Professional Documents
Culture Documents
Fault Current Calculation PDF
Fault Current Calculation PDF
FOR CALCULATION
1 In the calculation only three phase symmetrical fault has been considered.
2 A simplified procedure for calculating the symmetrical short circuit current called the E/X method is used,
which disregards all resistance,all static load and all prefault current.
4 Since X/R ratio of the effective impedance at the bus is unknown,It si considered that the calculated current
should not more than 80% of the allowed valve for the breaker at the existing bus voltage.
5 Motor Contribution has been considered as 2 times the rated current of HT motors and negligible in case of LT motors.
7 The distribution transformers in different load centres of the plant shall operate in isolation and not in parallel.
2 DESIGN DATA :
a Utility fault level at plant grid = 600 MVA
b Base MVA chosen = 25 MVA
c) Distribution Transformer
1 Rated capacity = 3.15 MVA
2 Voltage at HT side = 11 KV
3 Voltage at LT side(full load) = 0.380 KV
4 Percentage impedance = 8 %
d) Rating of HT motors‐
1 HT motor rating = 4150 Kw
2 Motor Power factor = 0.85 red
3 Motor efficiency = 0.95 %
4 Maximum starting torque considered for = 200 % FLT
the motor at 11kv
5 Maximum Running torque considered for = 100 % FLT
the motor at 11kv
Cable Size XLPE,Armoured 240 Sqmm
Cable no of run 5 No.
5 HT motor fed from cable = 0.23 ohm/km
5Rx3x240Sqmm XLPE CU (Z)
6 HT motor fed from cable length = 150 ohm/km
e) Rating of LT motors‐
1 LT motor rating = 350 Kw
2 Motor Power factor = 0.85 red
3 Motor efficiency = 0.90 %
4 Maximum starting torque considered for = 200 % FLT
the motor at 11kv
4 Maximum Running torque considered for = 100 % FLT
the motor at 11kv
Cable Size XLPE,Armoured 1.5 Sqmm
Cable no of run 1 No.
5 LT motor fed from cable = 0.020 ohm/km
3Rx4x300Sqmm XLPE CU (Z)
6 LT motor fed from cable Length = 70 mtr
A FAULT CURRENT CALCULATION FOR HT (UP TO NEAREST MOTOR TERMINAL FROM SOURCE)
Square (33)
= ohm
500
ZO = 2.178 ohm
1.1 x 33
= kA
√ 3 X 2.178
IFO = 9.62 kA
Xa = 0.150 ohm
Za = 0.2460 ohm
2.4 Total Impedance at 33KV SWGR at Substation‐1(Z1) = Za + Zo
Z1 = 2.425 ohm
2.5 Fault Current at 33KV SWGR at Proposed Substation (IF1) 1.1 X KV
= kA
√ 3 X Z1
( 1.1 X 33)
kA
(√ 3 X 2.425)
Selected Fault KA at 33KV Bus
IF1 = 8.643 kA 25 kA
Xb = 0.0025 ohm
Z2 = 2.430 ohm
( 1.1 X 0.15)
= kA
(√ 3 X 2.43)
IF2 = 8.625 kA
2
Zc (8.35/100) x 6.6) ohm
=
(8000/1000)
Zc = 0.455 ohm
Z3 = 0.553 ohm
( 1.1 X X x L)
= kA
(√ 3 X 0.553)
IF3 = 7.580 KA
Rd = 0.001075 ohm
5.2 Reactance of cable (X) (Reactance/Km) = 0.0830 ohm/Km
Xd = 0.000691667 ohm
2 2
5.3 Impedance of Cable (Zd) = √(Rd + Xd ) ohm
Zd = 0.0013 ohm
Z4 = 0.555 ohm
( 1.1 X )
= kA
(√ 3 X 0.555)
Re = 0.04752 ohm
6.2 Reactance of cable (X) (Reactance/Km) = 0.0890 ohm/Km
Xe = 0.01602 ohm
Ze = 0.0501 ohm
Z5 = 0.606 ohm
( 1.1 X X x L)
= kA
(√ 3 X 0.606)
IF5 = 6.917 kA
3 PU IMPEDANCES OF VARIOUS EQUIPMENT/SYSTEMS:
1 Base MVA chosen = 25 MVA
2 PU impedance of Utility (Base MVA) 25
= =
(Utility MVA) 600
= 0.041667 Pu
(Base MVA) x (Percentage Impedance)
=
3 PU Impedance of equipment ( Equipment MVA)
25 x ( 8/ 100 )
=
3.15
i) Distribution transformer(3.15 MVA) = 0.634921 Pu
iv) Voltage drop upto 4150kW motor terminals= (1.6839 + 0.097) = 1.78 %
Conclusion
Higher starting torque,however,can be achived by adjustment of electrolyte strength of LRS.
For starting of 4150 kw motor,the starting surrent have to be resticted to less than 200 % Even with above
assumption the voltage drop is 1.78 %
iv) Voltage drop upto 4150kW motor terminals= (1.6839 + 0.097) = 1.78 %
Conclusion
Higher starting torque,however,can be achived by adjustment of electrolyte strength of LRS.
For Running of 0.9 kw motor,the starting surrent have to be resticted to less than 0 % Even with above
assumption the voltage drop is 1.78 %
v) Voltage drop upto 350kW motor terminals = (0.15 + 0.44 +2.26) = 2.85 %
v) Voltage drop upto 3.15kW motor terminals = (0.08 + 0.23 +1.16) = 1.47 %
695.13
( x 0.02 x 70)
Voltage drop of the selected cable = 1
= 16.43 V
Voltage drop of the selected cable = 16.43
x 100
(380 / √3 )
= 2.50 %
The starting KVA of motors is calculated as:
For squirrel cage induction motors = Kw x 6
Starting KVA Efficiency x Power factor
= (k W x 6)
(0.9 x 0.85)
= kw X 7.84
= 2745.098 KVA