Quotation Document (Un-Priced)

Quotation No. : TKLQ_ME_160919-K1

PROJECT : Al-Zour Refinery Project

LOCATION : Al-Zour, Kuwait

CLIENT : HDEC-SAIPEM-SKEC

MR NO. : P4045ZOR-MR-EL-CM-008-003

VENDOR : THERMON KOREA LTD.

DATE : 2016-09-19
TABLE OF CONTENTS

1.0 QUOTATION & BILL OF MATERIAL

2.0 SPARE PARTS FOR TWO(2) YEARS OPERATION

3.0 CLARIFICATIONS

4.0 ELECTRIC HEAT TRACING LOAD CHART

5.0 RELATED CATALOGUES

6.0 INSTALLATION PROCEDURES


1.0 QUOTATION & BILL OF MATERIAL
THERMON KOREA LTD. QUOTATION
5F, DaeWon B/D, 11, Teheran-ro 98-gil
DATE : 2016-09-19
Gangnam-gu, Seoul 135-846, Korea
TEL : (02)6329-2653 FAX : (02)6329-2635
QUOTE No. : TKLQ_ME_160919-K1
http://www.thermon.com

PROJECT : Al-Zour Refinery Project

QUOTE TO : Hyundai Engineering & Construction Co., Ltd.


Attn : Ho-jun Lee DELIVERY TERMS : Ex works USA, EUROPE & GCC
PHONE No. : +82-2-746-3298 PAYMENT TERMS : (see below)
FAX No. : VALID TO : 2016-10-19
QUOTE BY : Kui-hwan Kim / Sales manager CONTACT : Kuihwan Kim / 02-6329-2641

No. Q'ty Description Extended Price

1 1 lot ELECTRIC HEAT TRACING MATERIAL & ACCESSORIES


2 1 lot SPARE PARTS FOR ERECTION, PRE-COMMISSIONING,
COMMISSIONING & START-UP
3 1 lot ENGINEERING & DOCUMENTATION FEE ( Detailed Engg Charges)
4 1 lot PACKING & TRANSFORTATION FEE

Currency USD Total

<OPTIONAL>

1 1 lot SPARE PARTS FOR TWO(2) YEARS OPERATION

2 1 M-day SUPERVISION OF INSTALLATION, TESTING & COMMISSIONING


TRAINING FOR OPERATION AND MAINTENANCE AT SITE
- 6 days a week, 8 hrs a day
- Traveling, boarding & lodging and local expenses, extra at actual (see below)

General remarks
1. VALIDITY : 30DAYS FROM THE QUOTED DATE.
2. SUPPLY DUE DATE : HEATING CABLE & ACCESSORIES: 08-10 WEEKS AFTER APPROVAL OF BOM.
3. SUPPLY DUE DATE : POWER DISTRIBUTION PANEL: 10-12 WEEKS AFTER APPROVAL OF GA & SLD DRAWINGS.
4. THIS QUOTATION IS BASED ON ACCEPTED A ELECTRICAL HEAT TRACED LINE TABLE.
5. DELIVERY TERMS : Ex works USA, EUROPE & GCC
6. LEGALIZATION CHARGES @ USD 200 FOR EACH DOCUMENT (E.G CERT OF ORIGIN, COMM INVOICE) IF APPLICABLE
7. STANDARD PACKAGING , SUITABLE FOR AIR SHIPMENT
8. SUPERVISOR ASSISTANCE CAN BE PROVIDED PER DAY, TO BE READ IN ACCORDANCE WITH BELOW CONDITIONS :
- Above rates are excluding cost for To & Fro travel,Lodging, local transport and all required VISA's & other subsequent cost to be borne by byuer.
- Per diem rates will apply from the date of departure of Thermon personnel from Base station & will remain valid till the day of return back to base station.
- Per diem are applicable for a 8 hours working day, 06 days a week. Overtime rates (1.5 times of per diem rates) will apply for work done on weekends.
- The seventh days of the week is considered as Holiday/Leave, if personnel is mobilized in the site & staying idle on this day per diem rates will apply. If personnel is required to
work on the seventh day of the week than Overtime rates (1.5 times of per diem rates) will apply.

9. PAYMENT TERMS : 90% AGAINST SHIPPING DOCUMENTS BEFORE DISPATCH OF MATERIAL. / 10% against final submission of documents.
10. ALL TYPES OF POWER CABLE GLANDS ARE EXCLUDED FROM OUR SCOPE OF SUPPLY.

Thermon's products, technology and services may be subject to applicable U.S. laws, including U.S. export control laws. Export, re-export, use or diversion
contrary to U.S. law is prohibited. If it is discovered at any time that a transaction may result in a violation of applicable U.S. law, Thermon reserves the right to
cancel all or such prohibited parts of the transaction and suspend future performance without further liability or penalty of any nature. Also, thermon’s an
exclusion of consequential damages .

Thermon provides this quotation based upon following terms and conditions.
Neither Party shall be liable to the other Party in contract, tort, warranty, strict liability or any other legal theory for any indirect, consequential, incidental, punitive
or exemplary damages or loss of profit or production. Notwithstanding anything to the contrary the liability of Supplier to the Purchaser under the Contract shall
in no case exceeding 100% of the Contract Price, provided however that such limitation of liability shall not apply to liabilities resulting from the gross
negligence, fraud, or willful misconduct of the Supplier or Sub-Suppliers. All liability under this contract shall terminate upon expiration of the warranty period as
defined in the Contract or any agreed extension thereof.

Byung Ho Park
PRESIDENT
THERMON KOREA LTD.
THERMON KOREA LTD.
(A fully owned subsidiary of Thermon Manufacturing Co. USA)
5F, DaeWon B/D, 11, Teheran-ro 98-gil
Gangnam-gu, Seoul 135-846, Korea
Telephone : +82-2-6329-2653 Fax : +82-2-6329-2635
kuihwan.kim@thermon.com www.thermon.com

PRICED BOM (Construction Qty.)


Shipment Unit
Item No Item Description Catalog No Qty UOM Make Total Price Remarks
point Price
USD USD
A Heat Tracing Cable and Accessories
1 Heating Cable (Self Regulating) KSX-15-2-OJ 2521 M Thermon USA

2 Heating Cable (Self Regulating) KSX-20-2-OJ 6344 M Thermon USA

Field Junction Box, GRP Enclosure


3 Std B/O 35 ea - GCC
(1 i/c + 3 o/g)

4 Power Junction Box ZP-Power 134 ea Thermon USA


5 Temperature Sensor PTD-100-1mtr 64 ea Thermon EUROPE
6 Junction Box for Temperature Sensor ZP-PTD100-XP 64 ea Thermon EUROPE
7 End Termination Kit for KSX Cable PETK-2 268 ea Thermon USA
8 Splice Termination Kit for KSX Cable SCTK-2 80 ea Thermon USA

9 End Kit for Tee Splice Kit (5 each per package) ET-8C 2 Pkg Thermon USA

10 In-Line Splice kit ZS/ZE 60 ea Thermon USA


11 Tee Splice kit ZS/ZE 10 ea Thermon USA
12 SS Band B-4 90 ea Thermon USA
13 SS Band B-10 10 ea Thermon USA

14 SS Band B-21 190 ea Thermon USA


15 Fiber Tape (33m per roll) FT-1H 936 Rolls Thermon USA
16 Caution Label (25nos. per Pkg.) CL 58 Pkg Thermon USA

B Power Distribution

1 Power Distribution Panel + Controller Panel


Incomer: 400Vac 3Ph 4wire ( as per Thermon drg) 3 ea - GCC
Main Incomer Breaker: 300A, 4P
Outgoing : 07nos. 220V (32A,2P) + 09nos. 400V
(32A,4P) o/g feeders + 02nos. 220V (32A,2P) + 02nos.
400V (32A,4P) Spare Feeders.
Suitable for Outdoor installation

Controller Panel
Controller Panel with 2nos. TCM18 pre-wired control &
monitoring panel (24 channels) in a NEMA 4X, SS
( as per Thermon drg) 3 ea Thermon USA
enclosure suitable for outdoor hazardous area
installation, Class-1 Div-2 equivalent to Zone-2
2 Power Distribution Panel
Incomer: 400Vac 3Ph 4wire ( as per Thermon drg) 1 ea - GCC

Main Incomer Breaker: 300A, 4P


Outgoing : 08nos. 220V (32A,2P) + 08nos. 400V
(32A,4P) o/g feeders + 02nos. 220V (32A,2P) + 02nos.
400V (32A,4P) Spare Feeders. + 6nos 220V (32A,2P)
o/g feeders for metering skid with 2Nos.
Microprocessor based multi-circuit controllers (30
channel controllers), TCM18.
Suitable for installation in Indoor safe area

Total Ex works USA, EUROPE & GCC

Page 1 of 1
THERMON KOREA LTD.
(A fully owned subsidiary of Thermon Manufacturing Co. USA)
5F, DaeWon B/D, 11, Teheran-ro 98-gil
Gangnam-gu, Seoul 135-846, Korea
Telephone : +82-2-6329-2653 Fax : +82-2-6329-2635
kuihwan.kim@thermon.com www.thermon.com

