You are on page 1of 2

Company Name:

Company Address:

Order Number:

General test information: Date/Time: 2017-06-06, 09:58:25 AM


Test device: CT-Analyzer Device Serial No.: EL074Z
File name: 2017\KHUDARIYAH-Commissioning\HA-36-BUS TIE-2\T071-HA-36_R\ALCE_2015-1001572511_2_3600.x
Assessments: OK

Used test settings:


I-pn: 3600.0 A Location: Object:
I-sn: 1.0 A Company: OSAIS Manufacturer: ALCE
Rated burden: 30.0 VA / 0.8 Country: KSA Type: AR03
Operating burden: 30.0 VA / 0.8 Station: KHUDARIYAH Serial number: 2015-1001572511
Applied standard: IEC 61869-2 Feeder/Bay: HA36 Core number: 2
Core type (P/M): P Phase: R Tap: 3600
Class: 5P IEC-ID Optional:
ALF: 20.0 Ts:
f: 60.0 Hz max. Rct: 18.0 Ω

Resistance test: Burden test:


Rmeas (30°C): 12.0488 Ω Burden: cos φ: Z:
Rref (75°C): 14.0987 Ω Vmeas: Imeas:

Excitation test:
V-kn: 637.21 V I-kn: 0.011096 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A ALF: >23.6248 ALFi: 22.81 ALF: >23.6248 ALFi: 22.81
Ls: 0.02655H Lm: 273.7108 H Ts: 7.184s Ts: 7.184s
Kr: 59.22 %

Ratio test:
Ratio: 3600.0 : 0.99977 ε : -0.0228 % ∆φ: 0.24 min Polarity: OK N: 3598.76
εc : 0.0266 %

Excitation curve data


Excitation curve data

1000

100
Es / V

10

0.1
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0.8 -0.216 -0.082 -0.058 -0.042 -0.029 -0.023 -0.021 -0.016
15 VA/ 0.8 -0.166 -0.051 -0.031 -0.018 -0.009 -0.004 -0.003 0.000
7.5 VA/ 0.8 -0.126 -0.032 -0.016 -0.006 0.003 0.006 0.007 0.009
3.75 VA/ 1 -0.069 -0.013 -0.003 0.004 0.010 0.013 0.013 0.015
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0.8 4.834 1.260 0.790 0.520 0.298 0.240 0.375 0.193
15 VA/ 0.8 5.535 1.473 0.920 0.622 0.405 0.300 0.273 0.353
7.5 VA/ 0.8 6.183 1.609 1.012 0.699 0.470 0.364 0.340 0.278
3.75 VA/ 1 7.201 1.996 1.310 0.920 0.645 0.520 0.496 0.431
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200
1.00 1.00 1.00
-1.00 -1.00 -1.00
0.050

0.000
0 50 100 150 200 250
Current deviation [%]

-0.050
100% Load

50% Load
-0.100

25% Load

-0.150

-0.200

-0.250

% I-pn