Professional Documents
Culture Documents
101.6.6 Swimming Pool. The provisions of the swimming pool code shall apply to the
erection, installation, alteration, repair, relocation, replacement, addition to, use and
maintenance of swimming pools, spas, or hot tub systems. Where a swimming pool code is
not adopted or where the content of the swimming pool code adopted by the jurisdiction is
not applicable, then swimming pool code shall mean the Uniform Swimming Pool, Spa & Hot
Tub Code (USPSHTC) promulgated by the International Association of Plumbing and
Mechanical Officials (IAPMO).
2 Alternate Add new text as follows: New definition because of its inclusion AM
Water as a source for On-Site Treated Non-
Sources TG Section 206.0 Potable Water.
Dry Weather Runoff. Water that flows along a surface, in a channel or sub-surface
including groundwater seepage, and is not associated with a rainwater catchment system or
stormwater harvesting.
3 Plumbing Add new definition as follows: A new definition for lavatory added to AM
Water clarify a lavatory faucet.
Efficiency Section 214.0
TG
Lavatory. A sink or washbasin intended primarily for the purpose of personal hygiene.
-2-
413.10.3.1 Sprinkler Heads in Common Zones. Sprinkler heads installed in zones
served by a common valve shall be limited to plant materials with similar
irrigation needs, and shall have matched precipitation rates (identical inches
of water application per hour).
413.10.3.2 Sprinkler Head Pressure Regulation. Sprinkler heads shall utilize
pressure regulating devices to maintain manufacturers recommend
operating pressure for each sprinkler and nozzle type.
413.10.3.3 Pop-up Type Sprinkler Heads. Where pop-up type sprinkler heads are
used, the sprinkler head shall rise to a height of not less than four (4) inches
(101 mm) above the soil level when emitting water.
413.10.3.5 Nozzle Performance Criteria. Irrigation zones containing turfgrass shall
be designed and installed to assure the average precipitation rate of the
sprinkler nozzles over the irrigated area does not exceed 200% of the soil
absorption rate, and shall not exceed a water application rate of 1.0 inches
per hour
413.11 Landscape Irrigation System Maintenance Schedule and Repairs. Landscape
irrigation systems shall be maintained and repaired in accordance with Section
413.10.1 and 413.10.2.
413.11.1 Maintenance. Landscape irrigation systems shall be maintained in proper
operating condition in accordance with the original design to retain water
use efficiency. A regular maintenance schedule shall be available for
submission to the Authority Having Jurisdiction and kept on site. A
landscape irrigation system maintenance schedule shall include, but not be
limited to, monthly inspection, adjustment and repair of the irrigation system
and its components; and removing any obstruction to emission devices.
Operation of the landscape irrigation system outside the irrigation schedule
is permitted for auditing and system maintenance purposes only.
413.11.2 Repair and Replacement. Repair and replacement of landscape irrigation
equipment and components shall be performed using parts that are
equivalent to the originally installed components in order to retain the
original water use efficiency of the system.
413.12 Qualifications. The Authority Having Jurisdiction shall have the authority to require
landscape irrigation contractors, installers, or designers to demonstrate competency.
Where required by the Authority Having Jurisdiction, the contractor, installer, or
designer shall be certified to perform such work. Note: certification programs, such
as those operated by US EPA and the Irrigation Association are examples of
certification programs that provide a demonstration of competency in water-efficient
irrigation designs and technology.
-3-
218.0
Plumbing Code. The plumbing code that is adopted by the jurisdiction. Where a plumbing
code is not adopted or where the content of the plumbing code adopted by the jurisdiction is
not applicable, then mechanical code shall mean the Uniform Plumbing Code (UPC)
promulgated by the International Association of Plumbing and Mechanical Officials (IAPMO).
220.0
Reclaimed (Recycled) Water. Non-potable water provided by a water/wastewater utility
that, as a result of tertiary treatment of domestic wastewater, meets requirements of the
public health Authority Having Jurisdiction for its intended uses. The level of treatment and
quality of the reclaimed (recycled) water shall be approved by the public health Authority
Having Jurisdiction.
220.0
Reclaimed (Recycled) Water. Non-potable water provided by a water/wastewater utility
that, as a result of tertiary treatment of domestic wastewater, meets requirements of the
public health Authority Having Jurisdiction for its intended uses. The level of treatment and
quality of the reclaimed (recycled) water shall be approved by the public health Authority
Having Jurisdiction.
501.7 Minimum Water Quality Requirements. The minimum water quality for alternate
water source systems shall meet the applicable water quality requirements for the intended
application as determined by the public health Authority Having Jurisdiction. In the absence
of water quality requirements, the EPA/625/R-04/108 contains recommended water reuse
guidelines to assist regulatory agencies develop, revise, or expand alternate water source
water quality standards.
504.10.2 Minimum Water Quality. On-site treated non-potable water supplied to toilets or
urinals or for other uses in which it is sprayed or exposed shall be disinfected. Acceptable
disinfection methods shall include chlorination, ultraviolet sterilization, ozone, or other
methods as approved by the Authority Having Jurisdiction. The minimum water quality for
on-site treated non-potable water systems shall meet the applicable water quality
requirements for the intended applications as determined by the public health Authority
Having Jurisdiction.
505.9.4 Minimum Water Quality. The minimum water quality for harvested rainwater shall
meet the applicable water quality requirements for the intended applications as determined
by the public health Authority Having Jurisdiction. No treatment is required for rainwater
-4-
used for subsurface or non-sprinkled surface irrigation where the maximum storage volume
is less than 360 gallons (1363 L).
