You are on page 1of 9

This sample chapter is for review purposes only. Copyright © The Goodheart-Willcox Co., Inc. All rights reserved.

Chapter 12
Branch
Circuits and
Feeders
Technical Terms • Feeder—A conductor that originates at the main
distribution or main disconnect device and termi-
Branch circuit Show-window lighting nates at another distribution center, panelboard,
Continuous load load or load center.
Feeders Track lighting • Subfeeders—These conductors originate at distri-
General lighting load bution centers other than the main distribution
center and extend to panelboards, load centers, and
Objectives disconnect switches that supply branch circuits.
• Panelboard—This can be a single panel or
After completing this chapter, you will be able to: multiple panels containing switches, fuses, and
H Identify the feeder and branch circuit portions of a circuit breakers for switching, controlling, and
distribution system. protecting circuits.
H Describe the various types of branch circuits. • Branch circuits—The portion of the wiring
H Define the functions of a feeder and the functions of system extending past the final overcurrent
branch-circuit conductors. device. These circuits usually originate at a panel
H Calculate lighting and receptacle loads using Code and transfer power to load devices.
requirements.
H Size branch circuits in accordance with the Code. Branch Circuits
H Determine branch circuit overcurrent protection
required by the Code. Any circuit that extends beyond the final overcurrent
H Use the Code to size feeder conductors. protective device is called a branch circuit. This includes
circuits servicing single motors (individual) and circuits
In an electrical system, power must be transferred serving many lights and receptacles (multiwire). Branch
from the service equipment to the lights, machines, and circuits are usually low current (30 amps or less), but can
outlets. Regardless of the wiring methods used, the also supply high currents.
conductors carrying the power fall into one of two cate- A basic branch circuit is made up of conductors
gories: feeders or branch-circuit conductors. This chapter extending from the final overcurrent protective device to
will explore the characteristics of these two conductor the load. Some branch circuits originate at safety switches
types. (disconnects), but most originate at a panelboard. The
following are several branch circuit classifications
Definitions (Figure 12-2):
• Individual branch circuit—A branch circuit
Several definitions are essential to understanding that supplies a single load.
branch circuits and feeders. The following items are illus- • Multioutlet branch circuit—A branch circuit
trated in Figure 12-1: with multiple loads.
• Service conductors—These conductors extend • General purpose branch circuit—A multi-
from the power company terminals to the main outlet branch circuit that supplies multiple outlets
service disconnect. for appliances and lighting.
145
146 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 147

Main service • Branch circuits exceeding 120 volts but not four-wire delta system with a neutral connected at the
disconnect exceeding 277 volts may supply mogul-base midpoint of a winding, the “high leg” phase conductor
Distribution screw-shell lampholders, ballasts for fluorescent should be identified with orange markings.
center lighting, ballasts for electric-discharge lighting,
Feeders
Panelboard
plug-connected appliances, and hard-wired appli- Branch-Circuit Loads
(final OCPD)
ances. Incandescent lighting operating over 150
volts is permitted in commercial construction. The Code places load limitations on branch circuits
Branch • Circuits exceeding 277 volts and up to 600 volts with continuous loads (loads with a duration longer than
circuits can supply mercury-vapor and fluorescent three hours, such as lighting). The continuous load must
lighting, provided the lighting units are installed not exceed 80% of the circuit rating allotted for it. If the
at heights not less that 22′ above grade and in overcurrent protective device is listed for continuous
tunnels at heights no less than 18′. operation at 100% of its rating, the 80% factor is not used.
Branch-circuit loads are classified into five categories:
Conductor Size and Ampacity • Lighting loads.
• Receptacle loads.
The amperage rating of branch-circuit conductors • Equipment loads.
must be greater than the maximum load the circuit will • Heating and cooling loads.
Service provide. For multiple-load branch circuits, the conductor • Motor loads.
conductors ampacity must correspond to the rating of the overcurrent
Subfeeders
protective device. However, for circuits supplying hard- NOTE
wired devices (such as electric heaters, air-conditioning Motor roads are discussed in Chapter 13 of this text.
Panelboard units, and water heaters), the fuse or circuit breaker can
(final OCPD)
be rated at the next higher rating. The conductor is Lighting Loads
Figure 12-1. Conductors are classified based on their location in the electrical supply system. acceptable if its rating is at least that of the load current,
even if the overcurrent protective device rating is higher. In the broad sense, lighting loads may be categorized
The smallest general-purpose conductor for branch as follows:
• Appliance branch circuit—A branch circuit circuits is 14 AWG. Tap conductors can be smaller. See • General lighting.
that supplies a single appliance load. Section 210.19 for more information. • Show-window lighting.
• Multiwire branch circuit—A branch circuit • Track lighting.
with two or more ungrounded conductors and Multiwire Branch Circuits • Sign and outline lighting.
one grounded conductor. • Other lighting.
A branch circuit can be either a two-wire or multi- Each lighting load is computed separately and then
Neutral Branch-Circuit Rating wire branch circuit. A multiwire branch circuit consists of combined to determine the total lighting load.
a grounded conductor and two or more ungrounded
Individual Branch conductors. A multiwire circuit can be an individual
Circuit
A branch circuit is sized for the load it will supply. General lighting
Sizing the circuit for additional future loads is good prac- circuit or a multioutlet circuit. General lighting is the overhead lighting within a
tice. The rating of a branch circuit depends on the rating building. Its intensity should be adequate for any type of
of the overcurrent device protecting the circuit. Conductor Color Code work performed in the area. Determining the general
Branch circuits serving only one device can have any lighting load can be based on either the load per area
rating, while a circuit supplying more that one load is Grounded conductors of branch circuits are identified method or the actual full-load current of the fixtures used,
limited to ratings of 15, 20, 30, 40, or 50 amps. by color. If the grounded conductor is 6 AWG or smaller, whichever is greater. Within a structure, there are normally
it is white, gray, white with a color stripe, or has three several different types of areas—storage, office, hallways,
Branch-Circuit Voltage continuous white stripes on other than green insulation. If and cafeterias—and these must be considered separately.
General Purpose wires from different systems are contained in the same Most commercial structures have continuous lighting
Branch Circuit raceway, the neutrals of different systems are distin-
Branch-circuit voltage limits are contained in Section loads and the branch circuits must be adequate for
210.6 of the Code. These limits are based on the equip- guished from one another. For example, the neutral of one carrying 125% of the calculated load. Code requirements
A system would be white, the neutral of the another system
ment being supplied by the circuit: for general lighting loads are found in several sections:
B • In residences and hotel rooms, circuits supplying would be gray, and the neutral of a third system would be • Section 220.12—Lighting loads for specified
Neutral lighting fixtures and small receptacle loads white with a colored stripe. The equipment grounding occupancies
cannot exceed 120 volts. conductor must be green, green with yellow stripes, or • Section 220.14—Other loads and all occupancies
Individual Multiwire • Circuits that are 120 volts and less may be used bare (without any insulation). • Section 220.16—Loads for additions to existing
Branch Circuit
to supply lampholders, auxiliary equipment of Hot conductors can be any color except white, gray, installations
Figure 12-2. Branch circuits are classified as individual or electric-discharge lamps, receptacles, and perma- green, and white with a color stripe. Normally, hot • Section 220.18—Maximum loads for branch
multioutlet, appliance or general. nently wired equipment. conductors are black, blue, and red. In a three-phase, circuits
148 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 149

