Appendix A

Firmware and Manual Versions

Firmware
Determining the Firmware Version in Your Meter
To find the firmware version number in your SEL-734 Meter, view the status report through use of the serial port
STAT command or the front-panel STATUS pushbutton.
The firmware revision number is after the R and the release date is after the D. For example, the following is
firmware revision number 100, release date May 5, 2003.
FID=SEL-734-R100-V0-Z001001-D20030505
Table A.1 lists the firmware versions, a description of modifications, and the instruction manual date code that
corresponds to firmware versions. The most recent firmware version is listed first.

Table A.1 Firmware Revision History (Sheet 1 of 6)

Manual
Firmware Identification (FID) Number Description of Changes
Date Code

Form 5 Meter ➤ Corrected issue with firmware upgrades where user settings could be 20090319
SEL-734-R529-V0-Z012011-D20090319 lost.
Form 9 Meter ➤ Corrected issue with LDP timestamp when IRIG is connected.
SEL-734-R129-V0-Z012011-D20090319 ➤ Improved response time of contact inputs when ac is applied.
Form 5 Meter ➤ Added support for DNP3 LAN/WAN. 20090108
SEL-734-R528-V0-Z012011-D20090108 ➤ Added a second independent user map for DNP.
Form 9 Meter ➤ Improved communications reliability of DNP with an updated
SEL-734-R128-V0-Z012011-D20090108 library.
➤ Improved the MV-90 communications interface for faster read times
and to maintain engineering access.
➤ Added FILE READ and FILE SHOW support for LDP data.
➤ Changed port PROTO setting option from MV-90 to MODM (Mod-
bus over Modem).
➤ Added HHF and CSV file export capability.
➤ Added VSSI and LDP graphing capability.
➤ Allow demand, peak demand, and energy reset through DNP.
➤ Support math variables in Display Points.
➤ Added three dedicated settings for improved front-panel and serial
port scaling.
➤ LDP data retrieved via LDP command and DNP now in
secondary quantities to match Modbus.
➤ LDP records are no longer affected by a change in CTR or PTR.
➤ Improved Ethernet communications with 10/100MB autonegotiate.
➤ Improved accuracy of demand calculated from energy consumed in a
LDP interval.
➤ Corrected the behavior of TOU demand values when aliased in
Display Points.

Date Code 20090319 Instruction Manual SEL-734 Meter


A.2 Firmware and Manual Versions
Firmware

Table A.1 Firmware Revision History (Sheet 2 of 6)

Manual
Firmware Identification (FID) Number Description of Changes
Date Code

Form 5 Meter ➤ Added IEC 61000-4-15 Flicker. 20080805


SEL-734-R526-V0-Z011010-D20080805 ➤ Added magnitudes, angles, and active power to the 50th
Form 9 Meter harmonic. Accuracy compliant with IEC 61000-4-7.
SEL-734-R126-V0-Z011010-D20080805 ➤ Added a second load profile recorder.
➤ Enhanced event reporting capabilities.
➤ Increased memory for load profile and event reporting.
➤ Modified ID and VER commands to reflect increased memory.
➤ Added modem dial-out on event trigger.
➤ Added voltage and frequency deviation quantities.
➤ Added VSSI to DNP.
➤ Increased number of TOU self reads from 6 to 15.
➤ Added daily repeating functions for TOU.
➤ Modified DNP and Modbus to include new quantities.
➤ Corrected communications issue with SUBNET Solutions® SSNET
software when SER settings contain a 0 or NA.
Form 5 Meter ➤ Added support for a Class 2 CT card. 20080313
SEL-734-R525-V0-Z010009-D20080313 ➤ Improved Load Profile Data recording when adjusting time across
Form 9 Meter one interval boundary.
SEL-734-R125-V0-Z010009-D20080313 ➤ Corrected IG stability in the VSSI report.
Form 5 Meter ➤ Improved reliability of DNP communications over Port 2 and Port F. 20071207
SEL-734-R524-V0-Z010009-D20071207 ➤ Corrected timestamps on LDP records to improve MV-90 reads.
Form 9 Meter
SEL-734-R124-V0-Z010009-D20071207
Form 5 Meter ➤ Prevented possibility of meter disabling when modifying Port 4 set- 20071019
SEL-734-R523-V0-Z010009-D20071019 tings.
Form 9 Meter
SEL-734-R123-V0-Z010009-D20071019
Form 5 Meter ➤ Enhanced Synchrophasor performance. 20070920
SEL-734-R522-V0-Z010009-D20070920 ➤ Corrected Device Time Synchronization via DNP.
Form 9 Meter ➤ Corrected potential Peak Demand discrepancy between Load Profile
SEL-734-R122-V0-Z010009-D20070920 and Time-of-Use.
➤ Corrected issue with Load Profile lookup via Modbus/MV-90
protocol.
➤ Corrected potential MV-90 protocol lockout.
➤ Added ability to enable/disable certain Fast Messages.
Form 5 Meter ➤ Added Load Profile data to DNP. 20070521
SEL-734-R521-V0-Z009008-D20070521 ➤ Expanded LDAR setting range to include 1-minute Load Profile
Form 9 Meter acquisition rate.
SEL-734-R121-V0-Z009008-D20070521 ➤ Expanded DMTC setting range to include a 1-minute demand time
constant.
➤ Reordered Test Mode quantities to make MWH3I the default test
quantity.
➤ Corrected Time-of-Use processing when time is changed or IRIG-B
is connected.
➤ Corrected per-point scaling on DNP counters.
➤ Corrected Load Profile DST flag when the Meter loses power.
➤ Corrected Modbus and MV-90 SER number reporting when SER >
512 records.

