You are on page 1of 6

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/316364775

Short Circuit Current and Voltage Stability Analysis of a Realistic Generation


System Using Fault Current Limiter and SVC

Article · April 2017

CITATIONS READS

0 650

4 authors:

Ezz Badry Salah Kamel


Aswan University
2 PUBLICATIONS   0 CITATIONS   
156 PUBLICATIONS   315 CITATIONS   
SEE PROFILE
SEE PROFILE

Loai Nasrat Ziad M. Ali


Aswan University Aswan University(Egypt) , and Prince Sattam University(KSA)
42 PUBLICATIONS   19 CITATIONS    40 PUBLICATIONS   18 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Green Building , Renewable Energy and Microgrid View project

IEEE Aswan International Workshop on Computational Methods in Power Systems (CMPS 2018) View project

All content following this page was uploaded by Ziad M. Ali on 22 April 2017.

The user has requested enhancement of the downloaded file.


International Journal on Power Engineering and Energy (IJPEE) Vol. (8) – No. (2)
ISSN Print (2314 – 7318) and Online (2314 – 730X) April 2017

Short Circuit Current and Voltage Stability


Analysis of a Realistic Generation System Using
Fault Current Limiter and SVC
1
Ezz Badry, 1Salah Kamel, 1Loai S.Nasrat, 1,2Ziad M. Ali
1
Department of Electrical Engineering, Faculty of Engineering, Aswan University, 81542 Aswan, Egypt
2
Electrical Engineering Department, Faculty of Engineering, Prince Sattam Bin Abdualziz University, 54 Wadi eldawaser11991,
Kingdom of Saudi Arabia
Ezzeldin.badry@khalda-eg.com, skamel@aswu.edu.eg, loaisaad@yahoo.com, dr.ziad.elhalwany@aswu.edu.eg

Abstract_ Due to the frequently increasing in loads, the solve this problem without any change in the existing
generated power must be upgraded to match this increasing, protection relay scope in the power system.
consequently a new short-circuit level will be developed
based on the value of the generation system upgraded, this This work illustrates in details a realistic example of
raising on short-circuit current level could be extremely power plant consists of three generators and needed to add a
harmful on the protective equipment. To overcome the new generator as per loading increases therefor Fault
problem of the new S.C. level a new approach can be Current Limiter are being uses to maintain short circuit
achieved by using the fault current limiter (FCL) which level, SVC will also be used as the voltage drops on the 3.3
consider the most economical and practical solution. This KV switchgear Bus Bar due to using of the FCL .
paper investigates a realistic power plant system @ Khalda II. Fault Current Limiter (FCL).
Petroleum Company (KPC), which located at Egypt western
desert. The main target is to add a new 7 MW Generator to FCL is a nonlinear devices works on decreasing the
an existing 14 MW power plant drawn by three Generators amount of the fault current cause it has a high impedance
therefor a short-circuit study will be calculated after and that can be added to the electric circuit when fault take
before adding the new Generator. An adequate FCL will be place. Some of FLC has low impedance at the normal
selected to maintain the short-circuit within the previous operation change to high impedance device extremely fast
levels, on the other hand the S.V.C. will be used to once the faults happened, and before a circuit breaker take
maintain the voltage level likewise the existing by carrying action to trip a few milliseconds later. The common
out the Load Flow analysis after adding the FCL, all condition that for different current limiters is the operation
operations will be executed using ETAP 12.6 software. should be at the distribution voltage level [1], and the FLC
could be classified into two main types as following:
Keywords— Fault current limiter, Short Circuit, Load A. Passive Limiters:
Flow, SVC, ETAP 12.6.
It is permanently connected in series with the circuit of the
I. INTRODUCTION power system so no need to turn on or using an external
Catastrophically damage for all components of the signal to control its operation, the series inductors and
power system will be occurs due to frequently increasing of superconducting fault current limiters are considered
loads which demanding increasing in system generation in passive devices[2-4], Reactors are counted as the most
the power plant so an increasing in the short circuit level common passive limiter and flexible to be connected
may exceed the equipment breaking capacity. anywhere in the distribution circuit. They are a linear
inductive reactance; arithmetically the impedance will be
By using larger stepper transformer, the level of the voltage
added to the system to reduce of the fault currents, a voltage
will be increase and so adequate the S.C. level and this will
regulation carried out to maintain the distribution system
grantee the safety conditions for the equipment of the
voltage within the limits, due to voltage drop, which exists
system, or by readjusting the existing protection scope to be
due to the current flow through the reactors, are in the same
matches with the new S.C. level. Actually, both solutions
quadrature with the load voltage. The case under study with
will be expensive to carry out because of the high equipment
this type of FCL will be investigated in this work.
fees, so an economical and a practical solution is needed to