PRICED BOM (Startup & Commissioning Spares)


Shipment Unit
Item No Item Description Catalog No Qty UOM Make Total Price Remarks
point Price
USD USD
A Heat Tracing Cable and Accessories

Field Junction Box, GRP Enclosure


1 Std B/O 2 ea - GCC
(1 i/c + 3 o/g)

2 Power Junction Box ZP-Power 2 ea Thermon USA


3 Temperature Sensor PTD-100-3mtr 2 ea Thermon EUROPE
4 Junction Box for Temperature Sensor ZP-PTD100-XP 2 ea Thermon EUROPE

5 End Termination Kit for KSX Cable PETK-2 4 ea Thermon USA


6 Splice Termination Kit for KSX Cable SCTK-2 12 ea Thermon USA
7 End Kit for Tee Splice Kit (5 each per package) ET-8C 1 Pkg Thermon USA
8 In-Line Splice kit ZS/ZE 2 ea Thermon USA
9 Tee Splice kit ZS/ZE 5 ea Thermon USA

10 SS Band B-4 10 ea Thermon USA

11 SS Band B-10 5 ea Thermon USA


12 SS Band B-21 15 ea Thermon USA
13 Fiber Tape (33m per roll) FT-1H 15 Rolls Thermon USA

14 Caution Label (25nos. per Pkg.) CL 10 Pkg Thermon USA


Ex works USA, EUROPE &
Total
GCC

Page 1 of 1
2.0 SPARE PARTS FOR TWO(2) YEARS
THERMON KOREA LTD.
(A fully owned subsidiary of Thermon Manufacturing Co. USA)
5F, DaeWon B/D, 11, Teheran-ro 98-gil
Gangnam-gu, Seoul 135-846, Korea
Telephone : +82-2-6329-2653 Fax : +82-2-6329-2635
kuihwan.kim@thermon.com www.thermon.com

PRICED BOM (2 Year Operational Spares) _ OPTION


Shipment Unit
Item No Item Description Catalog No Qty UOM Make Total Price Remarks
point Price
USD USD
A Heat Tracing Cable and Accessories
1 Heating Cable (Self Regulating) KSX-15-2-OJ 100 M Thermon USA

2 Heating Cable (Self Regulating) KSX-20-2-OJ 150 M Thermon USA

Field Junction Box, GRP Enclosure


3 Std B/O 2 ea - GCC
(1 i/c + 3 o/g)

4 Power Junction Box ZP-Power 2 ea Thermon USA


5 Temperature Sensor PTD-100-3mtr 2 ea Thermon EUROPE
6 Junction Box for Temperature Sensor ZP-PTD100-XP 2 ea Thermon EUROPE

7 End Termination Kit for KSX Cable PETK-2 4 ea Thermon USA


8 Splice Termination Kit for KSX Cable SCTK-2 12 ea Thermon USA
9 End Kit for Tee Splice Kit (5 each per package) ET-8C 1 Pkg Thermon USA
10 In-Line Splice kit ZS/ZE 2 ea Thermon USA
11 Tee Splice kit ZS/ZE 5 ea Thermon USA

12 SS Band B-4 10 ea Thermon USA

13 SS Band B-10 5 ea Thermon USA


14 SS Band B-21 15 ea Thermon USA
15 Fiber Tape (33m per roll) FT-1H 15 Rolls Thermon USA

16 Caution Label (25nos. per Pkg.) CL 10 Pkg Thermon USA


Total Ex works USA, EUROPE & GCC

Page 1 of 1
3.0 CLARIFICATIONS
Assumptions/ Clarifications:

1. We have considered pipe length, valves, flanges from the doc. “eeP4045ZOR-
MR-EL-CM-008_O_APPENDIX B(0)” provided with the RFQ documents.

2. Please note that in absence of quantities of supports, we have not considered


any heating cable and accessories for them.

3. Please note that we have considered only ETR lines provided in the doc.
“eeP4045ZOR-MR-EL-CM-008_O_APPENDIX B(0)” in our scope.

4. Please note that as per MR doc. “P4045ZOR-MR-EL-CM-008_O” (clause no. 2.2),


we have considered self-regulating heating cable in our design.

5. Please note that we have considered -3Deg.C./ 50Deg.C as minimum/ maximum


ambient temperature in our design.

6. Please note that we have design our system on 220V AC single phase voltage by
considering ±5% negative tolerance.

7. Please note that we have considered operating temperature as maintain


temperature in our design.

8. Please note that there are some pipelines whose operating temperature are not
given, hence for these lines we have not considered any heating cable and
accessories for them. Please provide the operating temperature (highlighted with
“data required” in the design sheet) so that we include these lines in our scope
of supply.

9. Please note that we have considered Mineral Wool insulation material as per doc.
“P4045ZOR-00-10-98-006_O”.

10. Please note that we have considered insulation thickness provided in the
Appendix-A of doc. “P4045ZOR-00-10-98-006_O”.

THERMON . . . The Heat Tracing Specialists


www.thermon.com
5F, DaeWon B/D, 11, Teheran-ro 98-gil, Gangnam-gu, Seoul 135-846, Korea• Thermon Korea Ltd.
• Phone: +82-2-6329-2681 • Fax: +82-2-6329-2635
11. Please note that in absence of details of instruments or vessels, we have not
considered any heat tracing cable and accessories for them.

12. Please note that there are some pipelines whose design/ exposure temperature
is not given, hence presently we are assuming that all these lines are having
design temperature of 90Deg.C, therefore we have considered KSX type self-
regulating heating cable in our design.

13. Please note that in order to further optimize the design and to make cost
effective proposal, we have utilizes the three phase circuits also in our design. In
3 phase circuitry, 4core power Cables need to be installed from Power
distribution panel to each individual field junction box mounted in the field, close
to heat traced pipe lines & 03 pipe mounted single phase power junction box
(ZP) will be fed from each field junction box.

14. Please note that we have considered 3nos. power distribution panel suitable for
outdoor installation and 1no. power distribution panel suitable for indoor
installation in safe area as per MR doc. “P4045ZOR-MR-EL-CM-008_O” (clause no.
2.3).

15. Please note that we have considered additional 6nos. outgoing feeder for heat
tracing of metering skid in indoor safe area distribution panel. Please refer bill of
material for the same.

16. Please note that there are many pipelines in the P&ID’s which are shown as ETR
lines but they are not mentioned in the line lists, hence in absence of details of
these lines we have not considered them in our design and hence not considered
any heating cable and accessories for them.

THERMON . . . The Heat Tracing Specialists


www.thermon.com
5F, DaeWon B/D, 11, Teheran-ro 98-gil, Gangnam-gu, Seoul 135-846, Korea• Thermon Korea Ltd.
• Phone: +82-2-6329-2681 • Fax: +82-2-6329-2635
4.0 ELECTRIC HEAT TRACING LOAD
DESIGN SHEET (PIPELINES)