B 101.7 Minimum Water Quality Requirements. The minimum water quality for all potable
rainwater catchment systems shall meet the applicable water quality requirements as
determined by the public health Authority Having Jurisdiction. In the absence of water quality
requirements, the guidelines EPA/625/R-04/108 contains recommended water reuse
guidelines to assist regulatory agencies develop, revise, or expand alternate water source
water quality standards.
B 104.2 Minimum Water Quality. The minimum water quality for harvested rainwater shall
meet the applicable water quality requirements for the intended applications as determined
by the public health Authority Having Jurisdiction, Health Department or other department
having jurisdiction.
8 Alternate Add new text as follows: New definitions because of its inclusion AM
Water as a source for On-Site Treated Non-
Sources TG Section 221.0 Potable Water.
Stormwater. Precipitation that has contacted a surface at grade or below grade and has not
been put to beneficial use.
Stormwater Harvesting. The collection, storage and treatment of stormwater for beneficial
use.
9 Sidney Add new sections as follows: Added a new section to include the AS
Cavanaugh, approved standard for pipe
Cavanaugh 303.2 Rehabilitation of Piping Systems. When pressure piping systems are rehabilitated rehabilitation.
Consulting using an epoxy linings system it shall meet ASTM F2831.
[renumber remaining sections]
-5-
ASTM F2831-11, Standard Practice for Internal Non Structural Epoxy Barrier Coating
Material Used in Rehabilitation of Metallic Pressurized Piping Systems.
10 GTC Revise Appendix A: Delete in entirety and replace with Appendix A - Reserved Water savings calculation was moved AM
into the body of the code with
Revision section 402.0 as follows: modification. A baseline calculation table
is included with a water savings
402.0 Water-Conserving Plumbing Fixtures and Fittings. – Revised – calculator to determine the minimum
402.1 General. The installation and water consumption for plumbing fixtures and fixture 20% reduction path of compliance.
fittings shall be in accordance with Section 402.1 through Section 402.8, applicable
standards referenced in Table 1101.1, and the plumbing code.
The maximum water consumption of fixtures and fixture fittings shall comply with one of the
following:
1. The maximum flow rates of fixtures and fixture fittings shall comply with the flow
rates specified in Table 402.1 and Sections 402.2 through Section 402.8.
2. The aggregate consumption of all fixtures and fixture fittings shall be at least 20
percent reduction of the calculated total daily water use in accordance with Tables
402.1.3(1) and 402.1.3(2).
402.1.1 Water Savings Calculation.
402.1.2 Purpose. The purpose of this Section is to provide a means of estimating the
water savings when installing plumbing fixtures and fixture fittings that use less water
than the maximum required by Energy Policy Act of 1992 and 2005 and the plumbing
code.
402.1.3 Calculation of Water Savings. Table 402.1.3(1) and Table 402.1.3(2) shall be
used to establish the aggregate consumption of all fixtures and fittings. Table 402.1.3(1)
shall be used to establish the baseline water use and Table 402.1.3(2) shall be used to
calculate the required reduction according to Section 402.1.
TABLE 402.1
MAXIMUM FIXTURE AND FITTINGS FLOW RATES FOR REDUCED WATER USING
FIXTURES
1
For multiple showerheads serving one shower compartment see Section 402.5.2
2
Shall also be listed to EPA WaterSense Tank-Type High Efficiency Toilet Specification.
3
Shall also be listed to EPA WaterSense Flushing Urinal Specification. Nonwater urinals
shall meet the specifications listed in Section 402.3.1.
TABLE 402.1.3(1)
WATER USE BASELINE5
ESTIMATED DAILY
MAXIMUM
DAILY USES OCCUPANTS3, WATER
FIXTURE TYPE FLOW-RATE DURATION 4
PER USES
CONSUMPTION2
PERSON (gallons)
2.5 gpm @ 80
Showerheads 8 minutes 1
psi
Private or
Private Use 2.2 gpm @ 60 0.25
4
Lavatory psi minutes
Faucets
Residential 2.2 gpm @ 60
4 minutes 1
Kitchen Faucets psi
2.2 gpm / 20
Wash [rim space
– –
Fountains (inches) @ 60
psi]
Lavatory
Faucets in other
than
Residences,
Apartments,
0.25
and Private 0.5 gpm 4
minutes
Bathrooms in
Lodging
Facilities (See
Section
402.4.2)
Metering 0.25 gallons
- 3
Faucets /cycle
Metering 0.25 gpm / 20
Faucets for [rim space
- –
Wash (inches) @ 60
Fountains psi]
1.6 gallons per 1 male1
Water Closets 1 flush
flush 3 female
1.0 gallons per 1 flush
Urinals 2 male
flush
Total Daily Volume
-7-
Annual Work Days
Total Annual Usage
For SI units: 1 gallon per minute = 0.06 L/s, 1 gallon = 3.785 L
For SI units: 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.89 kPa, 1
gallon = 3.785 L
Consumption = (Flow rate) x (Duration) x (Occupants) x (Daily uses)
1 The daily use number shall be increased to three if urinals are not installed in the room.
2 The maximum flow rate or consumption is from the Energy Policy Act (lavatories
excepted).
3 For residential occupancies, the number of occupants shall be based on two persons for
the first bedroom, and one additional person for each additional bedroom.
4 For non-residential occupancies, refer to the plumbing code, for occupant load factors.
5 When determining calculations, assume one use per person for metering or self-closing
faucets.
