You are on page 1of 8

CP 5431 FMS, CP 5412

CP 5431 FMS with Performance Data


CP 5412
FMS/DDE Manager

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.1

Siemens AG Page 1 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
CP 5431 FMS Communications Processor
for SIMATIC S5

 User interfaces:
 FMS: Variable services (partial access),
Information Report
 DP (Response times increased by multi-master operation)
 FDL, GP, PLC/PLC

 PG interface

 Clock synchronization

 Transmission speed 9.6 - 1500 Kbit/s

 Configured using COM 5431 FMS

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.2

Siemens AG Page 2 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
CP 5431 FMS - Protocols and Interfaces

FMS interface DP interface

7b FMS DP

7a LLI DDLM
PG
6
GP
5
inactive PLC/PLC inactive
4 L2
transport FDL
3

2 FDL Subset
1 RS 485 FO

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.3

FMS Fieldbus Message Specification

LLI Lower Layer Interface

PG PG functions, bus selection

GP Global I/O

PLC/PLC Communication between SIMATIC S5 PLCs only

FDL Fieldbus Data Link with the FDL communications services:


SDA Send Data with Acknowledgement
SDN Send Data with No Acknowledgement
SRD Send and Request Data

DP Distributed I/O

DDLM Direct Data Link Mapper

FO Fiber-optic

RS 485 Standard of the EIA (Electronic Industry Association) for an interface with
multipoint capability

Siemens AG Page 3 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
Performance Data of the CP 5431 FMS

ALI

Number of links: 32

Number of variables: Approx. 256


(indexes)

Maximum length 233 bytes


of a variable:

Maximum PDU size: 241 bytes


(user data: 233 bytes)

Link attributes: Master-Master and


Master-Slave

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.4

ALI Application Layer Interface


This interface is used for executing acyclic services.
The CP can be FMS client and FMS server.

Siemens AG Page 4 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
Performance Data of the CP 5431 FMS

CI

Number of links: 32

Maximum PDU size: 32 bytes

Maximum number of inputs: 232 bytes per CI slave


(max. 256 bytes in total)

Maximum number of outputs: 232 bytes per CI slave


(max. 256 bytes in total)

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.5

CI Cyclic Interface
FMS slaves are addressed cyclically using a polling list.
The cyclic interface enables data to be transmitted via the I/Os.
The CI is easy to handle (less programming effort).
In this type of communication the CP can only be a CLIENT.
The cyclic interface does not support SLAVE emulation.

Siemens AG Page 5 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
CP 5412 FMS (A2) Communications Processor for AT-PC

 Interface for FMS, FDL, DP and SIMATIC S7

 Runs under MS-DOS, Windows

 Short AT card

 Programming interface for C compilers from Microsoft and


Borland

 Transmission speed 9.6 Kbit/s - 12 Mbit/s

 Configuring tool included in the relevant software

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.6

Siemens AG Page 6 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
SINEC FMS/DDE Manager

 Connection of WINDOWS applications to FMS via the DDE


interface

 Simple communication using the variable services with


standard software like EXCEL or ACCESS

 Tools for generating and testing user software:


Configuring, not programming!
 Executable with CP 5412 FMS (A2)

* DDE Dynamic Data Exchange

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.7

Siemens AG Page 7 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412
SINEC FMS/DDE Manager for AT-PC

AT-PC with MS-DOS, WINDOWS

Other
EXCEL WINDOWS
applications

DDE interface

SINEC FMS/DDE Manager

FMS interface

FMS (DIN 19245 T.2)

CP 5412 FMS

SIMATIC NET
Siemens AG 1995. All rights reserved.
Datum: 01.10.96
Datei.Nr: KS5L2_CP.8

Siemens AG Page 8 KO-KS5L2


AUT 951 CP 5431 FMS, CP 5412