Project Al-Zour Refinery Project Insulation Material: Mineral Wool Heat Tracing Standard: IEEE-515/ IEC 62086
Owner Kuwait National Petroleum Company (KNPC) Insulation Thk: As per below Heat Tracing Supply Voltage 220V AC Single Phase
Client HDEC-SAIPEM-SKEC Min.Ambient -3Deg. C. Maxm ckt loading for EHT 32A
RFQ Ref. No. Email Dated: 29.08.2016 Max.Ambient 50Deg. C. Circuit Breaker Type Type C
TME Ref. No. Maint. Temp As per below Design Margin for Hloss 10%
Qty.of Qty.of No of Qty.of
Maint. Max. Oper. Design Pipe Design Htg cable Htg Cab Trace No of No of Htg cab Start-up Optg
Sl No P&ID No. Unit Line No. Pipe size Tracer/ Tracer/ Support Tracer/ Optg cur
Temp. Temp. Temp. Length Heat Loss model o/p ratio Valves Flanges qty cur Power
Valve Flange s Support
inch M w/m w/m Nos. M Nos. M Nos. M A A VA
1 P4045ZOR-93-08-1-J024-2 93 80-93P01-1201-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 6 1.06 11 0.24 0 0.56 23.00 6.44 3.2 711
2 P4045ZOR-93-08-1-J024-2 93 80-93P01-2233-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
3 P4045ZOR-93-08-1-J024 93 350-93P01-1121-31031K-ETR 14.0 65.0 65 26.0 55.4 KSX-15-2 30.9 2.0 0 5.94 5 0.46 0 1.09 54.30 15.20 7.6 1678
4 P4045ZOR-93-08-1-J024 93 350-93P01-1121-31031K-ETR 8.0 65.0 65 3.0 36.9 KSX-15-2 30.9 2.0 5 3.35 3 0.32 0 0.82 23.71 6.64 3.3 733
5 P4045ZOR-93-08-1-J024-1 93 80-93P01-1200-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 7 1.06 16 0.24 0 0.56 25.26 7.07 3.5 781
6 P4045ZOR-93-08-1-J024-1 93 80-93P01-2230-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
7 P4045ZOR-93-08-1-J032-2 93 80-93P01-1200-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
8 P4045ZOR-93-08-1-J024 93 350-93P01-1121-31031K-ETR 14.0 65.0 65 22.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 44.00 12.32 6.2 1360
9 P4045ZOR-93-08-1-J024 93 500-93P01-1107-31031K-ETR 20.0 65.0 80 90 24.0 76.2 KSX-20-2 47.4 2.0 0 9.14 2 0.53 0 1.39 49.06 16.68 10.6 2326
10 P4045ZOR-93-08-1-J024 93 500-93P01-1107-31031K-ETR 16.0 65.0 80 90 2.0 62.3 KSX-20-2 47.4 2.0 5 7.01 6 0.48 0 1.19 41.93 14.26 9.0 1988
11 P4045ZOR-93-08-1-J025-2 93 80-93P02-1203-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 6 1.06 11 0.24 0 0.56 23.00 6.44 3.2 711
12 P4045ZOR-93-08-1-J025-2 93 80-93P02-2239-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
13 P4045ZOR-93-08-1-J025 93 350-93P02-1123-31031K-ETR 14.0 65.0 80 90 19.0 55.4 KSX-15-2 30.9 2.0 0 5.94 5 0.46 0 1.09 40.30 11.28 5.7 1246
14 P4045ZOR-93-08-1-J025 93 350-93P02-1123-31031K-ETR 8.0 65.0 80 90 3.0 36.9 KSX-15-2 30.9 2.0 5 3.35 3 0.32 0 0.82 23.71 6.64 3.3 733
15 P4045ZOR-93-08-1-J025-1 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 7 1.06 16 0.24 0 0.56 25.26 7.07 3.5 781
16 P4045ZOR-93-08-1-J025-1 93 80-93P02-2236-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
17 P4045ZOR-93-08-1-J032-2 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
18 P4045ZOR-93-08-1-J025 93 350-93P02-1123-31031K-ETR 14.0 65.0 80 90 23.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 46.00 12.88 6.5 1422
19 P4045ZOR-93-08-1-J025 93 500-93P02-1109-31031K-ETR 16.0 65.0 80 90 2.0 62.3 KSX-20-2 47.4 2.0 5 7.01 6 0.48 0 1.19 41.93 14.26 9.0 1988
20 P4045ZOR-93-08-1-J025 93 500-93P02-1109-31031K-ETR 20.0 65.0 80 90 24.0 76.2 KSX-20-2 47.4 2.0 0 9.14 2 0.53 0 1.39 49.06 16.68 10.6 2326
21 P4045ZOR-93-08-1-J026-1 93 80-93P03-1204-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 7 1.06 16 0.24 0 0.56 25.26 7.07 3.5 781
22 P4045ZOR-93-08-1-J026-1 93 80-93P03-2242-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
23 P4045ZOR-93-08-1-J033-2 93 80-93P03-1204-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
24 P4045ZOR-93-08-1-J026 93 350-93P03-1122-31031K-ETR 14.0 65.0 65 22.0 55.4 KSX-15-2 30.9 2.0 0 5.94 5 0.46 0 1.09 46.30 12.96 6.5 1431
25 P4045ZOR-93-08-1-J026 93 500-93P03-1108-31031K-ETR 16.0 65.0 80 90 2.0 62.3 KSX-20-2 47.4 2.0 5 7.01 6 0.48 0 1.19 41.93 14.26 9.0 1988
26 P4045ZOR-93-08-1-J026 93 500-93P03-1108-31031K-ETR 20.0 65.0 80 90 24.0 76.2 KSX-20-2 47.4 2.0 0 9.14 2 0.53 0 1.39 49.06 16.68 10.6 2326
27 P4045ZOR-93-08-1-J026-2 93 80-93P03-1205-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 6 1.06 11 0.24 0 0.56 23.00 6.44 3.2 711
28 P4045ZOR-93-08-1-J026-2 93 80-93P03-2245-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
29 P4045ZOR-93-08-1-J026 93 350-93P03-1122-31031K-ETR 14.0 65.0 65 19.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 38.00 10.64 5.3 1175
30 P4045ZOR-93-08-1-J026 93 350-93P03-1122-31031K-ETR 8.0 65.0 65 3.0 36.9 KSX-15-2 30.9 2.0 5 3.35 3 0.32 0 0.82 23.71 6.64 3.3 733
31 P4045ZOR-93-08-1-J027-1 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 7 1.06 16 0.24 0 0.56 25.26 7.07 3.5 781
32 P4045ZOR-93-08-1-J027-1 93 80-93P04-2248-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
33 P4045ZOR-93-08-1-J033-2 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
34 P4045ZOR-93-08-1-J027 93 350-93P04-1124-31031K-ETR 14.0 65.0 80 90 23.0 55.4 KSX-15-2 30.9 2.0 0 5.94 5 0.46 0 1.09 48.30 13.52 6.8 1493
35 P4045ZOR-93-08-1-J027 93 500-93P04-1110-31031K-ETR 16.0 65.0 80 90 2.0 62.3 KSX-20-2 47.4 2.0 5 7.01 6 0.48 0 1.19 41.93 14.26 9.0 1988
36 P4045ZOR-93-08-1-J027 93 500-93P04-1110-31031K-ETR 20.0 65.0 80 90 24.0 76.2 KSX-20-2 47.4 2.0 0 9.14 2 0.53 0 1.39 49.06 16.68 10.6 2326
37 P4045ZOR-93-08-1-J027-2 93 80-93P04-1207-31031K-ETR 3.0 65.0 80 90 14.0 20.9 KSX-15-2 30.9 1.0 6 1.06 11 0.24 0 0.56 23.00 6.44 3.2 711
38 P4045ZOR-93-08-1-J027-2 93 80-93P04-2251-31031K-ETR 3.0 data required 3.0 - - - - 2 1.06 7 0.24 0 0.56 - - - -
39 P4045ZOR-93-08-1-J027 93 350-93P04-1124-31031K-ETR 8.0 65.0 80 90 3.0 36.9 KSX-15-2 30.9 2.0 5 3.35 3 0.32 0 0.82 23.71 6.64 3.3 733
40 P4045ZOR-93-08-1-J027 93 350-93P04-1124-31031K-ETR 14.0 65.0 80 90 19.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 38.00 10.64 5.3 1175
41 P4045ZOR-93-08-1-J032-002 93 100-93P01-1161-31031K-ETR 2.0 65.0 80 90 5.0 16.1 KSX-15-2 30.9 1.0 5 0.61 8 0.21 0 0.50 9.73 2.72 1.4 301
42 P4045ZOR-93-08-1-J032-002 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 15.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 15.00 4.20 2.1 464
43 P4045ZOR-93-08-1-J032-2 93 80-93P01-1200-31031K-ETR 3.0 65.0 80 90 20.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 20.00 5.60 2.8 618
44 P4045ZOR-93-08-1-J032-2 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 20.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 20.00 5.60 2.8 618
45 P4045ZOR-93-08-1-J032-2 93 80-93P01-1200-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
46 P4045ZOR-93-08-1-J032-2 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
47 P4045ZOR-93-08-1-J025 93 350-93P02-1123-31031K-ETR 14.0 65.0 80 90 46.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 92.00 25.76 12.9 2843
48 P4045ZOR-93-08-1-J025 93 500-93P02-1109-31031K-ETR 20.0 65.0 80 90 47.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 94.00 31.96 20.3 4456