Table 220.12 of the Code contains minimum general The general lighting load is not required if the load
NEC NOTE 410.14
lighting loads (in VA/ft2) for various types of buildings. for each lamp is determined separately. If the individual Sample Problem 12-4
A condensed version of this table is shown in Figure 12-3. load is continuous, it must be multiplied by 1.25. When Chain-supported fixtures used in a show window
The general lighting load is calculated by multiplying determining the current draw of fluorescent fixtures, use shall be permitted to be externally wired. No other Problem: Determine the track lighting load for a
the floor area (in ft2) by the unit load (in VA/ft2). If the the current rating of the ballast, not the tube wattage. externally wired fixtures shall be used. 22′ long section of track.
load is continuous, the calculated load is multiplied by
Solution: Every 2′ requires 150 volt-amperes, so
1.25 (the inverse of 80%) to determine the circuit
the length (in feet) is divided by 2′, and then multi-
requirements. Sample Problem 12-2 Sample Problem 12-3 plied by 150 volt-amperes:
Problem: A 4′ long, two-lamp fluorescent fixture Problem: A department store has two lighted show length
Track lighting load = × 150 VA
ballast draws 0.7 amps at 120 volts. How many of windows, one 25′ long and the other 20′ long. What 2′
General Lighting Loads 22′
these fixtures can be connected on a 20-amp circuit? are the branch-circuit requirements for the show- = × 150 VA
Type Building Unit Load (VA/ft2) 2′
window load?
Solution: This is a continuous load, so the current =1650 VA
Auditoriums 1 Solution: Compute the load based on linear feet of
used by the lights can only be 80% of the circuit show window: If this is a continuous load, the circuit requirements
Banks 3 1/2
current rating: would also include a 1.25 factor.
Barber shops 3 Total length = 25′ + 20′
Churches 1 = 45′
Allowable current = 20 A × 0.80 Sign and outline lighting
Dwelling units 3
= 16 A Show-window load = 45′ × 200 VA/ft Sign and outline lighting is discussed in Article 600
Hospitals 2
= 9000 VA of the Code. A structure must have at least one circuit
Hotels 2
By dividing the allowable load by the load of each The lighting is a continuous load, so the show- exclusively used to supply sign or outline lighting. The
Office buildings 3 1/2
lamp, the total number of lamps is determined: window load is multiplied by 1.25 to determine the circuit must be designed for a minimum load of 1200
Restaurants 2
Schools 3 16 A circuit load requirements: volt-amperes.
⎯⎯ = 22.8 fixtures Sign and outline lighting loads are considered contin-
Stores 3 0.7 A Circuit requirements = 9000 VA × 1.25
Warehouses 1/4 uous loads. Therefore, if the rating of the sign and outline
The maximum number of fixtures on the circuit is 22. = 11,250 VA
fixtures is greater than 960 volt-amperes (1200 × 0.8 = 960),
Figure 12-3. Minimum general lighting loads are dependent on The circuits supplying power for the show-window the circuit will be greater than 1200 volt-amperes.
the type of area being lit. lighting must have a minimum capacity of 11,250
Show-window lighting volt-amperes. Sample Problem 12-5
The show-window lighting load is not considered as In addition, receptacles are required for every 12′ of
part of the general lighting load. Section 220.43(A) of the show window. A total of five receptacles (two for Problem: A hardware store measures 80′ × 120′. A
Sample Problem 12-1 Code requires that show-window lighting be computed as the 20′ window and three for the 25′ window) are portion of the building (80′ × 40′) is used for
200 volt-amperes per linear foot or as the maximum volt- needed. The receptacle load can then be computed: storage. The remainder of the building is used as a
Problem: A 25,000 ft2 office building is being ampere rating of the equipment and lights, whichever is showroom. There is a total of 45′ of show windows,
5 × 180 VA = 900 VA
designed. What is the general lighting load and what greater. and there is one outdoor sign. What is the total
load does the circuit need to supply? Total load = 11,250 VA + 900 VA
lighting load for this building?
NEC NOTE 100 = 12,150 VA
Solution: From Table 220.12, the unit load for an Storage area
office building is 3 1/2 VA/ft2. The general lighting Show Window: Any window used or designed to
Track lighting
load is determined by multiplying this value by the be used for the display of goods or advertising mate-
Track lighting is often used in commercial buildings
square footage of the building: rial, whether it is fully or partly enclosed or entirely
for accent lighting. It is discussed in Part XV of Article
open at the rear and whether or not it has a platform
410 of the Code. The minimum load for track lighting is
3 1/2 VA/ft2 × 25,000 ft2 = 87,500 VA raised higher than the street floor level.
150 volt-amperes for every 2′ of track. To compute the
track lighting load requirements, simply determine the 40′
The general lighting load is 87,500 volt-amperes. total length of track lighting, divide by two, and multiply
The Code includes several sections applicable to
However, the load is continuous and can only be by 150 volt-amperes.
show-window lighting:
80% of the load supplied by the circuit. This value
• Section 220.43(A)—Show-window lighting.
must be multiplied by 1.25 to determine the circuit
• Section 220.14(G)—Load computation. NEC NOTE 410.2 80′
requirements: 25′
The Code also requires at least one receptacle outlet
Lighting track is a manufactured assembly 20′
87,500 VA × 1.25 = 109,375 VA
for every 12′ of show-window space measured horizon- 80′
designed to support and energize luminaires (lighting
tally with the load computed at 180 volt-amperes per
fixtures) that are capable of being readily repositioned
The circuit is designed to supply 109.375 kilovolt- outlet. This receptacle load is in addition to the show-
on the track. Its length can be altered by addition or
amperes. window lighting load. (Continued on the following page.)
subtraction of sections of track.
150 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 151