Reference Number: JO-P-095 743


International Journal on Power Engineering and Energy (IJPEE) Vol. (8) – No. (2)
ISSN Print (2314 – 7318) and Online (2314 – 730X) April 2017

B. Solid State Limiters(SSL) feeders from the 4 generators to the two main bus bars
feeding the 11 KV switchgear, when the coupler will
During the fault case and after a few milliseconds of its maintain always closed the operation of adding new
action the solid state devices inserted by electronic switches generator of 10 MW will be implemented as per the
to increase the system impedance and to limit fault currents. following steps:
[5]. SSL is categorized into two main types: The resonance
based devices and the impedance switched bypass limiters. A- Calculate the short circuit values on the main four
The operation of resonance-based devices is based on that buses and at the far end, six buses are depicted in table
during the fault the voltage sags will be happened and will (1), from the table (1). The Max. Values of S.C. are
have a direct effect on the fault current values [6, 7]. 7.749 KA at BUS 1 & 2. these values should be
The impedance switched bypass limiters connected in series adequate to the breaking capacity of the protective
with the main distribution line, a pair of GTO are shunted devices such as the CB, CT and PT.
with it to operate during the voltage alternate half cycles to
create a new path of low impedance. The GTO switches are Table (1) Short-Circuit Summary
closed due to the fault and a large impedance will be
appeared and so limiting the current, but there are some 3 PHASE LINE TO
disadvantages due to switching power loss and its reliability FAULTS GROUND FAULT
cause the switching times effects are under search and study Bus No. Voltage (KA) (KA)
to enhance [8-9]. (KV)
1 11.000 7.749 3.331
III. SHORT CIRCUIT STUDY. 2 11.000 7.749 3.331
A short circuit study is modeled to get the values of the Max. 21 3.300 7.167 1.303
and Min., a new generator or Fault Current limiter is added
31 3.300 7.167 1.303
and so the study will be updated and repeat the adding
process until optimize the best efficient limiter which will 33 3.300 7.167 1.303
contribute on limiting the fault current to the same values 36 3.300 7.167 1.303
before adding the new generator. 38 3.300 7.686 0.813
All S.C. calculations were carried by using ETAP 12.6 40 3.300 7.686 0.813
based on IEC 60909 [10-13], the associated standards 42 3.300 7.686 0.813
classify short circuit currents according to their magnitudes 48 3.300 7.686 0.813
(maximum and minimum) and classify the fault distances
from the generator (far and near). Maximum short circuit
B- Calculate the short circuit values for the previous
currents determine equipment ratings, while minimum
buses after adding the new 7 MW generator which
currents dictate protective device settings. Near-to-generator
will certainly as a result on increasing the Max.
and far-from-generator classifications determine which of
Fault current as shown in table (2).
the AC components decrease in the calculation.
Table (2) Short-Circuit Summary