Page. 1 of 5
Project Al-Zour Refinery Project Insulation Material: Mineral Wool Heat Tracing Standard: IEEE-515/ IEC 62086
Owner Kuwait National Petroleum Company (KNPC) Insulation Thk: As per below Heat Tracing Supply Voltage 220V AC Single Phase
Client HDEC-SAIPEM-SKEC Min.Ambient -3Deg. C. Maxm ckt loading for EHT 32A
RFQ Ref. No. Email Dated: 29.08.2016 Max.Ambient 50Deg. C. Circuit Breaker Type Type C
TME Ref. No. Maint. Temp As per below Design Margin for Hloss 10%
Qty.of Qty.of No of Qty.of
Maint. Max. Oper. Design Pipe Design Htg cable Htg Cab Trace No of No of Htg cab Start-up Optg
Sl No P&ID No. Unit Line No. Pipe size Tracer/ Tracer/ Support Tracer/ Optg cur
Temp. Temp. Temp. Length Heat Loss model o/p ratio Valves Flanges qty cur Power
Valve Flange s Support
inch M w/m w/m Nos. M Nos. M Nos. M A A VA
49 P4045ZOR-93-08-1-J033-002 93 100-93P03-1158-31031K-ETR 2.0 65.0 80 90 5.0 16.1 KSX-15-2 30.9 1.0 5 0.61 8 0.21 0 0.50 9.73 2.72 1.4 301
50 P4045ZOR-93-08-1-J033-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 15.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 15.00 4.20 2.1 464
51 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 15.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 15.00 4.20 2.1 464
52 P4045ZOR-93-08-1-J033-2 93 80-93P03-1204-31031K-ETR 3.0 65.0 80 90 20.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 20.00 5.60 2.8 618
53 P4045ZOR-93-08-1-J033-2 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 20.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 20.00 5.60 2.8 618
54 P4045ZOR-93-08-1-J033-2 93 80-93P03-1204-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
55 P4045ZOR-93-08-1-J033-2 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 5.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 5.00 1.40 0.7 155
56 P4045ZOR-93-08-1-J027 93 350-93P04-1124-31031K-ETR 14.0 65.0 80 90 46.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 92.00 25.76 12.9 2843
57 P4045ZOR-93-08-1-J005-1 93 100-93P07-1162-31031K-ETR 4.0 65.0 80 90 6.0 25.2 KSX-15-2 30.9 1.0 3 1.52 7 0.28 0 0.61 12.52 3.51 1.8 387
58 P4045ZOR-93-08-1-J008 93 300-93P07-2039-31031K-ETR 12.0 data required 10.0 - - - - 4 5.02 10 0.39 0 1.02 - - - -
59 P4045ZOR-93-08-1-J073 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 13.0 86.9 KSX-20-2 43.3 3.0 3 8.22 17 0.51 0 1.29 72.33 24.59 14.2 3132
60 P4045ZOR-93-08-1-J008 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 13.0 110.1 KSX-20-2 47.4 3.0 4 12.8 13 0.78 0 1.90 100.34 34.12 21.6 4757
61 P4045ZOR-93-08-1-J073 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 10.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 30.00 10.20 5.9 1299
62 P4045ZOR-93-08-1-J011-001 93 100-93LS07-1236-31042K-ETR 4.0 65.0 80 85 12.0 25.2 KSX-15-2 30.9 1.0 0 1.52 1 0.28 0 0.61 12.28 3.44 1.7 380
63 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 60.0 25.2 KSX-15-2 30.9 1.0 12 1.52 19 0.28 0 0.61 83.56 23.40 11.7 2583
64 P4045ZOR-93-08-1-J010-001 93 350-93P01-1121-31031K-ETR 14.0 65.0 65 7.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 14.00 3.92 2.0 433
65 P4045ZOR-93-08-1-J010-001 93 350-93P02-1123-31031K-ETR 14.0 65.0 80 90 7.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 14.00 3.92 2.0 433
66 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 3.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 10.50 3.57 2.1 455
67 P4045ZOR-93-08-1-J010-001 93 500-93P01-1107-31031K-ETR 20.0 65.0 80 90 4.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 8.00 2.72 1.7 380
68 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 4.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 12.00 4.08 2.6 569
69 P4045ZOR-93-08-1-J032-2 93 80-93P01-1200-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
70 P4045ZOR-93-08-1-J032-2 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
71 P4045ZOR-93-08-1-J010-001 93 350-93P01-1121-31031K-ETR 14.0 65.0 65 3.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 6.00 1.68 0.8 186
72 P4045ZOR-93-08-1-J024 93 500-93P01-1107-31031K-ETR 20.0 65.0 80 90 3.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 6.00 2.04 1.3 285
73 P4045ZOR-93-08-1-J010-001 93 350-93P01-1121-31031K-ETR 14.0 65.0 65 16.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 32.00 8.96 4.5 989
74 P4045ZOR-93-08-1-J010-001 93 500-93P01-1107-31031K-ETR 20.0 65.0 80 90 21.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 42.00 14.28 9.0 1991
75 P4045ZOR-93-08-1-J032-2 93 80-93P01-1200-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
76 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 60.0 25.2 KSX-15-2 30.9 1.0 9 1.52 22 0.28 0 0.61 79.84 22.36 11.2 2468
77 P4045ZOR-93-08-1-J032-2 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
78 P4045ZOR-93-08-1-J032-2 93 80-93P02-1202-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
79 P4045ZOR-93-08-1-J010-002 93 350-93P04-1124-31031K-ETR 14.0 65.0 80 90 3.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 6.00 1.68 0.8 186
80 P4045ZOR-93-08-1-J011-002 93 100-93LS07-1317-31042K-ETR 4.0 65.0 80 90 12.0 25.2 KSX-15-2 30.9 1.0 1 1.52 0 0.28 0 0.61 13.52 3.79 1.9 418
81 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 60.0 25.2 KSX-15-2 30.9 1.0 12 1.52 19 0.28 0 0.61 83.56 23.40 11.7 2583
82 P4045ZOR-93-08-1-J010-002 93 350-93P03-1122-31031K-ETR 14.0 65.0 65 7.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 14.00 3.92 2.0 433
83 P4045ZOR-93-08-1-J010-002 93 350-93P04-1124-31031K-ETR 14.0 65.0 80 90 7.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 14.00 3.92 2.0 433
84 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 4.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 12.00 4.08 2.4 520
85 P4045ZOR-93-08-1-J010-002 93 500-93P03-1108-31031K-ETR 20.0 65.0 80 90 4.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 8.00 2.72 1.7 380
86 P4045ZOR-93-08-1-J010-002 93 500-93P04-1110-31031K-ETR 20.0 65.0 80 90 16.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 32.00 10.88 6.9 1517
87 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 4.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 12.00 4.08 2.6 569
88 P4045ZOR-93-08-1-J033-2 93 80-93P03-1204-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
89 P4045ZOR-93-08-1-J033-2 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
90 P4045ZOR-93-08-1-J026 93 350-93P03-1122-31031K-ETR 14.0 65.0 65 3.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 6.00 1.68 0.8 186
91 P4045ZOR-93-08-1-J026 93 500-93P03-1108-31031K-ETR 20.0 65.0 80 90 3.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 6.00 2.04 1.3 285
92 P4045ZOR-93-08-1-J026 93 350-93P03-1122-31031K-ETR 14.0 65.0 65 21.0 55.4 KSX-15-2 30.9 2.0 0 5.94 0 0.46 0 1.09 42.00 11.76 5.9 1298
93 P4045ZOR-93-08-1-J010-002 93 500-93P03-1108-31031K-ETR 20.0 65.0 80 90 16.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 32.00 10.88 6.9 1517
94 P4045ZOR-93-08-1-J033-2 93 80-93P03-1204-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
95 P4045ZOR-93-08-1-J027 93 500-93P04-1110-31031K-ETR 20.0 65.0 80 90 17.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 34.00 11.56 7.3 1612
96 P4045ZOR-93-08-1-J033-2 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
97 P4045ZOR-93-08-1-J027 93 500-93P04-1110-31031K-ETR 20.0 65.0 80 90 3.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 6.00 2.04 1.3 285
98 P4045ZOR-93-08-1-J027 93 500-93P04-1110-31031K-ETR 20.0 65.0 80 90 16.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 32.00 10.88 6.9 1517
99 P4045ZOR-93-08-1-J033-2 93 80-93P04-1206-31031K-ETR 3.0 65.0 80 90 15.0 20.9 KSX-15-2 30.9 1.0 0 1.06 0 0.24 0 0.56 15.00 4.20 2.1 464
100 P4045ZOR-93-08-1-J027 93 500-93P04-1110-31031K-ETR 20.0 65.0 80 90 7.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 14.00 4.76 3.0 664

Page. 2 of 5
Project Al-Zour Refinery Project Insulation Material: Mineral Wool Heat Tracing Standard: IEEE-515/ IEC 62086
Owner Kuwait National Petroleum Company (KNPC) Insulation Thk: As per below Heat Tracing Supply Voltage 220V AC Single Phase
Client HDEC-SAIPEM-SKEC Min.Ambient -3Deg. C. Maxm ckt loading for EHT 32A
RFQ Ref. No. Email Dated: 29.08.2016 Max.Ambient 50Deg. C. Circuit Breaker Type Type C
TME Ref. No. Maint. Temp As per below Design Margin for Hloss 10%
Qty.of Qty.of No of Qty.of
Maint. Max. Oper. Design Pipe Design Htg cable Htg Cab Trace No of No of Htg cab Start-up Optg
Sl No P&ID No. Unit Line No. Pipe size Tracer/ Tracer/ Support Tracer/ Optg cur
Temp. Temp. Temp. Length Heat Loss model o/p ratio Valves Flanges qty cur Power
Valve Flange s Support
inch M w/m w/m Nos. M Nos. M Nos. M A A VA
101 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 6.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 6.00 1.68 0.8 186
102 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 5.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 16.50 5.61 3.6 783
103 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 6.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 6.00 1.68 0.8 186
104 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 5.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 16.50 5.61 3.6 783
105 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 6.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 6.00 1.68 0.8 186
106 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 5.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 16.50 5.61 3.6 783
107 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 6.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 6.00 1.68 0.8 186
108 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 5.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 16.50 5.61 3.6 783
109 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 4.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 12.00 4.08 2.6 569
110 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 4.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 12.00 4.08 2.6 569
111 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 44.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 44.00 12.32 6.2 1360
112 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 11.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 33.00 11.22 6.5 1429
113 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 8.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 25.50 8.67 5.5 1209
114 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 6.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 6.00 1.68 0.8 186
115 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 35.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 105.00 35.70 20.7 4547
116 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 29.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 88.50 30.09 19.1 4195
117 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
118 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
119 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 11.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 33.00 11.22 6.5 1429
120 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 8.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 25.50 8.67 5.5 1209
121 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 20.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 20.00 5.60 2.8 618
122 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 35.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 105.00 35.70 20.7 4547
123 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 29.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 88.50 30.09 19.1 4195
124 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 30.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 30.00 8.40 4.2 927
125 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
126 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 24.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 72.00 24.48 15.5 3413
127 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
128 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
129 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
130 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
131 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 28.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 84.00 28.56 16.5 3638
132 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
133 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
134 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
135 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
136 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
137 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
138 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
139 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
140 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
141 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
142 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
143 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
144 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
145 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
146 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
147 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
148 P4045ZOR-93-08-1-J011-001 93 100-93P01-1161-31031K-ETR 4.0 65.0 80 90 28.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 28.00 7.84 3.9 866
149 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 27.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 82.50 28.05 16.2 3573
150 P4045ZOR-93-08-1-J010-001 93 500-93P02-1109-31031K-ETR 20.0 65.0 80 90 8.0 76.2 KSX-20-2 47.4 2.0 0 9.14 0 0.53 0 1.39 16.00 5.44 3.4 759
151 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 27.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 82.50 28.05 17.8 3911
152 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 22.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 22.00 6.16 3.1 680