Additional lighting loads


Additional lighting loads should be computed sepa-
Sample Problem 12-6
Sample Problem 12-5 Continued
rately from the general lighting load and then added to
Problem: A hotel has 250 rooms, each with an area The general lighting load must be divided into three
Solution: Each type of lighting load is computed the general lighting load. Loads for additional lighting
of 400 ft2. Determine the general lighting load and parts to correspond to the three different demand factors.
separately and then combined to determine the total such as security lighting, parking area lighting, sidewalk
then calculate the derated load to be used for feeder The first 20,000 volt-amperes have a demand factor of
lighting load. First, the general lighting loads for lighting, roadway lighting, and stadium lighting are
calculations. 50%. The next 80,000 volt-amperes (20,000 to 100,000)
the two areas of the store are calculated: calculated using the actual load. These are considered
continuous loads where appropriate. The additional have a demand factor of 40%. The final 100,000 volt-
Solution: First, determine the total area of the hotel amperes (100,000 to 200,000) have a demand factor of
Storage area = 80′ × 40′
lighting load must be treated separately from the general
rooms: 30%. Each section is calculated individually:
= 3200 ft2
lighting load for computation purposes.

Demand factors for feeder loads 250 rooms × 400 ft2/room = 100,000 ft2 20,000 VA × 0.50 = 10,000 VA
Showroom area = 80′ × 80′ Due to the great diversity of lighting loads on commer-
= 6400 ft2 cial premises, Section 220.42 and Table 220.42 allow the The general lighting load for hotel rooms (from Table 80,000 VA × 0.40 = 32,000 VA
general lighting load to be derated (reduced) for feeder, 220.12) is 2 VA/ft2. Determine the general lighting 100,000 VA × 0.30 = 30,000 VA
panel, or service computations. See Figure 12-4. For load:
Table 220.3(A) lists unit loads for storage and show-
room as 1/4 VA/ft2 and 3 VA/ft2, respectively: example, it is highly unlikely that every light in a hospital To determine the derated feeder load, add the three
would be operating at the same time. Of course, there are 100,000 ft2 × 2 VA/ft2 = 200,000 VA
totals together:
areas within a hospital where the derating factors should
General lighting load (storage) = 3200 ft2 × 1/4 VA/ft2 not be applied as these areas (such as operating rooms, The branch circuits are required to supply the full 10,000 VA + 32,000 VA + 30,000 VA = 72,000 VA
= 800 VA emergency rooms, intensive care units, nurses stations, general load. However, the feeder can be derated using
stairways, and cardiac units) are likely to have lighting the factors in Table 220.42. The derated load used for sizing the feeder is 72,000
General lighting load (showroom) = 6400 ft2 × 3 VA/ft2 units on at all times. volt-amperes.
= 19,200 VA Table 220.42 Lighting Load Demand Factors
NOTE
Portion of Lighting Load Demand
General lighting load = 800 VA + 19,200 VA Derating factors do not apply to branch-circuit conductor or to Which Demand Factor Factor
branch-circuit overcurrent protective device calculations. Type of Occupancy Applies (Volt-Amperes) (Percent)
= 20,000 VA
Dwelling units First 3000 or less at 100
From 3001 to 120,000 at 35
The show-window lighting load is based on 200 VA Demand Factors for Remainder over 120,000 at 25
per linear foot:
Lighting Loads Hospitals* First 50,000 or less at 40
Remainder over 50,000 at 20

