General test information: Date/Time: 2017-06-06, 10:04:25 AM


Test device: CT-Analyzer Device Serial No.: EL074Z
File name: 2017\KHUDARIYAH-Commissioning\HA-36-BUS TIE-2\T073-HA-36_B\ALCE_2015-1001572512_1_3600.x
Assessments: OK

Used test settings:


I-pn: 3600.0 A Location: Object:
I-sn: 1.0 A Company: OSAIS Manufacturer: ALCE
Rated burden: 60.0 VA / 1 Country: KSA Type: AR03
Operating burden: 60.0 VA / 1 Station: KHUDARIYAH Serial number: 2015-1001572512
Applied standard: IEC 61869-2 Feeder/Bay: HA36 Core number: 1
Core type (P/M): P Phase: B Tap: 3600
Class: PX IEC-ID Optional:
f: 60.0 Hz max. Rct: 18.0 Ω Kx: 13.62

Resistance test: Burden test:


Rmeas (30°C): 14.01492 Ω Burden: cos φ: Z:
Rref (75°C): 16.39931 Ω Vmeas: Imeas:

Excitation test:
V-kn: 1040.195 V I-kn: 0.005581 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A Kx: 13.62 Kx: 13.62
Ls: Lm: 547.9035H Ts: 7.172s Ts: 7.172s
Kr: 87.95 %
required measured Assessments:
Ek: 800.0 V Ie: 0.03 A Ek: 1040.195 V Ie: 0.00558 A #N/A
E1, Vk1 400.0 V Ie1, Ik1 0.03 A Ie1 Ik1: 0.002 A #N/A

Ratio test:
Ratio: 3600.0 : 0.99937 ε : -0.0628 % ∆φ: 0.89 min Polarity: OK N: 3600.87
εt : 0.0241 %

Excitation curve data


Excitation curve data

10000

1000

100
Es / V

10

0.1
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
60 VA/ 1 -0.197 -0.104 -0.089 -0.078 -0.070 -0.063 -0.062 -0.061
30 VA/ 1 -0.171 -0.082 -0.069 -0.061 -0.054 -0.049 -0.048 -0.047
15 VA/ 1 -0.151 -0.070 -0.058 -0.051 -0.045 -0.043 -0.042 -0.040
7.5 VA/ 1 -0.138 -0.064 -0.053 -0.046 -0.041 -0.039 -0.038 -0.037
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
60 VA/ 1 9.485 2.628 1.684 1.105 0.679 0.890 0.833 0.660
30 VA/ 1 9.142 2.248 1.400 0.891 0.533 0.541 0.593 0.497
15 VA/ 1 8.936 2.038 1.223 0.766 0.437 0.306 0.276 0.378
7.5 VA/ 1 8.788 1.945 1.116 0.694 0.390 0.264 0.240 0.254
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200

0.000
0 50 100 150 200 250

-0.050
Current deviation [%]

100% Load
-0.100

50% Load

-0.150 25% Load

-0.200

-0.250

% I-pn