Page. 3 of 5
Project Al-Zour Refinery Project Insulation Material: Mineral Wool Heat Tracing Standard: IEEE-515/ IEC 62086
Owner Kuwait National Petroleum Company (KNPC) Insulation Thk: As per below Heat Tracing Supply Voltage 220V AC Single Phase
Client HDEC-SAIPEM-SKEC Min.Ambient -3Deg. C. Maxm ckt loading for EHT 32A
RFQ Ref. No. Email Dated: 29.08.2016 Max.Ambient 50Deg. C. Circuit Breaker Type Type C
TME Ref. No. Maint. Temp As per below Design Margin for Hloss 10%
Qty.of Qty.of No of Qty.of
Maint. Max. Oper. Design Pipe Design Htg cable Htg Cab Trace No of No of Htg cab Start-up Optg
Sl No P&ID No. Unit Line No. Pipe size Tracer/ Tracer/ Support Tracer/ Optg cur
Temp. Temp. Temp. Length Heat Loss model o/p ratio Valves Flanges qty cur Power
Valve Flange s Support
inch M w/m w/m Nos. M Nos. M Nos. M A A VA
153 P4045ZOR-93-08-1-J011-001 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 30.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 30.00 8.40 4.2 927
154 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
155 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 24.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 72.00 24.48 15.5 3413
156 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
157 P4045ZOR-93-08-1-J011-001 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
158 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
159 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
160 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
161 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
162 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 28.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 84.00 28.56 16.5 3638
163 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
164 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
165 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
166 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
167 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
168 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
169 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
170 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
171 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
172 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
173 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
174 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
175 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
176 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
177 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
178 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
179 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
180 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
181 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 25.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 25.00 7.00 3.5 773
182 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 25.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 75.00 25.50 14.8 3248
183 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 25.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 75.00 25.50 16.2 3555
184 P4045ZOR-93-08-1-J011-002 93 100-93P03-1158-31031K-ETR 4.0 65.0 80 90 28.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 28.00 7.84 3.9 866
185 P4045ZOR-93-08-1-J011-002 93 100-93P07-1159-31031K-ETR 4.0 65.0 80 90 30.0 25.2 KSX-15-2 30.9 1.0 0 1.52 0 0.28 0 0.61 30.00 8.40 4.2 927
186 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 27.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 82.50 28.05 16.2 3573
187 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 27.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 82.50 28.05 17.8 3911
188 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 23.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 69.00 23.46 13.6 2988
189 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 20.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 61.50 20.91 13.3 2916
190 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 22.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 67.50 22.95 13.3 2923
191 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 22.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 67.50 22.95 14.5 3200
192 P4045ZOR-93-08-1-J010-002 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 22.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 67.50 22.95 13.3 2923
193 P4045ZOR-93-08-1-J010-002 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 22.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 67.50 22.95 14.5 3200
194 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 22.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 67.50 22.95 13.3 2923
195 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 22.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 67.50 22.95 14.5 3200
196 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 22.5 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 67.50 22.95 13.3 2923
197 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 27.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 81.00 27.54 17.5 3840
198 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 24.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 72.00 24.48 14.2 3118
199 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 22.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 67.50 22.95 14.5 3200
200 P4045ZOR-93-08-1-J010-001 93 450-93P07-1120-31031K-ETR 18.0 80.0 80 23.0 86.9 KSX-20-2 43.3 3.0 0 8.22 0 0.51 0 1.29 69.00 23.46 13.6 2988
201 P4045ZOR-93-08-1-J010-001 93 750-93P07-1106-31031K-ETR 30.0 65.0 80 90 20.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 61.50 20.91 13.3 2916
202 P4045ZOR-93-08-1-J004 93 100-93P14-1036-31031K-ETR 4.0 80.0 80 90 9.0 31.5 KSX-20-2 43.3 1.0 1 1.52 3 0.28 0 0.61 11.36 3.86 2.2 492
203 P4045ZOR-93-08-1-J004 93 250-93P14-1035-31031K-ETR 3.0 80.0 80 90 2.0 26.1 KSX-20-2 43.3 1.0 1 1.06 3 0.24 0 0.56 3.78 1.29 0.7 164
204 P4045ZOR-93-08-1-J004 93 250-93P14-1035-31031K-ETR 10.0 80.0 80 90 5.0 55.2 KSX-20-2 43.3 2.0 0 4.26 4 0.34 0 0.93 11.36 3.86 2.2 492

Page. 4 of 5
Project Al-Zour Refinery Project Insulation Material: Mineral Wool Heat Tracing Standard: IEEE-515/ IEC 62086
Owner Kuwait National Petroleum Company (KNPC) Insulation Thk: As per below Heat Tracing Supply Voltage 220V AC Single Phase
Client HDEC-SAIPEM-SKEC Min.Ambient -3Deg. C. Maxm ckt loading for EHT 32A
RFQ Ref. No. Email Dated: 29.08.2016 Max.Ambient 50Deg. C. Circuit Breaker Type Type C
TME Ref. No. Maint. Temp As per below Design Margin for Hloss 10%
Qty.of Qty.of No of Qty.of
Maint. Max. Oper. Design Pipe Design Htg cable Htg Cab Trace No of No of Htg cab Start-up Optg
Sl No P&ID No. Unit Line No. Pipe size Tracer/ Tracer/ Support Tracer/ Optg cur
Temp. Temp. Temp. Length Heat Loss model o/p ratio Valves Flanges qty cur Power
Valve Flange s Support
inch M w/m w/m Nos. M Nos. M Nos. M A A VA
205 P4045ZOR-93-08-1-J004 93 50-93P14-1042-31031K-ETR 2.0 80.0 80 90 6.0 20.1 KSX-20-2 43.3 1.0 6 0.61 14 0.21 0 0.50 12.60 4.28 2.5 546
206 P4045ZOR-93-08-1-J004 93 50-93P14-1065-31031K-ETR 2.0 80.0 80 90 5.0 20.1 KSX-20-2 43.3 1.0 1 0.61 5 0.21 0 0.50 6.66 2.26 1.3 289
207 P4045ZOR-93-08-1-J004 93 50-93P14-1566-31031K-ETR 2.0 80.0 80 90 6.0 20.1 KSX-15-2 27.2 1.0 1 0.61 5 0.21 0 0.50 7.66 2.14 0.9 209
208 P4045ZOR-93-08-1-J004 93 750-93P14-1034-31031K-ETR 30.0 80.0 80 90 86.5 137.8 KSX-20-2 43.3 4.0 13 12.8 5 0.78 0 1.90 516.30 175.54 101.6 22356
209 P4045ZOR-93-08-1-J004 93 750-93P14-1034-31031K-ETR 3.0 80.0 80 90 2.0 26.1 KSX-20-2 43.3 1.0 2 1.06 12 0.24 0 0.56 7.00 2.38 1.4 304
210 P4045ZOR-93-08-1-J004 93 750-93P14-1034-31031K-ETR 10.0 80.0 80 90 3.0 55.2 KSX-20-2 43.3 2.0 1 4.26 1 0.34 0 0.93 10.60 3.60 2.1 459
211 P4045ZOR-93-08-1-J065 93 100-93P14-1269-31031K-ETR 4.0 65.0 80 90 5.0 25.2 KSX-15-2 30.9 1.0 1 1.52 3 0.28 0 0.61 7.36 2.06 1.0 228
212 P4045ZOR-93-08-1-J065 93 250-93P14-1270-31031K-ETR 3.0 65.0 80 90 2.0 20.9 KSX-20-2 47.4 1.0 1 1.06 3 0.24 0 0.56 3.78 1.29 0.8 180
213 P4045ZOR-93-08-1-J065 93 250-93P14-1270-31031K-ETR 10.0 65.0 80 90 4.0 44.1 KSX-20-2 47.4 1.0 0 4.26 4 0.34 0 0.93 5.36 1.82 1.2 255
214 P4045ZOR-93-08-1-J065 93 50-93P14-1268-31031K-ETR 2.0 65.0 80 90 5.0 16.1 KSX-15-2 30.9 1.0 0 0.61 1 0.21 0 0.50 5.21 1.46 0.7 161
215 P4045ZOR-93-08-1-J065 93 50-93P14-1401-31031K-ETR 2.0 65.0 80 85 5.0 16.1 KSX-15-2 30.9 1.0 6 0.61 12 0.21 0 0.50 11.18 3.13 1.6 346
216 P4045ZOR-93-08-1-J065 93 50-93P14-1674-31031K-ETR 2.0 65.0 80 90 4.0 16.1 KSX-15-2 30.9 1.0 3 0.61 5 0.21 0 0.50 6.88 1.93 1.0 213
217 P4045ZOR-93-08-1-J005-2 93 450-93P07-1119-31031K-ETR 16.0 data required 2.0 - - - - 7 7.01 12 0.48 0 1.19 - - - -
218 P4045ZOR-93-08-1-J005-2 93 450-93P07-1119-31031K-ETR 18.0 data required 20.0 - - - - 0 8.22 5 0.51 0 1.29 - - - -
219 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 24.0 65.0 80 90 2.0 89.9 KSX-20-2 47.4 2.0 1 10.9 4 0.61 0 1.60 17.34 5.90 3.7 822
220 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 12.0 65.0 80 90 4.0 51.0 KSX-20-2 47.4 2.0 10 5.02 2 0.39 0 1.02 58.98 20.05 12.7 2796
221 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 4.0 110.1 KSX-20-2 47.4 3.0 1 12.8 0 0.78 0 1.90 24.80 8.43 5.3 1176
222 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 3.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 9.00 3.06 1.9 427
223 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 12.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 36.00 12.24 7.8 1707
224 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 28.0 110.1 KSX-20-2 47.4 3.0 0 12.8 20 0.78 0 1.90 99.60 33.86 21.5 4722
225 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 10.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 31.50 10.71 6.8 1494
226 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 26.0 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 78.00 26.52 16.8 3698
227 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 18.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 55.50 18.87 12.0 2631
228 P4045ZOR-93-08-1-J005-2 93 750-93P07-1105-31031K-ETR 30.0 65.0 80 90 0.5 110.1 KSX-20-2 47.4 3.0 0 12.8 0 0.78 0 1.90 1.50 0.51 0.3 72