TABLE 402.1.3(2)
WATER SAVINGS CALCULATOR
CONSUMPTION
(gallons per DAILY WATER
DURATION DAILY
FIXTURE TYPE minute or OCCUPANTS 2,3 USES
(minutes) USES
gallons per (gallons)
cycle)
Showerheads 8 minutes 1
Private or
Private Use 0.25
4
Lavatory minutes
Faucets
Residential
Kitchen 4 minutes 1
Faucets
Wash
– –
Fountains
Lavatory
Faucets in
other than
Residences,
Apartments,
0.25
and Private 4
minutes
Bathrooms in
Lodging
Facilities
(See Section
402.4.2)
Metering 0.25
1 Cycle
Faucets minutes
Metering
Faucets for 0.25
–
Wash minutes
Fountains
-8-
Water 1 male1
1 flush
Closets 3 female
Urinals 1 flush 2 male
Total Daily Volume
Annual Work Days
Total Annual Usage
Annual Savings
% Reduction4
For SI units: 1 gallon per minute = 0.06 L/s, 1 gallon = 3.785 L
1 The daily use number shall be increased to three if urinals are not installed in the room.
2 For residential occupancies, the number of occupants shall be based on two persons for
the first bedroom, and one additional person for each additional bedroom.
3 For non-residential occupancies, refer to the plumbing code, for occupant load factors.
4 To calculate % Reduction use: [(TDVB - TDVS) / TDVB] x 100 Where: TDVB = Baseline
Total Daily Volume and TDVS = Water Savings Total Daily Volume
Notes and instructions for Table 402.1.3(2):
Table 402.1.3(1) is 4 a calculator that can help estimate water savings in residential and
nonresidential structures. The “Duration” of use and “Daily Uses” values that appear in the
table are estimates only and based on previous studies. To obtain and use a working copy
of this calculator, follow the download and use instructions below.
Instructions for download:
1. Go to the IAPMO web site at www.iapmogreen.org in order to download the water-
savings calculator. The calculator is a Microsoft Office Excel file (1997 or later), your
computer must be capable of running MS Excel.
2. Follow the instructions for downloading and running the file.
Instructions for use:
1. In the Baseline Case section, insert the number of total occupants, male occupants and
female occupants that apply for the building in the “Occupants” column. Unless specific
gender ratio values are provided, assume a 50/50 gender ratio.
2. Copy and paste these same values in the “Occupants” column of the Calculator section.
3. In the Calculator section only, insert the consumption values (flow rates in gpm or gallons
per flush or per cycle) in the “Consumption” column.
4. Estimated water savings in terms of percent savings versus baseline values, gallons per
day and gallons per year will be automatically calculated.
11 GTC Revised section as follows: A change was made to clarify that the AS
water supply rough-in height is from
402.3.1 Nonwater Urinals. Nonwater urinals shall comply with ASME A112.19.3/CSA finished floor.
B45.4, ASME A112.19.19/CSA B45.4 or IAPMO Z124.9. Nonwater urinals shall be cleaned A correction was made to indicate
and maintained in accordance with the manufacturer’s instructions after installation. Where drainage fixture units instead of water
nonwater urinals are installed they shall have a water distribution line roughed-in to the urinal supply fixture units.
location at a height not less than 56 inches (1422 mm) above finished floor to allow for the
installation of an approved backflow prevention device in the event of a retrofit. Such water
distribution lines shall be installed with shutoff valves located as close as possible to the
distributing main to prevent the creation of dead ends. Where nonwater urinals are installed,
not less than one water supplied fixture rated at not less than 1 water supply drainage fixture
-9-
unit (WSDFU) shall be installed upstream on the same drain line to facilitate drain line flow
and rinsing.
14 GTC Add new section as follows: A new section added to direct pressure AS
regulator installation requirements to the
404.2 Installation. Pressure regulators shall be installed in accordance with the plumbing plumbing code.
code.
15 Dave Revise section as follows: The changes made are consistent with AM
Zabrowski, the size of the industry-standard
Fisher- 406.1.2 Food Steamers. Food All steamers shall consume not use more than 52.0 gallons 12x20x2.5-inch hotel pans that the
Nickel, Inc. per hour (gph) (7.6 L/h 19 liters) per compartment hour per steamer pan in the full appliance can accommodate at one
operational mode. time.
Add Food Steamers to Chapter 2 Definitions: A new definition for food steamers is
added.
208.0
Food Steamers (Steam Cookers). A cooking appliance wherein heat is imparted to food in
a closed compartment by direct contact with steam. The compartment can be at or above
atmospheric pressure. The steam can be static or circulated.
16 Plumbing Revise section as follows: The changes made are consistent with AS
Water the size of the industry-standard
Efficiency 406.1.3 Combination Ovens. Combination ovens shall not consume more than 10 3.5gph 12x20x2.5-inch hotel pans that the
TG (38 13L/h) per pan in the full operational mode. appliance can accommodate at one
time.
Add combination ovens to Chapter 2 Definitions:
A new definition for combination ovens
205.0 is added.
- 10 -
Combination Ovens. A device that combines the function of hot air convection (oven
mode) and saturated and superheated steam heating (steam mode), or both, to perform
steaming, baking, roasting, rethermalizing, and proofing of various food products. In
general, the term combination oven is used to describe this type of equipment, which is
self contained. The combination oven is also referred to as a combination oven/steamer,
combi or combo.