SEL-734 Meter Instruction Manual Date Code 20090319


Firmware and Manual Versions A.3
Firmware

Table A.1 Firmware Revision History (Sheet 3 of 6)

Manual
Firmware Identification (FID) Number Description of Changes
Date Code

Form 5 Meter ➤ Added support for new analog output, digital output card. 20070312
SEL-734-R520-V0-Z008008-D20070312 ➤ Added Remote Analogs to SELOGIC for support of analog outputs.
Form 9 Meter ➤ Added Analog Output Objects, 40 and 41, to DNP for support of
SEL-734-R120-V0-Z008008-D20070312 Remote Analogs.
➤ Added TEST MODE command to ACSELERATOR QuickSet and
SEL ASCII protocol.
➤ Corrected front-panel default labels for VARh and VAh.
➤ Added ESPH setting to enable/disable synchrophasors.
➤ Changed SSI, LDP, and SER reports to indicate invalid data for
records with a checksum error.
➤ Changed flagging for time/date changes in load profile when IRIG-B
is used.
➤ Changed ACSELERATOR QuickSet support to disallow a setting of
NA for FLTBLK.
➤ Added ACSELERATOR QuickSet support for DNP External Modem
Settings on Port 2.
➤ Adjusted LDP report column spacing to accommodate more digits.
➤ Modified SER to report Daylight Saving Time changes.
➤ Changed low battery warning level from 2.8 Vdc to 2.3 Vdc.
➤ Changed low battery voltage condition to provide a HALARM warn-
ing pulse instead of clearing the ENABLE Meter Word bit.
➤ Eliminated power supply warnings from meter self-test.
➤ Corrected Ethernet session initialization conflict.
➤ Corrected DNP lock-up susceptibility on Port F and Port 2.
Form 5 Meter ➤ Improved crest factor metering issue. 20060919
SEL-734-R518-V0-Z007007-D20060919 ➤ Added MAC address to VER command.
Form 9 Meter ➤ Added settable Watt/VAR cutoff point.
SEL-734-R118-V0-Z007007-D20060919 ➤ Added per-point scaling on DNP counters.
➤ Added frozen DNP counters—optional: object 21, 23.
➤ Added MV-90-specific protocol port settings.
➤ Added harmonic magnitude report and SELOGIC® values.
➤ Corrected Telnet timeout issue (returns to ACC level 0).
➤ Added fractional XFTR setting for Transformer Line Loss Compen-
sation.
➤ Improved flagging of time/date changes in load profile report.
➤ Added Fast Messages:
20ENERGY
20DEM4Q
20PEAK4Q
20MET4Q
Form 5 Meter ➤ Added support for Time-of-Use metering. 20060519
SEL-734-R517-V0-Z006006-D20060519 ➤ Added Programmable Demand Reset.
Form 9 Meter ➤ Enhanced response to large front-panel settings files.
SEL-734-R117-V0-Z006006-D20060519 ➤ Enabled CTR/PTR settings changes with KYZ enabled.
➤ Added real and imaginary components to SELOGIC.
➤ Enhanced settings reads over long-distance Ethernet connection.
➤ Corrected TEST mode time-out.
➤ Corrected Volt-hour scaling.
➤ Enhanced TLL settings.
➤ Added MATH command.