Grand Total 3899.50 222 475 0 8705.00 ##### ##### #######


Termination Margin 160.00
Grand Total With Termination Margin 8865.00

Page. 5 of 5
5.0 RELATED CATALOGUES
PRODUCT SPECIFICATIONS

KSX™ SELF-REGULATING HEATING CABLE

APPLICATION
High performance KSX self-regulating heating cables are 2
designed specifically for high heat loss freeze protection
applications or process temperature maintenance where
steam cleaning is not required.
The heat output of KSX cable varies in response to the 3
surrounding temperature by reducing its thermal output
with increasing temperature.
KSX cables are certified for use in ordinary (nonclassified) 4
areas and in potentially explosive atmospheres in
accordance with the ATEX Directive and the IEC Ex
Scheme.

RATINGS
Available watt densities......15, 31, 48, 64 W/m @ 10°C
Nominal supply voltages 1................................. 230 Vac
Max. maintenance or exposure temperature CONSTRUCTION
Continuous power-on....................................... 121°C 1 Nickel-plated copper bus wires (1.3 mm2)
Minimum installation temperature.........................-60°C
2 Semiconductive heating matrix and fluoropolymer
Minimum bend radius
dielectric insulation
@ -15°C........................................................... 10mm
@ -60°C.......................................................... 32 mm 3 Tinned copper braid
T-rating based on stabilized design 2.................T3 to T6 4 Fluoropolymer overjacket provides additional protection
to cable and braid where exposure to chemicals or
Notes
1. Cable may be energised at other voltages; contact Thermon for design
corrosives is expected.
assistance.
2. Thermon heating cables are approved for the listed T-ratings using the BASIC ACCESSORIES 3
stabilised design method. This enables the cable to operate in hazardous
areas without limiting thermostats. The T-rating may be determined using Thermon offers system accessories designed specifically
CompuTrace® Electric Heat Tracing Design Software or contact Thermon for for rapid, trouble-free installation of Thermon heating
design assistance.
cables.
3. Information on additional accessories to complete a heater circuit installation
and to comply with approval requirements can be found in the “Self-Regulating All cables require a connection kit to comply with approval
Cables Systems Accessories” product specification sheet (Form TEP0010U). requirements. Information on accessories to complete a
heater circuit installation can be found in the “Heating
Cable Systems Accessories” product specification sheet
(Form TEP0010U).

PRODUCT FEATURES
• Withstands continuous flammability testing according
to IEC 60332-1: 1993
• Can be installed at temperatures to -60°C

THERMON The Heat Tracing Specialists®


European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The Netherlands • Phone: +31 (0) 15-36 15 37
Corporate Headquarters:100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . . www.thermon.com

Form TEP0072U-0215 • © Thermon Manufacturing Co. • Printed in U.S.A. • Information subject to change.
PRODUCT SPECIFICATIONS

KSX™ SELF-REGULATING HEATING CABLE

POWER OUTPUT CURVES CIRCUIT BREAKER SIZING AND TYPE 1


The power outputs shown apply to overjacketed cable Maximum circuit lengths for various circuit breaker
installed on insulated metallic pipe at the service voltage amperages are shown below. Circuit breaker sizing and
stated below. earth-fault protection should be based on applicable local
codes. For information on design and performance on
Product Type Power Output at 10°C other voltages, contact Thermon. Earth-fault protection
230 Vac Nominal W/m of equipment should be provided for each branch circuit
KSX 5-2 15 supplying electric heating equipment.
KSX 10-2 31
Type B Circuit Breakers
KSX 15-2 48 230 Vac Service Voltage
KSX 20-2 64 Max. Circuit Length 3 vs. Breaker Size
Start-Up Meters
Product
Temperature 2
Type
°C 16A 25A 32A
10 114 167 167
KSX at 230 Vac
70 0 114 167 167
KSX 5-2
-20 112 167 167
60 -40 94 160 167
KSX 20-2 10 76 117 117
0 76 117 117
50 KSX 10-2
-20 73 117 117
-40 64 106 117
Watts per Meter

40 KSX 15-2
10 47 77 94
0 45 74 94
KSX 15-2
30 -20 41 67 89
-40 37 60 79
KSX 10-2
20 10 34 55 73
0 33 52 69
KSX 20-2
-20 30 48 62
10 KSX 5-2
-40 27 43 57

0 Type C Circuit Breakers



0 20 40 60 80 100 120 230 Vac Service Voltage
Pipe Temperature °C Start-Up
Max. Circuit Length 3 vs. Breaker Size
Product Meters
Temperature 2
Type
°C 16A 25A 32A
CERTIFICATIONS/APPROVALS
10 114 167 167
I 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67 0 114 167 167
T200°C to T85°C FM 07ATEX0027 KSX 5-2
-20 113 167 167
-40 95 163 167
International Electrotechnical Commission
IEC Certification Scheme for Explosive Atmospheres 10 76 117 117
FMG 06.0009
0 76 117 117
KSX 10-2
-20 75 117 117
Factory Mutual Research
Ordinary and Hazardous (Classified) Locations -40 66 109 117
10 47 77 94
KSX has additional hazardous area approvals including: 0 47 77 94
KSX 15-2
• DNV • Lloyd’s • CCE • ABS • FSTN • GOST -20 47 76 94
Contact Thermon for additional approvals and specific -40 42 69 91
information. 10 39 64 81
0 39 64 81
KSX 20-2
-20 36 59 78
-40 33 53 70

Notes
1. Maximum circuit lengths shown are based on an instantaneous trip current
characteristic per IEC 60898 at the referenced start-up temperature and a
10°C maintenance temperature. For maximum circuit lengths with other trip
current characteristics contact Thermon.
2. While a heat tracing system is generally designed to keep the contents of
a pipe at the desired maintain temperature, the cable may be energized at
lower temperatures. For design data with lower start-up temperatures than
represented above contact Thermon for design assistance.
3. The maximum circuit length is for one continuous length of cable, not the
sum of segments of cable. Refer to CompuTrace® design software or contact
Thermon for current loading of segments.
PRODUCT SPECIFICATIONS

TCM18™ CONTROL AND MONITORING MODULE

TCM18 CONTROL AND MONITORING MODULE TCM18 COMMUNICATION


The TCM18 is a multicircuit microprocessor-based temperature The TCM18 has two RS485 ports which communicate via
control and monitoring module developed specifically for heat Modbus ASCII or RTU protocol. One port can communicate to
tracing. This module provides control and monitoring capabilities TraceView Network Explorer or to compatible DCS system. The
via digital information display for a maximum of eighteen heat trace second port is provided for an auxiliary RS485 communication to
circuits. This module can be configured for either process sensing an optional Ethernet or wireless communication module.
control (with either one or two RTD inputs for
each circuit) and/or ambient sensing control (with
the option of one or two RTD inputs).
The TCM18 provides circuit information and
programming capability through the LCD digital
display and a dedicated touchpad on the front
of each module.