17 Plumbing Revise section as follows: The reserved section for dipper wells AS
Water was developed that was consistent with
Efficiency 406.1.5 Dipper Well Faucets. Reserved. Where dipper wells are installed, the water supply industry standards.
TG to a dipper well shall have a shutoff valve and flow control. The flow of water into a dipper
well shall be limited by at least one of the following methods:
1. Maximum continuous flow. Water flow shall not exceed the water capacity of the
dipper well in one minute at supply pressure of 60 psi (413.7 kPa) and the
maximum flow shall not exceed 2.2 gpm (8.32 lpm) at a supply pressure of 60 psi
(413.7 kPa). The water capacity of a dipper well shall be the maximum amount of
water that the fixture can hold before water flows into the drain.
2. Metered flow. The volume of water dispensed into a dipper well in each activation
cycle of a self closing fixture fitting shall not exceed the water capacity of the dipper
well and the maximum flow shall not exceed 2.2 gpm (8.32 lpm) at a supply pressure
of 60 psi (413.7 kPa).
18 Plumbing Add new section as follows: New section for water efficiency AS
Water [and renumber remaining sections accordingly] provisions for evaporative cooling
Efficiency systems that tend to waste large
TG 410.4 Evaporative Cooler Water Use: Evaporative cooling systems (sometimes called quantities of water. Overflow alarms
swamp coolers) shall utilize use less than 3.5 gallons of water per ton-hour of cooling when needed since faulty valves cause
system controls are set to maximum water use. Water use, expressed in maximum water reservoirs to overflow undetected
use per ton-hour of cooling, shall be marked on the device and included in product user wasting large quantities of water.
manuals, product information literature and installation instructions. Water use information Provisions include discharge non-
shall be readily available at the time of code compliance inspection. potable reuse.
410.4.1 Overflow Alarm. Cooling system shall be equipped with an overflow alarm to alert
building owners, tenants or maintenance personnel when water refill valve continues to allow
water to flow into the reservoir when reservoir is already full. The alarm shall have a
minimum sound pressure level rating of 85 dB measured at a distance of ten feet.
410.4.2 Automatic Pump Shut-off. Cooling system shall automatically cease pumping
water to the evaporation pads when airflow across evaporation pads ceases.
410.4.3 Cooler Reservoir Discharge. A water quality management system (either timer or
water quality sensor) is required. Where timers are used, the time interval between
discharge of reservoir water shall be set to six hours or greater of cooler operation. Where
water quality sensors are used, the discharge of reservoir water shall be set for greater 800
ppm or greater of TDS. Continuous discharge or continuous bleed systems are prohibited.
410.4.4 Discharge Water Reuse. Discharge water shall be reused where appropriate
applications exist on site. Where a nonpotable water source system exists on site,
evaporative cooler discharge water shall be collected and discharged to such collection
system.
Exception: Where the reservoir water will adversely affect the quality of the nonpotable
- 11 -
water supply making the nonpotable water unusable for its intended purposes.
410.4.5 Discharge Water to Drain. Where discharge water is not required to be recovered
for reuse, the sump overflow line shall not be directly connected to a drain. Where the
discharge water is put into a sanitary drain, a minimum 6 inch air gap is required between
the termination of the discharge line and the drain opening. The discharge line shall
terminate in a location that is readily visible to the building owner, tenants or maintenance
personnel.
20 Plumbing Add new section as follows: A new section was added to include AS
Water water efficiency provisions for trap
Efficiency 413.0 Trap Primers. Trap primers shall be electronic or pressure activated and shall use no primers as well as alternative water
TG more than thirty (30) gallons (114 L) per year per drain. Where an alternate water source, as
sources.
defined by this code, is used for fixture flushing or other uses in the same room, the alternate
water source shall be used for the trap primer water supply.
Exception: Flushometer tailpiece trap primers complying with IAPMO PS 76 are exempted
from the provisions of this section
21 GTC Add new section as follows: A new provision added to allow the AM
collection of condensate for reuse.
414.0 Condensate Recovery. Condensate is permitted to be used as on-site treated non-
potable water where collected, stored and treated in accordance with Section 504.0.
22 Plumbing Add new section as follows: A new section to include water efficiency AS
Water provisions for automated vehicle wash
Efficiency 415.0 Automated Vehicle Wash Facilities. The maximum make-up water use for facilities.
TG automobile washing shall not exceed 40 gallons per vehicle for in-bay automatic car washes
and 35 gallons for conveyor and express type car washes. Spray wands and foamy brushes
shall use no more than 3.0 gallons per minute. Spot-free reverse osmosis discharge (reject)
water shall be recycled. Towel ringers shall have a positive shut-off valve. Spray nozzles
shall be replaced annually.
Exemption: Bus and large commercial vehicles washes are exempt from the requirements in
this section.
- 12 -
23 Alternate Revise section as follows: Editorial revision to correspond with AS
Water current language of competency in the
Sources TG 501.2 System Design. Alternate water source systems complying with this chapter shall be Supplement while complying with the
designed by a person registered or licensed to perform plumbing design work or who IAPMO Manual of Style.
demonstrates competency to design the alternate water source system as required by the
Authority Having Jurisdiction. Components, piping, and fittings used in any alternate water
source system shall be listed.
Revised language for B 101.2 to correspond with changes in 501.2
B 101.2 System Design. Potable rainwater catchment systems complying with this
appendix shall be designed by a person registered, or licensed, or deemed competent to
perform plumbing design work or who demonstrates competency to design the potable
rainwater catchment system as required by the Authority Having Jurisdiction to perform
potable rainwater catchment system design work.