Show-window lighting load = 45′ × 200 VA/ft Type of Porton of Demand Hotels and motels, First 20,000 or less 50
= 9000 VA Occupancy Load (VA) Factor (%) including apartment From 20,001 to 100,000 40
houses without provision Remainder over 100,000 30
Dwelling Unit for cooking by tenants*
The minimum load for the sign lighting is used: 0–3000 100 Warehouses (storage) First 12,500 or less at 100
3001–120,000 35 Remainder over 12,500 at 50

Sign lighting = 1200 VA Over 120,000 25 All others Total volt-amperes 100

Hospital *The demand factors of this table shall not apply to the computed load of feeders
or services supplying areas in hospitals, hotels, and motels where the entire lighting
Now the total lighting load can be calculated by 0–50,000 40 is likely to be used at one time, as in operating rooms, ballrooms, or dining rooms.
adding the parts together: Over 50,000 20

Hotels and
Total lighting load = 20,000 VA + 9000 VA + 1200 VA Motels 0–20,000 50
= 30,200 VA
20,000–100,000 40
Over 100,000 30 Receptacle Loads When a receptacle is the load supplied by an indi-
These loads are all continuous, so the total load is vidual branch circuit, the receptacle ampere rating must
Warehouses
multiplied by a factor of 1.25 to determine the The majority of receptacles installed in commercial be equal to or greater than that of the branch circuit.
circuit requirements. 0–12,500 100
structures do not supply continuous loads. It is difficult to When there are multiple receptacles on a branch circuit,
Over 12,500 50 predict what size load will be supplied at a receptacle, the receptacle rating varies with the current rating. See
30,200 VA × 1.25 = 37,750 VA All Others Total VA 100 unless the receptacle is dedicated (assigned a specific Figure 12-5, which reflects Table 210.21(B)(3).
purpose). The Code does not require a minimum number Receptacles connected to a 15-amp or 20-amp circuit
Figure 12-4. Lighting loads can be derated for structures where of outlets for commercial buildings. Normally, many are grounded. Grounded receptacles should not be used if
all lights are not in use continuously. receptacles are required. the circuit is not actually grounded. A GFCI receptacle
152 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 153

Receptacle Rating Multioutlet assemblies are frequently installed in


Sample Problem 12-9
repair shops, lighting display areas, electronics depart-
Circuit Rating (A) Receptacle Rating (A) ments, and other locations where many outlets are
Problem: The hardware store introduced in Sample Four receptacles are needed for each 40′ wall. The total
15 Not over 15 needed. These multioutlet assemblies require 180 volt-
Problem 12-5 will have one duplex receptacle for number of wall receptacles can now be calculated:
20 15 or 20 amperes for each 5′ of length. In stores, repair shops, and
30 30 every 12′ of wall around the storage area and show-
laboratories, the Code allows the overall load to be Wall receptacles = (6 × 7) + (2 × 4)
40 40 or 50 room. A total of twelve floor receptacles will be used.
50 50 derated in accordance with Table 220.44 (if the load = 42 + 8
Determine the receptacle load, including show-
exceeds 10,000 volt-amperes). = 50
window receptacles for 20′ and 25′ show windows.
Figure 12-5. Receptacle ratings are determined by the circuit The diversity and inconsistent loading of general
rating. purpose receptacles allows the total receptacle load to be One receptacle is needed for every 12′ of show win-
derated (see Section 220.44). If the load exceeds 10,000 dow length, so the 20′ show window requires two
volt-amperes, the first 10 kilowatts are counted at 100%, receptacles and the 25′ show window requires 3 recep-
can be used as a replacement for an ungrounded recep- but additional load is counted at 50%. This may not be Showroom Storage tacles. Therefore, the show windows require a total of
tacles outlet. used if the Code dictates that the specific appliances area
five receptacles. The total number of receptacles can
A load of 180 volt-amperes is assigned to each recep- cannot be derated. Refer to Sections 220.12 and 220.44 Showroom Storage
area be found by adding together the wall receptacles, floor