TCM18 RATINGS/SPECIFICATIONS TCM18 PRODUCT FEATURES


Control and monitoring capacity...................18 heat tracing circuits
• Module operates in a wide range of ambient conditions.
Nominal module supply voltage...................120-240 Vac 50/60Hz
• Each heat tracing circuit allows input from single or dual RTD
Input current..........................................................1.5 Amp max.
inputs.
Power consumption........................................................40 watts
• User friendly four line heated LCD display for circuit and alarm
Mimimum ambient temperature..........................................-40°C
information with input from a dedicated touchpad.
Maximum storage ambient..................................................70°C
• Conformally coated electronics for use in panels in indoor and
Data retention...........................................non-volatile EEPROM
outdoor locations.
Power clamp function................... programmable from 20% to 100%
• Low and high temperature alarm and additional programmable
Temperature input.............. up to 36 3-wire platinum 100 Ω RTDs
high temperature trip functions.
Temperature control range.....................................-129°C to 600°C
• Low and high heater current alarm and trip functions.
Control band..................programmable in increments of 1 degree
• High ground/earth leakage current alarm and trip functions
High operating current alarm and trips..............0.1 to 100 Amps
• Internal test functions for ground/earth leakage functionality.
Low operating current alarm..............................0.1 to 100 Amps
• Includes On-Off, On-Off with Soft Start, Proportional, and APC
Ground leakage alarm and trips.............................20 to 225 mA
(Ambient Proportional Control) modes.
(in 1 mA increments)
• Auxiliary 24 Vdc output for powering optional communication
Alarm relays
modules or other auxiliary devices.
Three sealed dry contacts, rated @ 0.4-amps resistive at 24 Vdc/Vac
• Equipment has been evaluated and found suitable for
Auxiliary output power.......................................... 24 Vdc at 0.5 Amps
Overvoltage Category II over the stated range of module
Self-test frequency.................programmable from 2 to 99 hours
supply voltage, in accordance with IEC-61010-1:2010.
Communication..........Modbus ASCII/RTU via Dual RS 485 ports
Communication rate........................................up to 57600 Baud
Certifications.......................................................................ATEX TCM18 DIMENSIONAL DATA
Pollution category......................................................................2 7.5"
(190 mm)

TCM18 CONNECTION PORTS 4.5


Auxiliary (114 mm)
Auxilary Input /
Power Out External Fuse Remote Acknowledge

19"
(482 mm)

Power Alarm PM6/RM6 Input RTB6 Input RS485 Ports


Input Output Cable Ports Cable Ports
Terminals

THERMON The Heat Tracing Specialists®


Corporate Headquarters:100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609
Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . . www.thermon.com

Form TEP0141-0314 • © Thermon Manufacturing Co. • Printed in U.S.A. • Information subject to change.
Product Specifications

PTD 100 Ex d RTD Probe

Application
The PTD-100 probe is specially designed to improve
the measuring accuracy between control input sensors
and controllers. The probe is designed to avoid the use
of zener barriers between sensor and controllers in
installations where the sensor is located in a hazardous
area and the controller in a safe area.
The probe can either be connected in an Ex e or Ex d
junction box and is suitable for use with Thermon’s
TC8165 or other electronic controllers.

Ratings
Number of wires.......................... 3 wire plus 1 earth tail
Resistance........................................... 100 Ohm @ 0°C
Accuracy..................................... Class B (DIN/IEC 751) features
Length of the probe 1................................................ 1 m Reliable measurements:
Sheath material of the probe...........316L stainless steel Complete earth shielded stainless steel outer jacket
Gland size............................................................... M20 prevents electromagnetic radiation to effect the
Length of lead wires.......................................... 150 mm measuring accuracy of control input.
Lead wire insulation material.................................PTFE
Rugged construction:
Temperature range, tip of probe............-200 to +550°C
Each PTD-100 has a stainless steel outer jacket so
Maximum temperature at gland............................ 100°C
that the probe cannot be damaged by sharp edges, for
Minimum bending radius 2................................... 30 mm
instance the cladding of thermal insulation.
Notes
1. Longer probe length of 3 meters available. Contact Thermon for additional Approved for hazardous areas:
information. The PTD-100 is suitable for use in hazardous areas
2. The measuring tip (length 15 mm) should not be bent. without the need for zener barriers. The probe can either
3. Conductor to be solid or stranded. be connected in an Ex e or Ex d junction box.
4. Maximum length for signal cables installed in ambient temperatures up to 40
°C. Max. loop resistance for controller input is 30 Ohm, incl. 1 Ohm allowance
for contact resistance at terminal. Wiring information
5. Refer to the TC-816 Product Specification, form number TEP0087U for more To obtain the maximum distance between the PTD-100
information.
and the controller for different conductor sizes of the
signal cable use the table below. Thermon recommends
Certifications/Approvals to use 3 wire cables with a braided earth shield.
II 2 G Ex d IIC DEMKO 08 ATEX 0729347U Use Thermon’s JB-K-0-PTD or Terminator ZP-PTD100-
WP EEx e wall mounted junction box to complete
The PTD-100 has additional hazardous area approvals including: terminations between the PTD-100 and control wiring.
• GGTN • Kazakhstan The junction boxes include one M25 power gland, two
Contact Thermon for additional approvals and specific information. M20 blind plugs, one M20 entry for the PTD-100 and 6x4
mm2 terminals. For pipe mounting use stainless steel
mounting bracket XP-1 140 x 140 mm.

Maximum signal cable length 4


Conductor 3 cross section
between PTD-100 and controller

1.5 mm2 1,0 km


2.5 mm2 1,7 km
4.0 mm2 2,7 km

THERMON The Heat Tracing Specialists®


European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The Netherlands • Phone: +31 (0) 15-36 15 37
Corporate Headquarters:100 Thermon Dr • PO Box 609 San Marcos, • TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . . www.thermon.com

Form TEP0093U-0113 • © Thermon Manufacturing Co. • Printed in U.S.A. • Information subject to change.
Product Specifications

SYSTEM ACCESSORIES
HEAT TRACING CABLES

Application Freeze Protection and Process Temperature Maintenance


The following information relates to power connection kits, end termination kits and common installation accessories used
with Thermon BSX™, RSX™, KSX™, HTSX™, VSX™, FP and HPT heating cables.

Pipe Mount Wall Mount Pipe Mount Wall Mount


Terminator ZP... is designed to fabricate power Terminator ZL... is designed to provide visual Terminator Beacon... end-of-circuit light kits
connections, in-line/T-splice connections or indication of an energized heating circuit. The kit are designed specifically for rapid, trouble-free
for making end terminations. The Terminator may be utilized as a power connection or an end installation of Thermon self-regulating and power-
ZP-XP is suitable for use in hazardous areas termination kit. Electrical connections are made limiting, parallel resistance polymer insulated
(Ex e T6/T4), harsh industrial environments and in terminal blocks utilizing nickel-plated copper heating cables. The Terminator Beacon utilizes
has a IP66 rating. The upfront positioning of terminals to ensure corrosion-free electrical a high intensity green LED assembly for superior
the terminal block permits easy access during integrity. day or night visibility.
assembly and for future routine maintenance.
The Terminator ZL kit includes; IP66 rated junction Product Reference Legend:
The Terminator ZP kit includes; Pipe-mounted box, yellow LED indicating lamp, four 6-mm2 line/ ZE-B..... BSX, RSX, HTSX, KSX, VSX, FP, HPT
expediter with suitable grommet, Junction box load terminals, two 6-mm2 earth terminal, pipe-
with two M25 entries and one M25-B-Exe blind mounted fitting, heater cable grommet.
plug, Four 6-mm2 line/load terminals, Two 6-mm2
Product Reference Legend:
earth terminals, Terminals rated to 22 amps (T6
ZL-XP and ZL-WP.......RSX, VSX, BSX, HTSX,
85°C) or 46 amps (T4 135°C), Maximum voltage
KSX, FP, HPT
rating of 750 Vac. Wallmount version is available.
Product Reference Legend:
ZP-XP and ZP-WP....... RSX, VSX, BSX, HTSX,
KSX, FP, HPT
ZP-R-XP and ZP-R-WP.............................TESH

