You are on page 1of 2

Company Name:

Company Address:

Order Number:

General test information: Date/Time: 2017-06-06, 10:29:22 AM


Test device: CT-Analyzer Device Serial No.: EL074Z
File name: UDARIYAH-Commissioning\HA-40-OG FEEDER BUS C\T032-HA-40_Y\ALCE_2015-1001509185_1_800.x
Assessments: OK

Used test settings:


I-pn: 800.0 A Location: Object:
I-sn: 1.0 A Company: OSAIS Manufacturer: ALCE
Rated burden: 30.0 VA / 0.8 Country: KSA Type: SA2D4H2
Operating burden: 30.0 VA / 0.8 Station: KHUDARIYAH Serial number: 2015-1001509185
Applied standard: IEC 61869-2 Feeder/Bay: HA40 Core number: 1
Core type (P/M): P Phase: Y Tap: 800
Class: 5P IEC-ID Optional:
ALF: 20.0 Ts:
f: 60.0 Hz max. Rct: 18.0 Ω

Resistance test: Burden test:


Rmeas (30°C): 4.83671 Ω Burden: cos φ: Z:
Rref (75°C): 5.65959 Ω Vmeas: Imeas:

Excitation test:
V-kn: 605.739 V I-kn: 0.014569 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A ALF: 22.99 ALFi: 22.06 ALF: 22.99 ALFi: 22.06
Ls: 0.0073351H Lm: 130.4196 H Ts: 4.397s Ts: 4.397s
Kr: 86.51 %

Ratio test:
Ratio: 800.0 : 0.99897 ε : -0.1026 % ∆φ: 0.61 min Polarity: OK N: 799.96
εc : 0.1059 %

Excitation curve data


Excitation curve data

1000

100

10
Es / V

0.1

0.01
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0.8 -0.530 -0.238 -0.186 -0.150 -0.118 -0.103 -0.099 -0.091
15 VA/ 0.8 -0.388 -0.160 -0.122 -0.096 -0.073 -0.062 -0.059 -0.054
7.5 VA/ 0.8 -0.273 -0.115 -0.083 -0.064 -0.047 -0.039 -0.037 -0.033
3.75 VA/ 1 -0.057 -0.052 -0.040 -0.032 -0.025 -0.021 -0.020 -0.018
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0.8 13.716 3.845 2.401 1.559 0.939 0.607 0.625 0.700
15 VA/ 0.8 13.796 3.667 2.284 1.474 0.909 0.647 0.590 0.453
7.5 VA/ 0.8 14.264 3.761 2.236 1.453 0.898 0.648 0.602 0.487
3.75 VA/ 1 16.377 4.529 2.862 1.932 1.254 0.962 0.901 0.764
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200
1.00 1.00 1.00
-1.00 -1.00 -1.00
0.000
0 50 100 150 200 250

-0.100
Current deviation [%]

-0.200
100% Load

50% Load
-0.300

25% Load

-0.400

-0.500

-0.600

% I-pn