You are on page 1of 2

Company Name:

Company Address:

Order Number:

General test information: Date/Time: 2017-06-06, 07:58:23 AM


Test device: CT-Analyzer Device Serial No.: EL074Z
File name: 017\KHUDARIYAH-Commissioning\HA-27-INCOMER-2\T015-HA-27_Y\ALCE_2015-1001508862_1_3600.x
Assessments: OK

Used test settings:


I-pn: 3600.0 A Location: Object:
I-sn: 1.0 A Company: OSAIS Manufacturer: ALCE
Rated burden: 60.0 VA / 1 Country: KSA Type: AR01a
Operating burden: 60.0 VA / 1 Station: KHUDARIYAH Serial number: 2015-1001508862
Applied standard: IEC 61869-2 Feeder/Bay: HA27 Core number: 1
Core type (P/M): P Phase: Y Tap: 3600
Class: PX IEC-ID Optional:
f: 60.0 Hz max. Rct: 16.0 Ω Kx: 13.61

Resistance test: Burden test:


Rmeas (30°C): 12.89965 Ω Burden: cos φ: Z:
Rref (75°C): 15.09429 Ω Vmeas: Imeas:

Excitation test:
V-kn: 1021.961 V I-kn: 0.007579 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A Kx: 13.61 Kx: 13.61
Ls: Lm: 440.774H Ts: 5.87s Ts: 5.87s
Kr: 83.31 %
required measured Assessments:
Ek: 800.0 V Ie: 0.025 A Ek: 1021.961 V Ie: 0.00758 A #N/A
E1, Vk1 400.0 V Ie1, Ik1 0.00249 A Ie1 Ik1: 0.00249 A #N/A

Ratio test:
Ratio: 3600.0 : 0.99957 ε : -0.0427 % ∆φ: 1.02 min Polarity: OK N: 3599.75
εt : -0.0069 %

Excitation curve data


Excitation curve data

10000

1000

100
Es / V

10

0.1
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
60 VA/ 1 -0.158 -0.096 -0.079 -0.066 -0.054 -0.043 -0.042 -0.040
30 VA/ 1 -0.118 -0.062 -0.051 -0.042 -0.033 -0.026 -0.024 -0.022
15 VA/ 1 -0.098 -0.043 -0.035 -0.028 -0.021 -0.018 -0.017 -0.013
7.5 VA/ 1 -0.082 -0.034 -0.026 -0.021 -0.015 -0.012 -0.011 -0.009
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
60 VA/ 1 10.309 3.442 2.272 1.518 0.970 1.023 0.955 0.724
30 VA/ 1 9.146 2.836 1.839 1.207 0.736 0.623 0.677 0.566
15 VA/ 1 8.634 2.456 1.566 1.012 0.596 0.423 0.388 0.433
7.5 VA/ 1 8.324 2.222 1.391 0.902 0.523 0.360 0.327 0.285
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200

0.000
0 50 100 150 200 250

-0.020

-0.040
Current deviation [%]

-0.060
100% Load

-0.080
50% Load

-0.100
25% Load

-0.120

-0.140

-0.160

-0.180

% I-pn