dT = 93 K
And
Ts = To + DT …………………….(4)
Where :
Ts = Smoke temp.
To =Ambient temp. = 303 K
Ts = 396 K
Ms Ts
V = ……………….(5)
To ps
Where :-
V = Required air volumetric flow rate
ps = Smoke density = 1.2 Kg/m3
V = 9.7 M3/Sec.
V = A X v ………………………….(8)
Where v = volumetric flow rate for one fan = 21,000 cfm
OR. v = volumetric flow rate for one fan = 9.7 M3/Sec.
A = duct cross sec. Area
V = desired air velocity in the duct = 6 M/Sec.
A = 1.62 M2
Static pressure ( in.wg) = 0.5 + duct friction loss
where duct friction loss = 0.5 in.wg
Total Static pressure ( in.wg) = 1 in.wg.
Conclusion :
System Description :
Exhaust Smoke Fans :
input the sugested fans
Nunmers: 2 Nos.
numbersFans/Zone
here .
Capacity: 10,500 cfmIf u (each)
put it as one it gives
Type : Tubilar ducted the total flow required .
Location : Roof Top
GENERAL
- All fans used in smoke management and exhaust system ( exhaust and fresh air fans )
shall be capable to withstand 200 oC temp.for 30 min.
- All fans shall be interconnected with fire allarm panel for automatic operation also, shall be
provided with ON /OFF switch near enterances for manual operation by occupants.
Mechanical Smoke Ventilation Calculations
For Basement Floor ( Store)
dT = 390 K
And
Ts = To + DT …………………….(4)
Where :
Ts = Smoke temp.
To =Ambient temp. = 303 K
Ts = 693 K
Ms Ts
V = ……………….(5)
To ps
Where :-
V = Required air volumetric flow rate
ps = Smoke density = 1.2 Kg/m3
V = 17.0 M3/Sec.
V = A X v ………………………….(8)
Where v = volumetric flow rate for one fan = 37,000 cfm
OR. v = volumetric flow rate for one fan = 17.0 M3/Sec.
A = duct cross sec. Area
V = desired air velocity in the duct = 6 M/Sec.
A = 2.83 M2
Static pressure ( in.wg) = 0.5 + duct friction loss
where duct friction loss = 0.5 in.wg
Total Static pressure ( in.wg) = 1 in.wg.
Conclusion :
System Description :
Exhaust Smoke Fans :
input the sugested fans
Nunmers: 2 Nos.
numbersFans/Zone
here .
Capacity: 18,500 cfmIf u (each)
put it as one it gives
Type : Tubilar ducted the total flow required .
Location : Roof Top
V = AXv ………………………….(8)
GENERAL
- All fans used in smoke management and exhaust system ( exhaust and fresh air fans )
shall be capable to withstand 200 oC temp.for 30 min.
- All fans shall be interconnected with fire allarm panel for automatic operation also, shall be
provided with ON /OFF switch near enterances for manual operation by occupants.
Left Well Pressurization fan For elevators . just inter the no.
of floors
Door Size :-
W = 0.8 M don’t touch it
H = 2.0 m formated cell
Qe = KAe (P)1/2
Where :
Ae = 0.003 x ( ( 2.0 + 0.8 ) x 2 ) + 2.0 x 32 = 0.73
K = 0.839
P = 50 Pascal.
Qe = 0.839 x Ae x (50)1/2
Where :-
A = Door Area
0.73 M2
Mechanical Ventilation Calculations
For Car Park ( Basement )
Fan selection
according to plane (or the
Fan Capacity = 13200 cfm posibility to install many
No. of fans = 4 nos. fans nos. of fans to reduce the
cap. Of the fan .
CONCLUSION
System Discription :
Exhaust Smoke Fans :
Nunmers: 4 Nos. Fans
Capacity: 13,200 cfm (each)
Type : Tubilar ducted
Location : ………………………………………….