tacle, whether it is single, duplex, or triplex. If a recep- and Table 220.44. receptacles, and show-window receptacles:
tacle is dedicated for a specific device, then the actual
load is used. If the dedicated load is continuous, then the Sample Problem 12-8 Total receptacles = 50 + 12 + 5
125% overrate is appropriate. = 67 receptacles
To calculate the allowable number of receptacles on a Problem: Determine (a) the receptacle load for an
branch circuit, multiply the circuit voltage and amperage, 80′ × 120′ hardware store and (b) the number of The total receptacle load can then be determined:
then divide by 180 volt-amperes. The receptacle load can Solution: Receptacles will be placed along six 80′-long
15-amp circuits needed to supply the load. The
be included with the general lighting load by adding a walls and two 40′-long walls. Determine the number
number of receptacles is unknown. Receptacle load = 67 × 180 VA
value of 1 VA/ft2 to the general lighting unit loads found in of receptacles needed for each 80′-long wall:
= 12,060 VA
Table 220.12. However, this method should only be used Solution: (a) The number of receptacles is
when the number of receptacles is unknown. unknown, so a receptacle load of 1 VA/ft2 can be Receptacles per 80′ wall = 80′ The total receptacle load is 12,060 VA. For feeder siz-
12′
calculated: = 6.67 ing, the first 10,000 VA must be counted at 100%, but
Sample Problem 12-7 only 50% of the additional load needs to be consid-
Area = 80′ × 120′ Seven receptacles are needed for each 80′ wall. Next, ered. Determine 50% of 2060 VA:
Problem: How many receptacles can be placed on = 9600 ft2 determine the number of receptacles needed for each
a 120-volt, 20-amp circuit? How many can be 2060 VA × 0.50 = 1030 VA
40′ wall:
placed on a 120-volt, 15-amp circuit?
Receptacle load = 1 VA/ft2 × 9600 ft2 Feeder load = 10,000 VA + 1030 VA
Solution: Determine the maximum circuit power: = 9600 VA Receptacles per 40′ wall = 40′ = 11,030 VA
12′
P =E × I = 3.33
= 120 V × 20 A (b) To determine the number of circuits required, The receptacle load on the feeder is 11,030 VA.
= 2400 VA (for 20-amp circuit) first calculate the allowable load for a single circuit:
P = 120 V × 15 A Equipment Loads Commercial kitchen equipment loads
= 1800 VA (for 15-amp circuit) Max load = 120 V × 15 A Loads for commercial cooking equipment are
= 1800 VA Within this category of branch-circuit loads is a vast discussed in Section 220.56 of the Code. The total feeder
Then divide the power by the load per receptacle array of equipment, such as appliances, water heaters, load is simply the sum of the nameplate ratings of the
(180 volt-amperes): Divide the total receptacle load by the maximum washers, dryers, and cooking equipment. Most of these appliances. If there are three or more pieces of cooking
load per circuit to determine the minimum number items are used for brief periods and are considered equipment, the feeder load can be derated in accordance
20-amp circuit: of circuits: noncontinuous, so the required load supplied by the with Table 220.56. The table in Figure 12-6 lists the
2400 VA = 13.3 circuit is identical to the equipment requirement. demand factors. The branch-circuit loads cannot be
180 V Circuits = 9600 VA Equipment is often hard-wired, but can also be cord- derated using these factors.
1800 V
15-amp circuit: = 5.33 and-plug connected to a receptacle. Branch circuits for Ovens, grills, fryers, food warmers, large vat blending
appliance loads must have conductors with an ampacity machines, booster heaters, conveyors, and tray assem-
1800 VA = 10
180 V
This is the minimum number, so round up to six equal to or exceeding the ampacity of the appliance. The blies are considered kitchen equipment and may be
circuits. ampacity of the appliance is marked on the unit by the derated in accordance with Table 220.56. Auxiliary
A 120-volt, 20-amp circuit can supply 13 receptacles. manufacturer. If the appliance has a motor, the ampacity equipment such as exhaust fans, space heaters, and air-
A 120-volt, 15-amp circuit can supply 10 receptacles. of the branch-circuit conductors must be 125% of the conditioning units are not counted as kitchen equipment
current rating of the motor. and cannot be derated.
154 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 155