Revise as follows:
505.9.4 Minimum Water Quality. The minimum water quality for harvested rainwater shall
meet the applicable water quality requirements for the intended applications as determined
by the public Health Authority Having Jurisdiction. In the absence of water quality
requirements determined by the Authority Having Jurisdiction, the minimum treatment and
water quality shall also comply with Table 505.9.4. No treatment is required for rainwater
used for subsurface or non-sprinkled surface irrigation where the maximum storage volume
is less than 360 gallons (1363 L).
TABLE 505.9.4
- 13 -
505.9.11 for drip irrigation.
Subsurface and drip • Debris excluder or other N/A
irrigation approved means in compliance
with Section 505.9.10.
• 100 Micron (100 µm) in
compliance with Section
505.9.11 for drip irrigation.
Spray irrigation where the • Debris excluder or other N/A
maximum storage approved means in compliance
volume is less than 360 with Section 505.9.10.
gallons (1363 L) • Disinfection in accordance with
Section 505.9.8.
• Turbidity: < 10
NTU
Cooling tower make up • Debris excluder or other • Escherichia
water approved means in compliance coli: < 100
with Section 505.9.10. CFU/100 mL
• 100 Micron (100 µm) in
compliance with Section • Turbidity: < 10
505.9.11. NTU
Table 501.5
Minimum Alternate Water Source Testing, Inspection and Maintenance Frequency
504.11 Signs. Signs in buildings using on-site treated nonpotable water shall be in
accordance with Section 504.11.1 and Section 504.11.2. 501.10.
504.11.1 Commercial, Industrial, and Institutional Restroom Signs.
504.11.2 Equipment Room Signs.
505.10 Signs. Signs in buildings using rainwater water shall be in accordance with Section
505.10.1 and Section 505.10.2. 501.10.
505.10.1 Commercial, Industrial, and Institutional Restroom Signs.
505.10.2 Equipment Room Signs.
- 15 -
501.10 Commercial, Industrial, and Institutional Restroom Signs. A sign shall be
installed in all restrooms in commercial, industrial, and institutional occupancies using
reclaimed (recycled) water, on-site treated water, and non-potable rainwater for water
closets, urinals, or both. Each sign shall contain 1⁄2 of an inch (12.7 mm) letters of a highly
visible color on a contrasting background. The location of the sign(s) shall be such that the
sign(s) shall be visible to all users. The location of the sign(s) shall be approved by the
Authority Having Jurisdiction and shall contain the following text:
501.10.1 Equipment Room Signs. Each room containing reclaimed (recycled) water, on-
site treated water, and non-potable rainwater equipment shall have a sign posted in a
location that is visible to anyone working on or near non-potable water equipment with the
following wording in 1 inch (25.4 mm) letters:
504.12 Inspection and Testing. On-site treated nonpotable water systems shall be
inspected and tested in accordance with Section 504.12.1 through Section 504.12.2 501.11.
504.12.1 Supply System Inspection and Test.
504.12.2 Annual Cross-Connection Inspection and Testing.
504.12.2.1 Visual System Inspection.
504.12.2.2 Cross-Connection Test.
504.12.2.3 Discovery of Cross-Connection.
504.12.2.4 Annual Inspection.
- 16 -
505.11 Inspection and Testing. Rainwater catchment systems shall be inspected and
tested in accordance with Section 505.11.1 through Section 505.11.2 501.11.
505.11.1 Supply System Inspection and Test.
505.11.2 Annual Cross-Connection Inspection and Testing.
505.11.2.1 Visual System Inspection.
505.11.2.2 Cross-Connection Test.
505.11.2.3 Discovery of Cross-Connection.
505.11.2.4 Annual Inspection.
501.11 Inspection and Testing. Alternate water source systems shall be inspected and
tested in accordance with Section 501.12.1 through Section 501.12.2.
501.11.1 Supply System Inspection and Test. Alternate water source systems shall be
inspected and tested in accordance with the plumbing code for testing of potable water
piping.
501.14 Sizing. Unless otherwise provided for in this supplement, alternate water source
piping shall be sized in accordance with the plumbing code for sizing potable water piping.
- 19 -
B104.4.1.2 Below Grade. Rainwater storage tanks installed below grade shall be
structurally designed to withstand all anticipated earth or other loads. Holding tank covers
shall be capable of supporting an earth load of not less than 300 pounds per square foot
(lb/ft2) (1465 kg/m2) when the tank is designed for underground installation. Below grade
rainwater tanks installed underground shall be provided with manholes. The manhole
opening shall be a minimum diameter of 20 inches and located not less than 4 inches (102
mm) above the surrounding grade. The surrounding grade shall be sloped away from the
manhole. Underground tanks shall be ballasted, anchored, or otherwise secured, to prevent
the tank from floating out of the ground when empty. The combined weight of the tank and
hold down system should meet or exceed the buoyancy force of the tank.
34 GTC Add new sections as follows: Venting requirements were added for AS
storage tanks.
505.9.5.8 Storage Tank Venting. Where venting by means of drainage or overflow piping is
not provided or is considered insufficient, a vent shall be installed on each tank. The vent
shall extend from the top of the tank and terminate a minimum of six inches (6”) above grade
and shall be a minimum of 1 ½” in diameter. The vent terminal shall be directed downward
and covered with a 3/32 inch (2.4 mm) mesh screen to prevent the entry of vermin and
insects.