Date Code 20090319 Instruction Manual SEL-734 Meter


A.4 Firmware and Manual Versions
Firmware

Table A.1 Firmware Revision History (Sheet 4 of 6)

Manual
Firmware Identification (FID) Number Description of Changes
Date Code

Form 5 Meter ➤ Manual update only—see Table A.2 for a summary of 20060420
SEL-734-R516-V0-Z005001-D20060131 manual changes.
Form 9 Meter
SEL-734-R116-V0-Z005001-D20060131
Form 5 Meter ➤ Corrected modem disconnect/VSSI conflict. 20060131
SEL-734-R516-V0-Z005001-D20060131
Form 9 Meter
SEL-734-R116-V0-Z005001-D20060131
Form 5 Meter ➤ Correct synchrophasor dropped packets. 20051118
SEL-734-R515-V0-Z005001-D20051118 ➤ Saving Port 1 settings always restarts meter.
Form 9 Meter
SEL-734-R115-V0-Z005001-D20051118
Form 5 Meter ➤ Prevented possibility of meter disabling after a settings change. 20051027
SEL-734-R514-V0-Z005001-D20051027 ➤ Ensured synchrophasor feature always responds to enable messages.
Form 9 Meter
SEL-734-R114-V0-Z005001-D20051027
Form 5 Meter ➤ Corrected contact input response to ac voltage. 20051003
SEL-734-R513-V0-Z005001-D20051003
Form 9 Meter
SEL-734-R113-V0-Z005001-D20051003
Form 5 Meter ➤ Added Meter Gain Adjustment settings. 20050817
SEL-734-R512-V0-Z005001-D20050817 ➤ Increased the range of the SET E command.
Form 9 Meter ➤ Corrected Compressed Event Report header format error.
SEL-734-R112-V0-Z005001-D20050817 ➤ Enhanced Configurable Display Points.
➤ Added signed VAR through Modbus.
➤ Enhanced SEL-5601 support of Raw Event Report.
➤ Allow field change of Meter form.
➤ Added multiple, simultaneous Modbus TCP/Telnet sessions.
➤ Added additional energy registers to Modbus map.
➤ Added Quadrant Bits to Meter Word bits.
➤ Corrected VAR quadrant accumulation error when at zero Power Factor.
➤ Added support for COMTRADE-formatted Event Reports.
Form 5 Meter ➤ Corrected possible error condition when reading event reports. 20050617
SEL-734-R511-V0-Z004001-D20050617
Form 9 Meter
SEL-734-R111-V0-Z004001-D20050617

SEL-734 Meter Instruction Manual Date Code 20090319


Firmware and Manual Versions A.5
Firmware

Table A.1 Firmware Revision History (Sheet 5 of 6)