IV. STATIC VAR COMPENSATOR OPERATION 3 PHASE LINE TO


FAULTS GROUND
To provide the fast acting reactive power the static VAR Bus Voltage FAULT
compensator (SVC) is installed on high voltage transmission (KA)
No. (KV) (KA)
networks [14-15], SVCs are parts of the Flexible AC 1 11.000 8.312 3.373
transmission system [16-17] device family, regulating
voltage, power factor, harmonics and stabilizing the system, 2 11.000 8.312 3.373
and here in our case study the SVC has to be used after 21 3.300 7.272 1.304
adding the adequate fault current limiter to regulate the far 31 3.300 7.272 1.304
end bus voltage which influence in stabilizing the system. 33 3.300 7.272 1.304
36 3.300 7.272 1.304
V. RESULT AND DISCUSSION
38 3.300 7.793 0.813
The power plant single line diagram is shown in Fig.3 40 3.300 7.793 0.813
consists of three existing generator, two 2MVA power
42 3.300 7.793 0.813
transformers 11 KV/.4KV, two 2.5MVA power transformer
11KV/3.3KV, 14 medium voltage CBs mounted with its 48 3.300 7.793 0.813
related protective devices, 4 CBs represent as incoming

Reference Number: JO-P-095 744


International Journal on Power Engineering and Energy (IJPEE) Vol. (8) – No. (2)
ISSN Print (2314 – 7318) and Online (2314 – 730X) April 2017

C- Adding the fault current reactor in series with both


Generators 3&4 as in Fig. 1 Then calculate the new
short circuit values as shown in table (3). The results
show that the sufficient values of the Max. Fault
current which dropped from8.312 KA to 7.43 KA
resulting on adding new fault current limiter reactors.

Table (3) Short-Circuit Summary

3 PHASE LINE TO
FAULTS GROUND
Bus No. Voltage (KA) FAULT
(KV) (KA)
1 11.000 7.403 3.230
2 11.000 7.403 3.230
21 3.300 7.106 1.299
31 3.300 7.106 1.299
33 3.300 7.106 1.299
36 3.300 7.106 1.299
38 3.300 7.624 0.812
40 3.300 7.624 0.812
42 3.300 7.624 0.812
48 3.300 76.24 0.812

D- Preform the load flow analysis to check the


voltage stability for all the mentioned buses and Fig. (1) SLD after adding the FCL
found all buses listed on table (4) in under voltage
case which resulting of inserting series reactor on Table (4) LF Marginal Alerts results
the circuit, this problem had been overcome by
using Static Var Compensator at the far end bus#48 Bus No. Condition Rating % operating
As shown in Fig. (1) (KV)
37 Under voltage 3.300 97.4
Fig. (2) Shows the amount of current change before and 38 Under voltage 3.300 97.7
after adding the new generator and after adding the fault 39 Under voltage 3.300 97.4
current limiter. 40 Under voltage 3.300 97.7
41 Under voltage 3.300 97.6
42 Under voltage 3.300 97.7
47 Under voltage 3.300 97.7
48 Under voltage 3.300 97.7
53 Under voltage 0.400 97.9
55 Under voltage 0.400 97.7

Reference Number: JO-P-095 745


International Journal on Power Engineering and Energy (IJPEE) Vol. (8) – No. (2)
ISSN Print (2314 – 7318) and Online (2314 – 730X) April 2017
VI. CONCLUSION
Upgrading generation station is one of the most required
operations now days, due to the rapidly increased in loads,
some of this stations were not prepared for upgrading and
leading to risky rises in the fault current level, all
equipment, which are dealing directly with the system
current, must withstand this rises in S.C. level.
To overcome this problem there are two direction one of
them is rise the voltage level of the system and the other is
increase the impedance of the faulty circuit, in this paper
after adding new 10 MW generator to an existing system of
15 MW we trying to maintain the new fault current level to
the same as was before adding the new generator thus we
don’t have to replace any of the system equipment, this
minimizing of the fault current had been achieved by adding
Fig. (2) Fault current values in the three cases