B104.4.6 Storage Tank Venting. Where venting by means of drainage or overflow piping is
not provided or is considered insufficient, a vent shall be installed on each tank. The vent
shall extend from the top of the tank and terminate a minimum of six inches (6”) above grade
and shall be a minimum of 1 ½” in diameter. The vent terminal shall be directed downward
and covered with a 3/32 inch (2.4 mm) mesh screen to prevent the entry of vermin and
insects.
35 Hot Water Delete sections as follows: Recirculation system provisions for both AS
TG residential and non-residential have
602.3 Recirculation Systems. been combined under General
602.3.1 Pump Operation. provisions.
602.3.2 Demand Controlled.
602.3.3 System Balancing. The sub-section on Demand Controlled
602.3.4 Flow Balancing Valves. has been replaced with a new sub-
602.3.5 Air Elimination. section entitled Recirculation Pump
602.3.6 Gravity or Thermosyphon Systems. Controls
603.4.4.1 Recirculation System Balancing.
603.4.4.2 Flow Balancing Valves.
603.4.4.3 Air Elimination
603.4.5.2 Temperature Maintenance Controls.
603.4.5.4 Circulating Pump Controls.
- 20 -
601.3.1.1 For Low-Rise Residential Buildings. Circulating hot water systems shall be
arranged so that the circulating pump(s) can be turned off (automatically or manually) when
the hot water system is not in operation. [ASHRAE 90.2:7.2]
601.3.1.2 For Other than Low-Rise Residential Buildings. When used to maintain storage
tank water temperature, recirculating pumps shall be equipped with controls limiting
operation to a period from the start of the heating cycle to a maximum of 5 minutes after the
end of the heating cycle. [ASHRAE 90.1:7.4.4.4]
601.3.2 Recirculation Pump Controls. Pump controls shall include on-demand activation
or time clocks combined with temperature sensing. Time clock controls for pumps shall not
let the pump operate more than 15 minutes every hour. Temperature sensors shall stop
circulation when the temperature set point is reached and shall be located on the circulation
loop at or near the last fixture. The pump, pump controls and temperature sensors shall be
accessible. Pump operation shall be limited to hours of operation only.
601.3.3 Temperature Maintenance Controls. For other than low-rise residential buildings,
systems designed to maintain usage temperatures in hot-water pipes, such as recirculating
hot-water systems or heat trace, shall be equipped with automatic time switches or other
controls that can be set to switch off the usage temperature maintenance system during
extended periods when hot water is not required. [ASHRAE 90.1:7.4.4.2]
601.3.4 System Balancing. Systems with multiple recirculation zones shall be balanced to
uniformly distribute hot water, or they shall be operated with a pump for each zone.
601.3.5 Flow Balancing Valves. Flow balancing valves shall be a factory preset automatic
flow control valve, a flow regulating valve, or a balancing valve with memory stop.
601.6.6 Air Elimination. Provision shall be made for the elimination of air from the return
system.
601.3.7 Gravity or Thermosyphon Systems. Gravity or thermosyphon systems are
prohibited.
602.3 Recirculation Systems. Recirculation systems shall meet the provisions in Section
601.3
36 Hot Water Delete sections as follows: Both Sections on insulation are identical AS
TG and apply to both Residential and Non-
602.5 Insulation. residential and therefore are placed
603.4.3 Insulation. under General provision.
601.2 Insulation. Hot water supply and return piping shall be thermally insulated. The wall
thickness of the insulation shall be equal to the nominal diameter of the pipe up to 2 inches
(50 mm). The wall thickness shall be not less than 2 inches (51 mm) for nominal pipe
diameters exceeding 2 inches (51 mm). The conductivity of the insulation [k-factor
(Btu•in/(h•ft2•oF))], measured radially, shall be less than or equal to 0.28 [Btu•in/(h•ft2•oF)]
[0.04 W/(m•k)]. Hot water piping to be insulated shall be installed such that insulation is
continuous. Pipe insulation shall be installed to within ¼ of an inch (6.4 mm) of all
- 21 -
appliances, appurtenances, fixtures, structural members, or a wall where the pipe passes
through to connect to a fixture within 24 inches (610 mm). Building cavities shall be large
enough to accommodate the combined diameter of the pipe plus the insulation, plus any
other objects in the cavity that the piping must cross. Pipe supports shall be installed on the
outside of the pipe insulation.
Exceptions:
(1) Where the hot water pipe is installed in a wall that is not of sufficient width to
accommodate the pipe and insulation, the insulation thickness shall be permitted to have the
maximum thickness that the wall can accommodate and not less than 1/2 of an inch (12.7
mm) thick.
(2) Hot water supply piping exposed under sinks, lavatories, and similar fixtures.
(3) Where hot water distribution piping is installed within attic, crawlspace, or wall insulation.
(a) In attics and crawlspaces the insulation shall cover the pipe not less than 5 inches (140
mm) further away from the conditioned space.
(b) In walls, the insulation must completely surround the pipe with not less than 1 inch (25.4
mm) of insulation.
(c) If burial within the insulation will not completely or continuously surround the pipe, then
these exceptions do not apply.
602.5 Insulation. Insulation of hot water and return piping shall meet the provisions in
Section 601.2.
603.4.3 Insulation. Insulation of hot water and return piping shall meet the provisions in
Section 601.2.
37 Hot Water Add section as follows: Provisions for hot water submetering AS
TG were added with the applicable
602.7.1 Hot Water System Submeters. Where a hot water supply from a circulation loop or maximum volume requirements.
electric heat trace line is equipped with a submeter, the hot water distribution system
downstream of the submeter shall have either an end-of-line hot water circulation pump or
shall be electrically heat traced. The maximum volume of water in the runoffs of the
circulation loop or electric heat trace line downstream of the submeter shall not exceed 16
ounces (oz) (473 mL).