Manual
Firmware Identification (FID) Number Description of Changes
Date Code

Form 5 Meter ➤ Fixed rollover in Modbus® energy registers. 20050427


SEL-734-R510-V0-Z004001-D20050427 ➤ Improved Ethernet communication over large networks.
Form 9 Meter ➤ Improved calculations for THD reporting.
SEL-734-R110-V0-Z004001-D20050427 ➤ Corrected RAM Failure when using Ethernet on high-traffic network.
➤ Corrected TLL selection when in TEST mode.
➤ Corrected the need for power reset when changing from 232 to
modem on Port 4.
➤ Added part number support for future power supply option.
➤ Improved handling of DNP map during firmware upgrade.
➤ Added AT string for setting of internal modem.
➤ Corrected VSSI/Event report conflict.
➤ Fixed SELOGIC® counters handling of default NA values.
➤ Added Energy cut-off point.
➤ Added fractional CTR/PTR settings.
➤ Extended maximum front panel time-out setting (FP_TO) to 120
minutes.
➤ Changed VBASE default setting to 120 V.
➤ Added additional KYZ/Test Mode settings (KEn_UNITS,
KEn_SCALE, and KET).
➤ Added RESET button local bit.
➤ Added Date and Time of peak demand (MET D T).
➤ Provided field upgrade path from R108 to R110.
Form 5 Meter ➤ Manufacturing process improvements. 20041111
SEL-734-R509-V0-Z003001-D20041111 Note: Rewrites calibration constants and must be installed at SEL.
Form 9 Meter
SEL-734-R109-V0-Z003001-D20041111
Form 5 Meter ➤ Add energy registers to DNP counter objects. 20040915
SEL-734-R508-V0-Z003001-D20040915 ➤ Fix Software Flow Control with SEL-2032/2030/2020
Form 9 Meter Communications Processors.
SEL-734-R108-V0-Z003001-D20040915 ➤ SSI Reporting Improvements.
➤ Correct error in Math Variable processing.
➤ Improve operation of modem at speeds below 9600 bps.
➤ Correct harmonic trigger oscillation.
➤ Correct MV-90 LDP multiple request issue introduced in R107/R507.
Form 5 Meter ➤ Change TLL Inputs. 20040511
SEL-734-R507-V0-Z003001-D20040511 ➤ Add Precision to Ke Setting.
Form 9 Meter ➤ Correct RESET pushbutton functionality in TEST Mode.
SEL-734-R107-V0-Z003001-D20040511
Form 5 Meter ➤ Manual update only. See Table A.2 for a summary of manual updates. 20040224
SEL-734-R506-V0-Z002001-D20040213
Form 9 Meter
SEL-734-R106-V0-Z002001-D20040213
Form 5 Meter ➤ Resolve Ethernet and Test Mode Conflict. 20040213
SEL-734-R506-V0-Z002001-D20040213
Form 9 Meter
SEL-734-R106-V0-Z002001-D20040213
Form 5 Meter ➤ Enable VB_RMS, VC_RMS on display points. 20040130
SEL-734-R505-V0-Z002001-D20040130 ➤ Enable Date, Time, and Date/Time on display points.
Form 9 Meter ➤ Enable DST support for Southern Hemisphere.
SEL-734-R105-V0-Z002001-D20040130 ➤ Improved metering accuracy in reverse power flow conditions.
➤ Enable single-phase calibration testing of Form 5 meters.

Date Code 20090319 Instruction Manual SEL-734 Meter


A.6 Firmware and Manual Versions
Instruction Manual

Table A.1 Firmware Revision History (Sheet 6 of 6)

Manual
Firmware Identification (FID) Number Description of Changes
Date Code

Form 5 Meter ➤ Resolve DNP and Test Mode conflict. 20031103


SEL-734-R504-V0-Z001001-D20031101 ➤ Release SELBOOT R101, which allows firmware uploads on Port 3.
Form 9 Meter ➤ Set PMDOK bit when phasor data is valid.
SEL-734-R104-V0-Z001001-D20031101
Form 5 Meter ➤ Limits password string length to eight characters. 20030825
SEL-734-R503-V0-Z001001-D20030825
Form 9 Meter
SEL-734-R103-V0-Z001001-D20030825
Form 5 Meter ➤ Initial version. 20030730
SEL-734-R502-V0-Z001001-D20030730
Form 9 Meter
SEL-734-R102-V0-Z001001-D20030730

Instruction Manual
The date code at the bottom of each page of this manual reflects the creation or revision date.
Table A.2 lists the instruction manual release dates and a description of modifications. The most recent instruction
manual revisions are listed at the top.