Fig (3) Single line diagram

Reference Number: JO-P-095 746


International Journal on Power Engineering and Energy (IJPEE) Vol. (8) – No. (2)
ISSN Print (2314 – 7318) and Online (2314 – 730X) April 2017
limitation,” in Power Engineering Society Winter Meeting, vol. 4.
two of passive FLC (reactors / Z= 4 ohm) in series with the IEEE Power Engineering Society, Jan. 2000, pp. 2482–2487.
two Generator 3&4,results show that the adding of FLC is [8] R. K. S. et al., “Solid state distribution current limiter and
able to control the fault current by increasing the impedance circuit breaker: Application requirements and control strategies,”
IEEE Transactions on Power Delivery, vol. 8, no. 3, pp. 1155–
of the system without adding or interrupting the circuit. The 1164, July 1993.
fault current limiter is proved to be and effective technique [9] P. K. C. Meyer and R. W. DeDoncker, “Design of a novel low
to limit the current in the faulty network without any loss fault current limiter for medium-voltage systems,” in Applied
physical change in the structure of the network. Power Electronics Conference and Exposition, vol. 3. IEEE
APEC, 2004, pp. 1825–1831
VII. REFERENCES [10] IEC 60909-0 Short-Circuit Currents in Three-phase a.c.
[1] P. G. S. et al., “The utility requirements of a fault current systems - Part 0: Calculation of Currents (including 2002
limiter,” IEEE Transactions on Power Delivery, vol. 7, no. 3, pp. corrigendum 1) for systems up to 500kV.
1124–1311, Apr.1992. [11] IEC 60909-1 Short-circuit currents in three-phase a.c. systems
[2] J. F. Amon, P. C. Fernandez, E. H. Rose, A. D’Ajuz and A. - Part 1: Factors for the calculation of short-circuit currents
Castanheira, “Brazilian Successful Experience in the Usage of according to IEC-60909-0
Current Limiting Reactors for Short-Circuit Limitation,”
International Conference on Power Systems Transients (IPST’05), [12] IEC 60909-2 Electrical equipment - Data for short-circuit
Montreal, 19-23 June 2005, pp. 215- 220 current calculations in accordance with IEC 909 (1988)
[13] IEC 60909-4 Short-circuit currents in three-phase a.c. systems
Part 4: Examples for the calculation of short-circuit currents
[3] W. Paul and M. Chen, “Superconducting control for surge
currents,” IEEE Spectrum, pp. 49–54, May 1998. [14] De Kock, Jan; Strauss, Cobus (2004). Practical Power
[4] B. W. Lee, J. Sim, K. B. Park and I. S. Oh, “Practical Distribution for Industry. Elsevier. pp. 74–75. ISBN 978-0-7506-
Application Issues of Superconducting Fault Current Limiters for 6396-0.
Electric Power Systems,” IEEE Transactions on Applied [15] Deb, Anjan K. Power Line Ampacity System. CRC Press.
Superconductivity, Vol. 18, No. 2, 2008, pp. 620-623. pp. 169–171. ISBN 978-0-8493-1306-6.
[5] D. Fedasyuk, P. Serdyuk, Y. Semchyshyn and Lviv Polytechnic
National University, “Resistive Superconducting Fault Current [16] Song, Y.H., Johns, A.T. Flexible ac transmission systems.
Limiter Simulation and Design,” 15th International Conference, IEE. ISBN 0-85296-771-3
Poznan, 19-21 June 2008, pp. 349-353. [17] Hingorani, N.G. & Gyugyi, L. Understanding FACTS -
[6] Principles of Fault Current Limitation by a Resonant LC Concepts and Technology of Flexible AC Transmission Systems.
Circuit, vol. 139. IEE, Jan. 1992. IEEE. ISBN 0-7803-3455-8.
[7] C. S. Chang and P. C. Loh, “Designs synthesis of resonant
fault current limiter for voltage sag mitigation and current

Reference Number: JO-P-095 747

View publication stats

You might also like