN/m (suction)
* RIGHT WALL -0.50 0.00 x0.97x5= 0.00 kN/m (suction)
CALCULATION OF EXTERNAL PRESSURE COEEFFICIENT ON PITCHED ROOFS
(AS PER IS-875 1987:PART 3 ;REAFFIRMED 2003)

α= 5.71

h (in meters) = 10

w (in meters) = 30

h/w = 0.3
ROOF ANGLE WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.
α E F G H E F G H
5.71 -0.943 -0.943 -0.400 -0.400 -0.800 -0.429 -0.800 -0.429

EXTERNAL PRESSURE COEEFFICIENT ON PITCHED ROOFS (AS PER TABLE 5 OF IS-875:PART 3)

ROOF WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.


ANGLE(α) E F G H E F G H
0 -0.8 -0.8 -0.4 -0.4 -0.8 -0.4 -0.8 -0.4
5 -0.9 -0.9 -0.4 -0.4 -0.8 -0.4 -0.8 -0.4
10 -1.2 -1.2 -0.4 -0.4 -0.8 -0.6 -0.8 -0.6 FOR H/W <= 1/2
20 -0.4 -0.4 -0.4 -0.4 -0.7 -0.6 -0.7 -0.6
30 0 0 -0.4 -0.4 -0.7 -0.6 -0.7 -0.6
45 0.3 0.3 -0.5 -0.5 -0.7 -0.6 -0.7 -0.6
60 0.7 0.7 -0.6 -0.6 -0.7 -0.6 -0.7 -0.6
5.71 -0.943 -0.943 -0.400 -0.400 -0.800 -0.429 -0.800 -0.429

ROOF ANGL WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.


α E F G H E F G H
0 -0.8 -0.8 -0.6 -0.6 -1.0 -0.6 -1.0 -0.6
5 -0.9 -0.9 -0.6 -0.6 -0.9 -0.6 -0.9 -0.6
NOTE: 10 -1.1 -1.1 -0.6 -0.6 -0.8 -0.6 -0.8 -0.6
when wind acts in lateral direction of frame ( i.e 0 deg wind angle) 20 -0.7 -0.7 -0.5 -0.5 -0.8 -0.6 -0.8 -0.6 1/2 < H/W <= 3/2
*E & F falls on windward side & has same co-efficients 30 -0.2 -0.2 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
*G & H falls on leeward side & has same co-efficients 45 0.2 0.2 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
60 0.6 0.6 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
when wind acts in longitudinal direction of frame ( i.e 90 deg wind angle) 5.71 -0.929 -0.929 -0.600 -0.600 -0.886 -0.600 -0.886 -0.600
*E & G has same coefficients
*F & H has same co-efficients ROOF ANGL WIND ANGLE = 0 deg. WIND ANGLE = 90 deg
α E F G H E F G H
the coefficients are assumed to act outwards i.e suction pressure 0 -0.7 -0.7 -0.6 -0.6 -0.9 -0.7 -0.9 -0.7
(as mentioned in clause 6.2.2.2 of IS 875) 5 -0.7 -0.7 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8
10 -0.7 -0.7 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8
20 -0.8 -0.8 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8 3/2 < H/W < 6
co-efficients for the local effects are not used for calculating 30 -1.0 -1.0 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
40 -0.2 -0.2 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
force on structural elements(as mentioned in clause 6.2 of IS 875) 50 0.2 0.2 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
60 0.5 0.5 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
5.71 -0.700 -0.700 -0.600 -0.600 -0.800 -0.800 -0.800 -0.800