Table A.2 Instruction Manual Revision History (Sheet 1 of 7)

Revision
Summary of Revisions
Date

20090319 Appendix A
➤ Updated for firmware version R129/R529.
20090108 Preface
➤ Added FCC Class A Warning text under Laser section.
Section 1
➤ Added ERCOT and CFG G0000-48-1999 Certification compliant statements.
Section 3
➤ Removed specific ACSELERATOR QuickSet information and replaced with installation information.
Section 4
➤ Added AVG to I and V RMS entry in Table 4.1: Metering Quantity Definitions.
➤ Added reset Via Remote Bits and DNP section under Demand Metering and Energy Metering.
➤ Modified interfaces information in Energy Interfaces subsection.
➤ Modified Load Profile Report content.
➤ Added Load Profile Retrieval Using File Transfer section.
➤ Added Starting/Stopping daylight saving strings definition.
➤ Added Table 4.21: SEL-734 Load Profile Record Response.
➤ Added Table 4.23: Record Type 0065-Present Values.
➤ Added Table 4.24: Record Type 0066-Meter Status.
➤ Added Table 4.25: Record Type 0067-LDP Status.
➤ Added Table 4.26: Status Nibble Definitions.
➤ Added Table 4.27: Record Type 0068-SER Data.
➤ Added Table 4.28: Record Type 0069-LDP Error.
Section 5
➤ Changed Self Read number to 15.
➤ Added Rated Demand or Energy topic.

SEL-734 Meter Instruction Manual Date Code 20090319


Firmware and Manual Versions A.7
Instruction Manual

Table A.2 Instruction Manual Revision History (Sheet 2 of 7)

Revision
Summary of Revisions
Date

Section 6
➤ Added Event Analysis information from the previous Section 12 "Analyzing Events."
Section 8
➤ Corrected Primary and Secondary indications in description following Equation 8.1.
➤ Deleted Extra Details for Displaying Metering Values on the Rotating Default Display.
Section 9
➤ Added Meter Word Bits RSTDEM, RSTPKDM, and RSTENGY to Table 9.3: SEL-734 Meter Word Bits.
➤ Update Front-Panel Settings and Rollover discussions.
Settings Sheets
➤ Added ASCII Report Settings.
➤ Added Remote Reset Equation Settings.
➤ Modified Set F Front-Panel Display Settings.
➤ Removed example command screen captures.
Section 10
➤ Modified Ethernet port connector and communications cables discussion.
➤ Modified Figure 10.3: Ethernet Port Status LEDs to show changes.
➤ Removed example command screen captures.
Section 11
➤ Removed Main Menu > Events, Main Menu > Targets details.
➤ Removed Figure 11.14: Set/Show > Meter Function.
➤ Renamed Figure 11.15: to Set/Show > Meter Function.
➤ Removed Figure 11.17: Set/Show > Date/Time Function.
➤ Removed Figure 11.19: Save Settings Changes.
➤ Removed Main Menu > Status details.
Appendix A
➤ Updated for firmware version R127/R527.
Appendix B
➤ Removed appendix Firmware Upgrade Instructions.
➤ Renumbered SEL Distributed Port Switch Protocol (LMD) to Appendix B (formerly Appendix C).
Appendix C
➤ Renumbered SEL Communications Processor to Appendix C (formerly Appendix D).
Appendix D
➤ Renumbered Setting SELOGIC Control Equations to Appendix D (formerly Appendix E).
Appendix E
➤ Renumbered Distributed Network Protocol to Appendix E (formerly Appendix F).
Appendix F
➤ Renumbered Modbus RTU Communications Protocol to Appendix F (formerly Appendix G).
➤ Added Figure F.1: Example Decimal Enumeration to demonstrate example of decimal enumeration.
➤ Added Table F.25: Load Profile Record Status Bits.
➤ Added Table F.26: Load Profile Status Enumeration.
Appendix G
➤ Renumbered MIRRORED BITS Communications to Appendix G (formerly Appendix H).
Appendix H
➤ Renumbered Analog Quantities to Appendix H (formerly Appendix I).
Appendix I
➤ Renumbered Optional Internal Modem Information to Appendix I (formerly Appendix J).