If there is no circulation loop or electric heat traced line downstream of the submeter, the
submeter shall be located within two (2) feet of the central hot water system; or the branch
line to the submeter shall be circulated or heat traced to within two (2) feet of the submeter.
The maximum volume from the submeter to each fixture shall not exceed 32 ounces (oz)
(946 mL).
38 GTC Update Table 603.4.2 of GPMCS to 2010 Edition of ASHRAE 90.1. The proposed changes to Chapter 6 of AS
the GPMCS are based on ASHRAE
SEE ATTACHMENT 1 90.1-2010.
39 Hot Water Add section as follows: A new section added for drainage heat AS
TG recovery devices with the appropriate
606.0 Drain Water Heat Exchangers. Drain water heat exchangers shall comply with compliance standard.
IAPMO PS-92. The heat exchanger shall be accessible.
- 22 -
40 GTC Update Chapter 7 of GPMCS to 2010 Edition of ASHRAE 90.1. The proposed changes to Chapter 7 of AS
the GPMCS are based on ASHRAE
SEE ATTACHMENT 1 90.1-2010.
43 HVACR TG Add new section as follows: A new section reserved for grease AS
removal devices for kitchen exhaust
703.5.8.3 Grease Removal Devices. Reserved. hoods.
- 23 -
44 HVACR TG Revise section as follows: Energy Star compliance was added to AM
the provisions for fans.
805.2 Bathroom Exhaust Fans. Except when a whole house ventilation energy recovery
system is used, a mechanical exhaust fan vented to the outdoors shall be provided in each
room containing a bathtub, shower, or tub/shower combination. The ventilation rate shall be
not less than 50 ft3/min (23.6 L/s) for intermittent operation and 20 ft3/min (9.4 L/s) for
continuous operation. Fans shall be in accordance with the ENERGY STAR program
- 24 -
ARI (AHRI) 550/590- Performance Rating of Water Chilling Packages 704.3.1.2, Table
2003 Using the Vapor Compression Cycle 703.8.1(3)
ARI (ANSI/AHRI) 560- Absorption Water Chilling and Water Heating Table 703.8.1(3)
2000 Packages
ARI (AHRI) 1160 (I-P) - Performance Rating of Heat Pump Pool Heaters Table 603.4.2
20089
ASHRAE 52.1-1992 Gravimetric and Dust Spot Procedures for 803.1.1
WITHDRAWN Testing Air Cleaning Devices Used in General
Ventilation for Removing Particulate Matter
ANSI/ASHRAE 52.2- Method of Testing General Ventilation Air Chapter 2, 803.1.1
2007 Cleaning Devices for Removal Efficiency by
Particle Size
ANSI/ASHRAE 55-2004 Thermal Environmental Conditions for Human 807.1
2010 Occupancy
ANSI/ASHRAE 62.1- Ventilation for Acceptable Indoor Air Quality 703.5.1, 703.5.2.1,
2007 2010 703.5.2.3
ANSI/ASHRAE 62.2- Ventilation and Acceptable Indoor Air Quality in 805.1.3
2007 2010 Low-Rise Residential
Buildings
ANSI/ASHRAE 90.1- Energy Standard for Buildings Except Low-Rise Chapter 6, Chapter 7
2007 (2008 Residential Buildings (Includes Addenda a, b, c,
Supplement) 2010 (I-P) g, h, i, j, k, l, m, n, p, q, s, t, u, w, y, ad, and aw)
ANSI/ASHRAE 90.2- Energy Efficient Design of Low-Rise Residential Chapter 6, Chapter 7
2007 Buildings
ASHRAE 136-1993 A Method of Determining Air Change Rates in 805.1.3.1.3
(R2006) Detached Dwellings
ANSI/ASHRAE 146-2006 Method of Testing and Rating Pool Heaters Table 603.4.2
2011
ASHRAE GRP-158-1979 Cooling and Heating Load Calculation Manual Table 702.6.1
- 25 -
ASTM D3261-2003 Standard Specification for Butt Heat Fusion 705.1.2
2010a Polyethylene (PE) Plastic Fittings for
Polyethylene (PE) Plastic Pipe and Tubing
ASTM D3350-2008 Standard Specification for Polyethylene Plastics 705.1.2
2010a Pipe and Fittings Materials
ASTM E96/E96M-2005 Standard Test Methods for Water Vapor 702.4.1
2010 Transmission of Materials
ASTM F1055-2006 2011 Standard Specification for Electrofusion Type 705.1.2
Polyethylene Fittings for Outside Diameter
Controlled Polyethylene and Crosslinked
Polyethylene (PEX) Pipe and Tubing
CAN/CSA C448-2002 Design and Installation of Earth Energy 705.1.1
(R2007) Systems
CFR 10, 430, App N DOE Uniform Test Method for Measuring the Table 603.4.2, Table
Energy Consumption of Furnaces 703.8.1(5), Table
703.8.1(6)
CFR 10, 431 DOE Energy Efficiency Program for Certain Table 703.8.1(6)
Commercial and Industrial Equipment
CAN/CSA B137.1-20059 Thermoplastic Pressure Piping Compendium, 705.1.2
Polyethylene (PE) pipe
CSA ANSI Z21.10.3/CSA Gas Water Heaters, Volume III, Storage Water Table 603.4.2
4.3-2004 2011 Heaters With Input Ratings Above 75 000 BTU
per Hour, circulating and Instantaneous
CSA ANSI Z21.47b/CSA Gas-Fired Central Furnaces Table 703.8.1(5)
2.3b -20078 A/CSA 2.3A-
2007