Feeder Demand Factors for circuits supplying heating equipment (see Section An air-conditioning branch-circuit load is determined Feeders
424.22): from the data provided on the nameplate affixed to the
Kitchen Equipment • Heating equipment is protected by the branch- unit. The nameplate will list the phase, voltage, frequency, The conductors between the service equipment and
Units of Equipment Demand Factors (%) circuit overcurrent protective device. This can be full-load current, and other pertinent information of the the branch-circuit overcurrent devices are called feeders.
1–2 100 a set of fuses or circuit breakers. hermetic motor compressor. The full-load current rating Article 215—Feeders provides information regarding the
3 90 • Motors used in conjunction with the heating shown on the nameplate serves as the basis for deter- safe and adequate sizing and installation of these conduc-
4 80 equipment must also have overcurrent protection. mining the branch-circuit conductor size, overcurrent tors. This article also applies to subfeeders, which provide
5 70
6+ 65 • Heating units having resistance elements exceeding protection requirement, controller rating, and disconnect power to branch-circuit panels but originate at power
48 amps must have their load subdivided. Each of size. distribution centers rather than the service equipment.
Figure 12-6. The load for multiple pieces of commercial the loads must have overcurrent protection provided Sometimes the branch-circuit current rating is also Feeder loading is dependent on the total power
cooking equipment can be derated in accordance with the by the manufacturer. Conductors from the overcur- included on the nameplate. In such instances, use the requirement of the system. If it is possible for all
demand factors listed in Table 220.56. rent devices to the heating unit must be sized at larger of the branch-circuit current rating or full-load connected loads to operate simultaneously, then the
125% if the load is 50 kilowatts or less. current rating for sizing the circuit. If a unit has two or feeder must be of sufficient ampacity to meet that
• If the unit load for the heating equipment is greater more motors, then the circuit ampacity must be computed demand. If only 75% of the connected loads will ever be
NEC NOTE 220.56 than 50 kilowatts, the conductors can be sized at at 125% of the largest motor plus the sum of the other operating at the same time, then the feeder would be sized
100% provided the heating unit has a controller motors. For a single-motor unit disconnect, use 115% of larger than the service conductors.
Demand factors for kitchen equipment shall be
(thermostat). If this is not the case, then the the full-load current. Prior to installation, certain factors must be consid-
applied to all equipment that has either thermostatic
conductors must be sized at 125% of the load. ered to ensure the feeder size, type, and overcurrent
control or intermittent use as kitchen equipment. They
• For conditions other than those described above, NOTE protection is correct for the application:
shall not apply to space-heating, ventilating, or air-
size the conductors at 125% of the load. A disconnecting means must be within sight of the unit
• Material—The feeder can be copper or aluminum.
conditioning equipment.
and it must be correctly sized at 115% of the total current
• Location—The environment around the feeder
Sample Problem 12-10 rating.
(damp, hot, corrosive) must be considered.
• Wiring method—The feeder can be run in
Heating and Cooling Loads Problem: A 30-kilowatt, 240-volt heating unit with The overcurrent protective device cannot exceed conduit, cable trays, or other systems.
a 6-amp fan motor is being installed for a shoe store. 175% of the motor full-load current or branch-circuit • Cable—Single or multiconductor cable can be
Regardless of the type of structure—residential, Determine the size of the THW conductors and rating, whichever is larger. This can be increased to 225% used.
commercial, or industrial—the heating load must be overcurrent protective device for the circuit if the motor will not start or come up to full speed without • Type—Feeders can be paralleled or individual.
computed at 100% of the nameplate rating of the unit. supplying the equipment. tripping an overcurrent protective device rated for 175%. • Length—Voltage drop becomes a consideration
Depending on the type of heating unit, the branch circuit The label may include the rating of the motor in horse- in long feeders.
Solution: First, determine the current required for • Derating factor—Conductor sizing includes
may require other considerations. power. This rating must be converted prior to determining
the heating unit: several factors: conduit fill, ambient temperature,
Fixed electric space heating is covered in detail in the branch-circuit load rating. Use Tables 430.247 through
Article 424—Fixed Electric Space-Heating Equipment. 430.250 for converting horsepower to amperes. These and connected load demand.
I=P
This article includes fixed equipment, such as central E tables are contained in the Reference Section at the end of • Neutral—A neutral wire may not be necessary
heating systems, boilers, heating cable, and unit heaters = 30,000 VA the text. with the feeder.
240 V • Demand factor—Continuous loads will affect
(baseboard, panel, and duct heaters). For information
= 125 A
regarding the installation, control, and specifics about Sample Problem 12-11 feeder size.
each type of heater, refer to Article 424. • Protection—Various overcurrent protective
The Code also requires a disconnect for the heater Combining the current for the heating unit and the Problem: For an air-conditioning unit with a three- devices can be used with feeders.
and motor controller, as well as supplementary overcur- motor: phase, 230-volt, 20-hp motor, what is the required
rent protection for any fixed electric space-heating units. size of the branch-circuit overcurrent protective Summary of Commercial Service Load
The disconnect is for safety during maintenance. The Required current = 125 A + 6 A
= 131 A
device? Computation Procedure
disconnecting means must be within sight of the unit and
must disconnect all components of the heating unit, Solution: Use Table 430.250 to convert horse- 1. Determine the general lighting load based on the total
The conductors must be designed for 125% of this power to amperes. 20 horsepower with a 230-volt
including any overcurrent protective devices, contactors, square footage multiplied by the volt-ampere load
current (Section 424.3(B)): supply is equal to 54 amps. This load must be
elements, and motor controllers. indicated in Table 220.12.
The rules for sizing the branch-circuit wiring and increased by 125% for the conductor ampacity:
Required conductor capacity = 131 A × 1.25 2. If the lighting is a continuous load, as is true of most
overcurrent protection are very specific. The rating on the = 164 A commercial lighting, increase the load by 125%. That
equipment nameplate is used to determine the load. If the Conductor ampacity = 54 A × 1.25 is, multiply by 1.25. (Section 210.20(A))
equipment operates continuously for at least three hours, The overcurrent protective device must be the next = 67.5 A 3. For feeder and service loads, use Table 220.42 and
its rating must be increased by a factor of 1.25. highest standard size (Section 240.6), which is 175 amps. apply the lighting demand factor required for the type
Fixed electric space heating shall be considered Using Table 310.15(B)(16), 2/0 AWG copper conduc- The next highest standard overcurrent protective of building.
continuous load. Several general rules must be followed tors are needed. The equipment grounding conductor device rating is 70 amps. 4. After computing both air-conditioning and heating
when sizing the overcurrent protective devices for branch can be a 6 AWG copper conductor (Section 250.122). loads, omit the smaller of the two. (Section 220.60)
156 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 157