Date Code 20090319 Instruction Manual SEL-734 Meter


A.8 Firmware and Manual Versions
Instruction Manual

Table A.2 Instruction Manual Revision History (Sheet 3 of 7)

Revision
Summary of Revisions
Date

Glossary
➤ Added ASCII report scaling to the Global Settings definition.
20080805 Preface
➤ Changed the name from SEL-734 Revenue Metering System to SEL-734 Advanced Metering System to better
communicate the new Power Quality features.
Section 1
➤ Modified Table 1.3: SEL-734 Model Numbers to reflect new ordering options.
➤ Added Table 1.4: SEL-734 Feature Availability to describe differences between part numbers.
➤ EPMU no longer disables harmonic calculations.
➤ Updated specifications regarding harmonics.
➤ Added specifications for IEC 61000-4-15 Flicker.
Section 3
➤ Updated Part Number selector in Quickset.
➤ Updated Table 3.2: HMI Tree Functions, with Flicker and Synchrophasors.
Section 4
➤ Added information about new Harmonic Metering features.
➤ Added information about second Load Profile recorder.
Section 5
➤ Minimum TOU rate interval now one minute.
➤ Now 15 pairs of self-read register blocks.
Section 7
➤ EMPU no longer disables harmonic calculations.
Section 9
➤ Added NEWEVNT Meter Word bit for use with Modem dial-out feature.
Settings Sheets
➤ Added new settings for event reporting.
➤ Added new settings for second load profile recorder.
➤ Added new Modem protocol settings.
Section 10
➤ Updated command definitions for event reporting.
➤ Added MET FL command for Flicker Metering.
➤ Updated command definitions for harmonic metering.
➤ Updated MET command to include Voltage and Frequency Deviation values.
➤ Modified LDP command for second recorder.
➤ Updated SEL-734 Meter Command Summary.
Section 12
➤ Updated for new event reporting capabilities.
Appendix A
➤ Updated for firmware version R126/R526.
Appendix F
➤ Added VSSI to DNP.
➤ Added new harmonic quantities to DNP.
➤ Added new Flicker quantities to DNP.
➤ Added second load profile recorder to DNP.
Appendix G
➤ Added new harmonic quantities to Modbus.
➤ Added new Flicker quantities to Modbus.
➤ Added second load profile recorder to Modbus.

SEL-734 Meter Instruction Manual Date Code 20090319


Firmware and Manual Versions A.9
Instruction Manual

Table A.2 Instruction Manual Revision History (Sheet 4 of 7)

Revision
Summary of Revisions
Date

Appendix I
➤ Updated Analog Quantities table with new harmonic values and new flicker values.
20080313 Section 1
➤ Updated Table 1.3, SEL-734 Model Numbers with outdoor enclosure and CL2 ordering options.
➤ Updated Revenue Accuracy, AC Current Inputs, and Certifications portions in Specifications.
Section 2
➤ Updated Table 2.4, Optical Port Probes.
Section 4
➤ Added CL2 amp information for FAULT Meter Word bit in Maximum/Minimum Metering Elements.
Settings Sheets
➤ Added note to Harmonic Trigger Settings.
Section 10
➤ Updated Table 10.10, Secondary Voltage and Current with CL2 information.
Section 13
➤ Added troubleshooting possibility to All Front-Panel LEDs Dark subsection.
➤ Added actions when meter power is cycled to Information Lost During Power Cycle.
Appendix A
➤ Updated for firmware version R125/R525.
Appendix G
➤ Updated note in the Energy Metering portion of Table G.23: Modbus Register Map.
➤ Added Pri notation to addresses 1152–1246.
20071207 Appendix A
➤ Updated for firmware version R124/R524.
20071019 Section 1
➤ Removed Surge Immunity Exception from ANSI C12.20 certification in Specifications.
Appendix A
➤ Updated for firmware version R123/R523.
20070920 Section 1
➤ Updated Synchronized Phasor Measurement accuracy information in Specifications.
➤ Extended published range of ac voltage inputs for revenue metering in Specifications.
➤ Modified Certifications section to reflect performance improvements in Specifications.
Section 3
➤ Added Passwords and Security section.
Section 4
➤ Added Metering Calculations section.
➤ Added information about the new MET PM command.
➤ Described the behavior of harmonic quantities when synchrophasors are enabled.
➤ Added a 1-minute option to the LDAR setting.
Section 7
➤ Modified to reflect new synchrophasor performance.
Section 8
➤ Added accuracy information for the analog output options card.