Mechanical Smoke Ventilation Calculations
For …………………………………
WHERE :-
THEN :-
M f = 5193.05
3
2/3
2/3
Stair Case Pressurization For Internal Stairs .
Door Size :-
W = 0.8 M
H = 2.0 m
Qe = KAe (P)1/2
Where :
Ae = 0.003 x ( ( 2.0 + 0.8 ) x 2 ) + 2.0 x 8= 0.18
K = 0.839
P = 50 Pascal.
Qe = 0.839 x Ae x (50)1/2
Where :-
A = Door Area
V = Air Velocity = 0.75 m/sec.
Af = Area Factor = 0.6
= 4236 CFM
Conclusion :
System Description :
Left Well Pressurization fan For elevators .
Qty. : 1 Nos. Fan/stair case
Capacity : 4,300 cfm (each)
Type : Tube Axial Fan
Location : stair case Roof
1- Provide one no. fresh air pressurized fan located on each stair case roof
of 4,300 CFM & 1.5 In.wg.
2- Provide deffrential pressure sensor at the midlle way of stair case high and interface
with fan control panel .
0.18 M2
MECHANICAL DEPARTMENT.
DESCRIPTION VALUE
ALCULATION *
UNIT I/O
CAR INPUT
FT INPUT
M² INPUT
FT² OUTPUT
SEC RECOMMENDED
PPM RECOMMENDED
% RECOMMENDED
CAR OUTPUT
GAL/HR AVERAGE
g/hr.ft² OUTPUT
g/hr.ft² RECOMMENDED
- OUTPUT
CFM/FT²-S RECOMMENDED
CFM/FT² OUTPUT
ACH OUTPUT
CFM OUTPUT
IN" W INPUT
HP OUTPUT
CALCULATED BY :
PROJECT :
1- ASSUMPTION
- Ambient Temperature = 115 F
- Max. Allowed Temp. Rise = 10.8 F
- Sub- Station Ref. No. 1
- Number Of Transformers = 1 Nos.
- Transformer Rateing = 1000 KVA
- Number Of Transformers = 0 Nos.
- Transformer Rateing = 1000 KVA
- Power Factor = 0.8
- Transformer Eff. = 0.98
2- CALCULATION
Heat Loss / Transformer
=( 1 x 1000 + 0 x 1000 )x 0.8 x (1 - 0.98 )
= 16 KW
= 16000 Watt
Number of fans = 1
Fan Capacity / Each = 4,682 = CFM
Fan rating KW/Each = 1.11 KW
Fan st. Pressure = 1 IN.WG
GENERATOR ROOM VENTILATION CALCULATION
H
Ventilating air (cu.m/min.) = + Engine Combustion Air
D x SH x Dt
Where :-
H = Total Heat Radiation in (KW) (for engine + generator)
H = 125.5 KW (Ref. To specs. Sheet)
V = Ventilating air (cu.m/min.)
D = Density of air (kg/m3)
= 1.07 At 54 deg. C
SH = Specific heat of air ( kw.min/Kg.C)
= 0.017
dT= Temp. Rise inside engine room ( deg.C)
= 10 deg.C
ECA = Engine Combustion Air (Exhaust gas flow )
= 120 cu.m/min (Ref. To specs. Sheet)
7,182 cu.m/hr.
THEN :-
125.5
Ventilating air (V) = + 120
1.07 x 0.017 x 10
V = 810 cu.m/min
V = 28,564 cu.ft/min.
Important Notes :-
1- clean , cool , dry air circulates around the switchgear , flows through the rear of the generator , across
the engine , and discharges through the radiator
2- Cool air shoul always be available for the engine air cleaner (air filter ).
3- For best ventilation results , air should flow first across the generator then to both sides of the engine .
4- Inlets located at the end of the room will provide adequate ventilation only to the engine nearast the
inlet.
5- Air flow restriction should be 0.5 inch W.G
the generator , across