5. Compute receptacle outlets as follows:


• Receptacles as 180VA each. (Section 220.14(I)) Sample Problem 12-12 Sample Problem 12-12 Continued Sample Problem 12-13 Continued
• Multioutlet assemblies at 180 VA per each 5′
portion. (Section 220.14(H)(1)) Problem: A small retail store is being constructed. All loads are added to determine the total load:
needed. The 3/4-hp, 208-volt motors draw 3.5 amps,
• Show windows at either of the following (Section Its power supply is single-phase, 120/240-volt. The
Total load = 29,500 VA + 10,800 VA + 50,000 VA + 1470 VA as shown in Table 430.250. The actual motor voltage
220.14(G)): store is 80′ × 60′ and has several loads:
= 91,770 VA is 208 V × 1.732 (or 360 volts) because the service
(1) The unit load per outlet as required in 50-kVA heating equipment
is three-phase.
other provisions of Section 220.14 25-kVA air-conditioning unit
The total current can be calculated:
(2) At 200 VA per 300 mm (1 foot) of show 1/2-hp, 240-volt ventilating unit General lighting load = 2 × 80′ × 80′ × 3 1/2 VA/ft2
window 60 duplex receptacles = 44,800 VA
• Heavy-duty lamp holders at 600 VA each. I=P
40 linear feet of show-window lighting E
(Section 220.14(E)) 1.2-kVA outdoor sign lighting = 91,770 VA Show-window lighting load = 50′ × 200 VA
• Others as outlined in Section 220.14 Copper THW conductors are used as feeders. What 240 V = 10,000 VA
6. Apply any of the demand factors as shown in Table = 382 A
size should the current-carrying feeders be?
220.44 for receptacle loads and Table 220.56 for Exterior lighting load = 30 × 175 VA
Solution: First, all the loads must be computed. Using Table 310.16, 500 kcmil conductors will be = 5250 VA
kitchen equipment loads.
The heating unit and air-conditioning unit will not sufficient.
7. Add the sign lighting load (1200 VA minimum).
be used at the same time, so only the larger load is The neutral feeder conductor is sized for the Receptacle load = 200 × 180 VA
(Section 220.14(F))
needed. The 1/2-hp, 240-volt motor draws a current 120-volt loads (lighting and receptacles) only. = 36,000 VA
8. Compute the motor loads using the appropriate tables
in Article 430. of 4.9 amps, as shown in Table 430.248.
Neutral feeder load = Lighting load + Receptacle load Heating/air-conditioning load = 85,000 VA
9. Increase largest motor load based on full-load current = 29,500 VA + 10,800 VA
General lighting load = 80′ × 60′ × 3 VA/ft2
by 25%. (Section 430.24) = 40,300 VA Motor load = 3 × 3.5 A × 360 V
= 14,400 VA
10. Size the service and service conductors. Compute by = 3780 VA
dividing the total load by the line voltage. Conductor The current can be calculated:
Show-window lighting load = 40′ × 200 VA The total lighting load is the combination of the
size is selected from Table 310.15(B)(16).
11. Using the guideline given in Section 250.24(C), size = 8000 VA I=P three separate lighting loads.
E
the grounded service conductor. Be sure the grounded
Sign lighting load = 1200 VA = 40,300 VA Total lighting load = 44,800 VA + 10,000 VA + 5250 VA
service conductor is not smaller than the grounding 240 V
electrode conductor as given in Table 250.66. = 168 A = 60,050 VA
Receptacle load = 60 × 180 VA
12. Provided there is no discharge lighting, the neutral A 2/0 AWG copper conductor should be used for the
= 10,800 VA The motor load and lighting loads are continuous,
load—if over 200 amperes—can be derated by 70%. neutral feeder conductor. so the conductors must supply 125% of the full-load
Refer to Section 220.61.
Heating/air-conditioning load = 50,000 VA current:
Sample Problems Total lighting load = 60,050 VA × 1.25
Motor load = 4.9 A × 240 V
The following examples represent a small sampling = 1176 VA = 75,063 VA
of situations requiring computations to determine correct Sample Problem 12-13
Motor load = 3780 VA × 1.25
sizing of equipment, conductors, overcurrent protection, The total lighting load is the combination of the
and other load demands encountered in commercial three separate lighting loads. Problem: A two-story office building (80′ × 80′) is = 4725 VA
wiring. The main purpose is to introduce the concept and supplied with 120/208-volt service. Several loads
All loads are added to determine the total load:
give the reader a general feel for the overall procedure. Total lighting load = 14,400 VA + 8000 VA + 1200 VA are supplied:
Numerous other factors such as wiring methods, routing, = 23,600 VA 75-kVA air-conditioning unit Total load = 75,063 VA + 36,000 VA + 85,000 VA + 4725 VA
distances, and voltage drop (to name a few) have been 85-kVA heating unit = 200,788 VA
purposefully ignored here for the sake of simplicity. Still, The motor load and lighting loads are continuous, 200 duplex receptacles
by reviewing and understanding these examples and the so the conductors must supply 125% of the full- 50 linear feet of show window The total current can be calculated:
step-by-step methodology, the commercial electrician, load current: 30 exterior light fixtures (175 VA each)
designer, engineer, and student will be better equipped to 3 blower motors (3/4-hp, 208-volt) I=P
E
move on to the “real” calculations required in practical Total lighting load = 23,600 VA × 1.25 Copper THW conductors are used as feeders. What
design situations. size should the current-carrying conductors be? = 200,788 VA
= 29,500 VA 360 V
The following problems illustrate load calculation = 557 A
Solution: First, all loads must be computed. The
and feeder sizing for commercial structures: Motor load = 1176 VA × 1.25 heating unit and air-conditioning unit will not be Using Table 310.16, 1250 kcmil conductors will be
• Small retail store—Sample Problem 12-12. = 1470 VA used at the same time, so only the larger load is sufficient.
• Office building—Sample Problem 12-13.
• Restaurant—Sample Problem 12-14. (Continued on the following page.) (Continued)
• Hotel—Sample Problem 12-15.
158 Modern Commercial Wiring Chapter 12 Branch Circuits and Feeders 159