Date Code 20090319 Instruction Manual SEL-734 Meter


A.10 Firmware and Manual Versions
Instruction Manual

Table A.2 Instruction Manual Revision History (Sheet 5 of 7)

Revision
Summary of Revisions
Date

Section 9
➤ Added information about the new FMR1, FMR2, FMR3, and FMR4 settings.
➤ Corrected the range of the PREDAL setting.
➤ Added a 1-minute option to the LDAR setting.
➤ Described the behavior of harmonic quantities when synchrophasors are enabled.
➤ Added the TSTYPE setting (for use with synchrophasors).
➤ Changed ESPH setting name to EPMU.
Section 10
➤ Clarified the behavior of Access Level E commands.
➤ Added information about the MET H command behavior when synchrophasors are enabled.
➤ Added MET PM command to Meter Command Summary.
Section 12
➤ Added information about Auto Messages.
Appendix A
➤ Updated for firmware version R122/R522.
Appendix D
➤ Added information about the new FMR1, FMR2, FMR3, and FMR4 settings.
Appendix F
➤ Clarified scaling on analog inputs.
Appendix G
➤ Added a 1-minute option to the LDAR setting in Table G.23.
➤ Clarified behavior of communications counters.
Appendix I
➤ Described the behavior of harmonic quantities when synchrophasors are enabled.
Command Summary
➤ Added MET PM command.
20070515 Section 1
➤ Updated Table 1.2 and Table 1.3 to reflect new Horizontal/Vertical option.
➤ Updated Figure 1.2.
➤ Added new Type Test Information and Certifications in Specifications section.
Section 2
➤ Updated Figure 2.1.
➤ Modified description under Meter Mounting subsection.
➤ Added Figure 2.2.
➤ Added Figure 2.4.
Section 4
➤ Moved and updated Table 4.1.
➤ Corrected Figure 4.1.
➤ Modified Table 4.2.
➤ Modified Table 4.6.
➤ Added Table 4.9.
Section 12
➤ Updated Table 12.1.
Appendix B
➤ Added Meter Form Configuration to the Firmware Upgrade Instructions.

SEL-734 Meter Instruction Manual Date Code 20090319


Firmware and Manual Versions A.11
Instruction Manual

Table A.2 Instruction Manual Revision History (Sheet 6 of 7)

Revision
Summary of Revisions
Date

Appendix F
➤ Added DNP object descriptions to the Overview section.
➤ Added Load Profile section.
➤ Updated Table F.1, Table F.2, Table F.5, and Table F.6.
➤ Added Table F.3.
➤ Updated Point Remapping section.
Setting Sheets
➤ Updated Analog Output Settings.
➤ Modified DMTC range.
Appendix I
➤ Updated footnotes in Table I.1.
Command Summary
➤ Added EVE C, EVE C R, EVE L, and EVE R commands.
20070312 Preface
➤ Updated Class 1 LED Product Compliance Label picture.
Section 1
➤ Updated Figure 1.2 and Figure 1.3.
➤ Added AO/DO board information.
➤ Updated Operating Temperature specifications.
➤ Added Analog Output specifications.
Section 2
➤ Updated Figure 2.4.
➤ Added Sealing subsection.
➤ Added AO/DO board information.
Section 4
➤ Updated Crest Factor Metering subsection.
➤ Added note to Load Profile Report subsection.
Section 7
➤ Updated Meter Configuration for High-Accuracy Timekeeping subsection.
➤ Updated Synchrophasor Measurements subsection.
Section 8
➤ Added Analog Outputs subsection.
Setting Sheets
➤ Added Analog Output settings.
➤ Added ESPH setting to SET G Command settings.
Section 10
➤ Corrected Table 10.17.
➤ Added TEST MODE command.
Section 12
➤ Corrected SSI Report Memory Details subsection.
Section 13
➤ Added TEST MODE command information.
➤ Corrected Table 13.4.
Appendix A
➤ Updated for firmware version R120/R520.
Appendix F
➤ Added Analog Outputs information.

Date Code 20090319 Instruction Manual SEL-734 Meter


A.12 Firmware and Manual Versions
Instruction Manual

Table A.2 Instruction Manual Revision History (Sheet 7 of 7)

Revision
Summary of Revisions
Date

Appendix I
➤ Added Analog Outputs information.
Command Summary
➤ Added TEST MODE command.

SEL-734 Meter Instruction Manual Date Code 20090319