CSA/AM CSAANSI Gas Unit Heaters, Gas Packaged Heaters, Gas Table 703.8.1(5)
Z83.8/CSA2.6 20069 Utility Heaters and Gas-Fired Duct Furnaces
CTI ATC-105-2000 Acceptance Test Code for Water Cooling Table 703.8.1(7)
Towers
CTI ATC-105S-2004 Acceptance Test Code for Closed Circuit Table 703.8.1(7)
Cooling Towers
CTI STD-201-20042011 Standard for Certification of Water Cooling Table 703.8.1(7)
Tower Thermal Performance
EPA/625/R-04/108, 2004 Guidelines for Water Reuse 501.7
EPA WaterSense High-Efficiency Lavatory Faucet Specification, 402.4.1
Version 1.0, October 1, 2007
EPA WaterSense Tank-Type High-Efficiency Toilet Specification, 402.2.1
Version 1.01, January 24, 2007May 20, 2011
IAPMO IGC 207-2006b Reclaimed Water Conservation System for 504.0, Appendix B
2009a/CSA B128 - 2006 Flushing Toilets
IAPMO IGC 250-2007 Diverter Valve for Rainwater Tank 505.0, Appendix B
IAPMO PS 76 Ballcock or Flushometer Valve Tailpiece Trap 413.0
Primers and Trap Primer Receptors / Adaptors
IAPMO UMC 2009* Uniform Mechanical Code 101.6.3
IAPMO UPC 2009* Uniform Plumbing Code 103.6.4
IAPMO USEC 2009* Uniform Solar Energy Code 604.1
IAPMO Z124.9-2004 Plastic Urinal Fixtures 402.3, 402.3.1
ISO 13256-1-1998 Water-source Heat Pumps - Testing and Rating Table 703.8.1(2)
for Performance – Part 1: Water-to-Air and
Brine-to-Air Heat Pumps
NFPA 31-20062011 Standard for the Installation of Oil Burning 702.6.2
Equipment
- 26 -
NFPA 54-2009*(2012) National Fuel Gas Code 702.6.2
NFPA 211-20062010 Standard for Chimneys, Fireplaces, Vents, and 702.6.2
Solid Fuel-Burning Appliances
NSF/ANSI 44-20079 Residential Cation Exchange Water Softeners 405.1
NSF/ANSI 53-2007a Drinking Water Treatment Units – Health Effects B104.2.1
2010
NSF P151, 1995 Protocol for Health Effects from Rainwater B103.1
Catchment System Components
SCAQMD METHOD Determination of Volatile Organic Compounds 808.1
316A-1992 (revised (VOC) in materials Used for Pipes and Fittings
1996)
SMACNA-1985 HVAC Air Duct Leakage Test Manual 702.4.3.1, 703.4.4.2.2
SMACNA-1994 HVAC Systems Commissioning Manual 703.7.3.4.1
SMACNA-2005 HVAC Duct Construction Standards, Metal and 703.4.4, 703.4.4.2.1
Flexible
SMACNA-2007 IAQ Guidelines for Occupied Buildings under 803.1.1
Construction
UL 181A-1994 Closure Systems for Use with Rigid Air Ducts Table 703.4.4.2(2)
2005(R2005) and Air Connectors
UL 181B-1995 Closure Systems for Use with Flexible Air Ducts Table 703.4.4.2(2)
2005(R2006) and Air Connectors
UL 727-2006 Oil Fired Central Furnaces Table 703.8.1(5)
UL 731-1995 Standard for Safety Oil-Fired Unit Heaters Table 703.8.1(5)
47 GTC Revise table as follows: Minimum water quality standards for AM
potable water and frequency of testing is
Table B 101.5.1 added. Disinfection devices expanded to
Description Minimum Frequency include a requirement to be listed or
certified to perform the required
Perform applicable water 3-months microbiological reduction.
quality tests to verify
compliance with Section
B104.2.
B 104.2 Minimum Water Quality. The minimum water quality for harvested rainwater shall
meet the applicable water quality requirements for the intended applications Upon initial
system startup, the quality of the water for the intended applications shall be verified at the
point(s) of use, as determined by the public health Authority Having Jurisdiction, Health
Department or other department having jurisdiction. In the absence of water quality
requirements determined by the Authority Having Jurisdiction, the minimum water quality
shall comply with the following limits:
- 27 -
Normal system maintenance will require system testing every 3 months. System shall
comply with the following standards
a. Upon failure of the fecal coliform test, system shall be re-commissioned involving
cleaning, and retesting in accordance with section B104.2
b. One sample shall be analyzed for applications serving up to 1,000 persons. When
the treated water shall serve 1,000-2,500 persons two (2) samples shall be analyzed
and for 2,501-3,300 persons three (3) samples shall be analyzed.
49 GTC Add new section as follows: New section as a result of the editorial AS
revision to move storage tank
B 104.4.1 Construction. Rainwater storage tanks shall be constructed of solid, durable construction under the section on
materials not subject to excessive corrosion or decay and shall be watertight. Storage tanks Rainwater Storage Tanks.
shall be approved by the Authority Having Jurisdiction for potable water applications,
provided such tanks comply with approved applicable standards.
- 28 -