Sample Problem 12-14 Sample Problem 12-15 Continued

Problem: A restaurant is supplied with three-wire, Cooking equipment load = 52,000 VA The total reduced lighting load is determined: All loads are added to determine the total load:
120/240-volt service. The restaurant is 50′ × 80′ and
has several loads: Table 220.56 contains load-reduction factors for Lighting load = 10,000 VA + 32,000 VA + 8000 VA Total load = 50,000 VA + 2,160,000 VA + 37,500 VA
(1) 12-kW electric range (120-volt) commercial kitchen equipment. For six or more pieces = 50,000 VA = 2,247,500 VA
(1) 10-kW water heater (240-volt) of equipment, the feeder conductors can be designed
(2) 8-kW fryers (240-volt) for 65% of the load. The air-conditioning load must be calculated. The The total current can be calculated:
(2) 1.5-kW coffeemakers (120-volt) voltage is 208 V × 1.732 (360 volts) due to the three-
(1) 2.5-kW steam table (120-volt) Reduced cooking equipment load = 52,000 VA × 0.65 phase supply: I=P
= 33,800 VA E
(2) 3.0-kW toasters (120-volt)
(1) 2.5-kW disposal unit (120-volt) Air-conditioning load = 360 V × 30 A = 2,247,500 VA
The total lighting load is the combination of the two 360 V
(1) 1.5-kW outdoor sign (120-volt) = 10,800 VA = 6243 A
separate lighting loads.
(1) 40-kW heating unit
This is larger than the heating load, so the air-conditioning
(26) duplex receptacles Total lighting load = 8000 VA + 1500 VA The total current is 6243 A.
load is used in the total load. The load per room is
Copper THW conductors are used as feeders. What = 9500 VA 10,800 VA, so it must be multiplied by 200 to determine
size should the current-carrying feeders be?
the total load:
Solution: First, the loads must be computed. The lighting loads are continuous, so the conductors
must supply 125% of the full-load current: Total air-conditioning load = 10,800 VA × 200
General lighting load = 50′ × 80′ × 2 VA/ft2 = 2,160,000 VA
= 8000 VA Total lighting load = 9500 VA × 1.25
= 11,875 VA General equipment load = 30,000 VA × 1.25
Sign lighting load = 1500 VA = 37,500 VA
All loads are added to determine the total load:
Receptacle load = 26 × 180 VA
= 4680 VA Load = 11,875 VA + 4680 VA + 40,000 VA + 33,800 VA
= 90,355 VA
Review Questions 14. Compute the receptacle load for a department store
having 165 duplex receptacles.
Heating load = 40,000 VA Answer the following questions. Do not write in this book.
The total current can be calculated: 15. A furniture store has 60 linear feet of show window.
The cooking equipment will be combined as the 1. What type of conductors extend beyond the final Calculate this continuous load.
cooking equipment load: I=P overcurrent device? 16. What is the minimum outside sign lighting load
E 2. What type of conductors originate at the main discon- required by the Code?
Electric range: 12,000 VA = 90,355 VA nect device and terminate at panelboards and load 17. What is the general lighting load for a 50-room motel
240 V
Water heater: 10,000 VA = 377 A centers? where each room is 12′ × 20′?
Fryers: 16,000 VA 3. How is the rating of a branch circuit determined? 18. A 24-hour service restaurant has 75 duplex recepta-
Coffeemakers: 3000 VA Using Table 310.15(B)(16), 500 kcmil conductors will 4. What is the smallest conductor permitted for use in a cles. Calculate the total load for feeder calculations.
Steam table: 2500 VA be sufficient. branch circuit? 19. What is the service demand for a small bank mea-
Toasters: 6000 VA 5. What color insulation is used on equipment grounding suring 2500 ft2 and supplied with 208/120-volt,
Disposal unit: 2500 VA conductors? three-phase service? Assume lighting as continuous.
6. Define continuous load. The bank has the following loads:
7. What are the five general types of branch-circuit loads? 15 kW heating (208-volt)
Sample Problem 12-15 8. If the exact number of receptacles is unknown, how 7.5 hp air conditioning
can the receptacle load be calculated? 50 linear feet of show window
Problem: A 200-unit hotel is supplied with three- General lighting load = 200 × 300 ft2 × 2 VA/ft2 9. How is the show-window lighting load determined? 25 duplex receptacles
phase, 120/208-volt service. Each unit is 300 ft2, has a = 120,000 VA 10. How many receptacles must be installed for the 20. A new high school is to be erected, supplied with
30-amp air conditioner (208-volt) and has a heating nondwelling receptacle loads derating to reduce the 208/120-volt, single-phase power. The school has the
load of 8 kilowatts. The hotel also has a 30-kilowatt This load can be reduced in accordance with Table total receptacle load? following dimensions and loads. Calculate the total
continuous load for general equipment. What is the 220.42: 11. A large hotel has 2500 ft2 of hallway space. Assuming feeder conductor and feeder neutral loads. Assume
total current that must be supplied to the hotel? continuous load, how many volt-amperes should be all lighting loads are continuous.
50% of 0–20 kW = 10,000 VA
Solution: First, all loads must be computed. The 40% of 20–100 kW = 32,000 VA
allowed for this load for service computation? 30,000 ft2 classroom space
heating unit and air-conditioning unit will not be used at 30% of 100–120 kW = 8000 VA
12. Calculate the general lighting load for a commercial 6000 ft2 auditorium
the same time, so only the larger load is needed. Section warehouse having an area of 90,000 ft2. Assume 5000 ft2 cafeteria (use restaurant load)
220.14 explains that the receptacle loads do not need continuous duty. 10 kW outside lighting (120-volt)
(Continued on the following page.) 13. What is the demand factor used for four kitchen 225 duplex receptacles (120-volt)
to be included.
equipment loads in a commercial cafeteria?
160 Modern Commercial Wiring

Kitchen equipment: (2) 2.5 kW toasters (208-volt)


(2) 15 kW ovens (208-volt) (1) 1/2 hp vent fan (120-volt)
(2) 10 kW ranges (208-volt) (1) 3/4 hp blower motor (120-volt)
(4) 4 kW fryers (208-volt) Heating:
(1) 10 kW water heater (208-volt) 40 kW electric heat (208-volt)
(1) 3 kW dishwasher (208-volt)

USING THE NEC


Refer to the National Electrical Code to answer the 4. How is the size for a feeder overcurrent protective
following questions. Do not write in this book. device determined?
1. In addition to Article 210, which other section 5. Article 220 addresses branch-circuit, feeder, and
contains information on branch circuits supplying service calculations. How are fractions of amperes
pipe organs? handled in calculations?
2. What is the minimum branch-circuit current rating 6. Show-window loads can be computed in two ways.
for cooking ranges with ratings of 8 3/4 kW or Name the ways.
higher?
3. How near to the appliance does a dedicated appli-
ance receptacle need to be installed?

You might also like