Q1. A symmetrical short circuit occurs on the 22KV load bus bar. Find the fault apparent power and the
fault current. Choose a base of 150MVA. Also draw the reactance diagram
[1.91KA, 73MVA]
Q2. A 50 MVA, 11KV, 3 phase alternator was subjected to different types of faults. The fault currents
were: 3 phase fault 1870A,LL fault 2590A and SLG fault 4130A. The alternator is solidly grounded. Find
the per unit values of the 3 phase sequence reactances. [1.403, 0.351, 0.151]
Q3. A generator connected through a 5 cycle circuit breaker to a transformer, is rated 100MVA, 18KV
with 19%, 26% and 130% as sub- transient, transient and steady state reactances respectively. It is
operating under no load and rated voltage when a three phase short circuit occurs between the breaker
and transformer. Find:
(i) The sustained short circuit current [2467]
(ii) The initial rms current in the breaker [16882]
(iii) The maximum possible DC component of the short circuit current in the breaker
Q4.
[1430, 2000]