Terminator ZS/ZE...designed to fabricate PETK...circuit fabrication kits are required for SCTK...splice connection termination kits are
accessible outside-the-insulation splices or use with all Thermon Parallel Heating Cables required when preparing outside-the-insulation
end terminations of Thermon Heating Cables. Connection Kits. Kits for termination of SX cables splices with all Thermon Parallel Heating
Electrical connections are made using wire include a power connection boot, end cap, RTV Cables Connection Kits. Kits for terminations
fasteners (for applications requiring terminations adhesive and a caution label. Kits for termination of SX cables include 2 splice connection boots,
to be made with terminal block connections, the of HPT and FP cables also include tape strip and assorted wire nuts and RTV adhesive. Kits for
Terminator ZP kit may be used). a distinct grommet. termination of HPT and FP cables also include a
distinct grommet.
Product Reference Legend: Product Reference Legend:
ZS/ZE-XP........... BSX, RSX, HTSX, KSX, VSX, PETK-1.....................................BSX, RSX, VSX Product Reference Legend:
FP, HPT PETK-2............................................ KSX, HTSX SCTK-1.....................................BSX, RSX, VSX
PETK-3 .................................................FP, HPT SCTK-2............................................ KSX, HTSX
PETK-3-ECM .......................................FP, HPT SCTK-3..................................................FP, HPT
PETK-3-ZT ...........................................FP, HPT
PETK-4 .........................................HPT > 240°C

THERMON The Heat Tracing Specialists®


European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The Netherlands • Phone: +31 (0) 15-36 15 37
Corporate Headquarters:100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . . www.thermon.com

Form TEP0010U-0113 • © Thermon Manufacturing Co. • Printed in U.S.A. • Information subject to change.
Product Specifications

SYSTEM ACCESSORIES
HEAT TRACING CABLES

Cable End Termination Kits, Attachment Tapes and Miscellaneous Items

CS-L-*-Ex…. Circuit switch with lamp to be used as B-4, B-10, B-21...stainless steel attachment bands IEK-SX...Insulation entry kit for use in (non)
an in-line isolation switch for single phase, phase- for securing Thermon nonmetallic kits to pipes.
hazardous locations that protects and seals the
phase and 3-phase heat tracing circuits. Available B-4...for pipes up to 100 mm diameter
in 16 A, 25 A and 40 A versions. B-10...for pipes up to 250 mm diameter heating cable while penetrating insulation cladding.
B-21...for pipes up to 530 mm diameter BSX........................................................... IEK-SXM
ABA-25...for pipes up to 25 mm diameter
ABA-40... for pipes up to 40 mm diameter KSX, HTSX, FP, HPT................................... IEK-SXS
RSX, VSX.................................................... IEK-SXL
Terminator-LN-Tool...for tightening the locknuts of TESH...........................................................IEK-TES
the Terminator kits. Tool is recommended to ensure
enclosure is properly secured to the pipe-mounted
expediter.

M25-SX.-Ex....Ex e approved nonmetallic gland for M25-PWR-Exe, M25-B-Exe...Ex e approved FT-1L, FT-1H...fixing tape for attaching heating cable
use with M25 junction boxes. nonmetallic gland and plug for use with Terminator. to piping every 300 mm or as required by code or
M25-SX.-IND....nonmetallic gland for use with M25-PWR-Exe...power gland is suitable for securing specification.
JB-K-0-M25 junction boxes power cables with diameters between 8 and 17 mm. AL-20H, AL-30H...aluminium tapes for continu-
M25-B-Exe...blind plug. ous (longitudinal) covering cable to piping and/
BSX.....................................................M25-SXM-...
or equipment.
KSX, HTSX, FP, HPT.............................M25-SXS-... M25-PWR-IND, M25-B-IND, M25-LN-IND...non-
RSX, VSX.............................................. M25-SXL-... metallic gland and plug for use in threaded openings Item Max. Temp. Min. Temp. Size
Number (Exposure) (Installation) (mm x m)
TESH.................................................. M20-PWR-... of junction boxes.
FT-1L 93 °C 5 °C 12 x 33
M25-PWR-IND...power gland is suitable for securing FT-1H 260 °C -40 °C 12 x 33
power cables with diameters between 11 and 18 mm. AL-20H 150 °C -5 °C 50 x 55
M25-B-IND...blind plug and sealing washer. AL-30H 150 °C -5 °C 76 x 55

M25-LN-IND...locknut for securing M25 glands in


JB-K-1 and JB-K-2 boxes.

SK-SX-OJ...Ex e approved under-the-insulation CL...vinyl-based peel-and-stick caution labels are XP-1-...predrilled stainless steel (type 304) mounting
repair and splice kit for overjacketed SX cables. Kit intended for direct exposure to industrial environ- bracket designed for mounting Thermon junction
includes stainless steel shells, screws, grommets, ments. Electrically heated pipelines and vessels boxes and thermostats directly to the pipework.
RTV adhesive/sealant, insulation tape and the neces- should be clearly identified at frequent intervals The bracket is easily secured to the pipe using B-4,
sary wire pins/lugs. along the pipeline or vessel. Caution labels should B-10 or B-21 attachment bands. The XP-1 utilises
be placed at 3 to 6-m intervals or as required by a 110-mm standoff.
code or specification. Additional languages or other XP-1-140X140.................... JB-K-0, JB-K-1, JB-K-2
texts are available; contact Thermon. XP-1-WP......................................... Terminator WP
6.0 INSTALLATION PROCEDURES
Electric Heat Tracing
INSTALLATION PROCEDURES
Electric Heat Tracing
Complete Electric Heat Tracing System . . .

Types of Heating Cables1 . . .


Self-Regulating Heating Cables:
BSX™ (refer to Form TEP0067U)
1725 II 2 G & D Ex e II T5 or T6 DEMKO 02ATEX0132424, UL 06.0013 Ex e II T5 or T6

RSX™ 15 (refer to Form TEP0048U)2


1725 II 2 G Ex e II T4 to T6 KEMA 07ATEX0179, KEMA 07.0052 Ex e II T4 to T6

HTSX™ (refer to Form TEP0074U)


1725 II 2 G Ex eb IIC T2 or T3, II 2 D Ex tb IIIC T300°C or T200°C FM 12ATEX0014
FMG 12.0003 Ex eb IIC T2 or T3, Ex tb IIIC T300°C or T200°C

KSX™ (refer to Form TEP0072U)


1725 II 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67 T200°C to T85°C FM 07ATEX0027
FMG 06.0009 Ex e II T3 to T6,
Ex tD A21 IP66/IP67 T200°C to T85°C

VSX™ (refer to Form TEP0008U)


1725 II 2 G & D Ex e II T3 DEMKO 02ATEX0152667
UL 05.0008x Ex e II T3

Power-Limiting Heating Cable:


HPT™ (refer to Form TEP0011U)
1725 II 2 G Ex e II T2 to T6, II 2 D Ex tD A21 T300°C to T85°C FM 07ATEX0028
FMG 06.0006 Ex e II T2 to T6

Parallel Constant Watt Heating Cable:


FP (refer to Form TEP0016U)3
1725 II 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67 T200°C to T85°C FM 07ATEX0016
FMG 06.0008 Ex e II T3 to T6,
Ex tD A21 IP66/IP67 T200°C to T85°C

Series Constant Watt Heating Cables:


HTEK™ (refer to Form TEP0022U)
1725 II 2 G Ex eb IIC T260°C (T2) to T6, II 2 D Ex tb IIIC T260°C to T85°C FM 11ATEX0050
CCVE 11.0002 Ex eb IIC T260°C (T2) to T6, Ex tb IIIC T260°C to T85°C

TEK™ (refer to Form TEP0021U)


1725 II 2 G Ex eb IIC T260°C (T2) to T6, II 2 D Ex tb IIIC T260°C to T85°C FM 11ATEX0050
CCVE 11.0002 Ex eb IIC T260°C (T2) to T6, Ex tb IIIC T260°C to T85°C

TESH™ (refer to Form TEP0070U)


1725 II 2 G Ex e IIC T2 To T6 Gb, II 2 D Ex tb IIIC IP6X T260°C to T80°C Db ISSeP 10ATEX015X

Notes . . .
1. Refer to the heating cable product specification sheets for temperature ratings as limited by the manufacturer.
2. For foundation heating with RSX, refer to Form TEP0059.
3. For foundation heating with FP, refer to Form TEP0079.

1
Electric Heat Tracing
The following installation procedures are for the installation Complete Electric Heat Tracing System . . .
of a Thermon electric heat tracing system1. The installation
A complete electric heat tracing system may typically include
must comply with Thermon requirements and be installed
the following components2:
in accordance wit the regulations as per standard EN-IEC
60079-14 and EN-IEC 60079-30-2 for hazardous areas 1. Electric heat tracing cable1, 5 (self-regulating, power-
(where applicable), and any other applicable national and limiting, parallel constant watt or series constant watt).
local electric codes. 2. Power connection kit.
3. RTD sensor or control thermostat3.
Individuals installing these products are responsible for 4. In-line/T-splice kit (permits two or three cables to be
complying with all applicable safety and health guidelines. spliced together).
Proper personal protective equipment, or PPE, should be 5. Cable end termination.
utilized during installation. Contact Thermon if you have
5a. End of circuit light kit.
any additional questions.
6. Attachment tape (use on 30cm intervals or as required by
Applications . . . code or specification).
1. Electric heat tracing cables are used for freeze protection 7. “Electric Heat Tracing” label (peel-and-stick label attaches
or temperature maintenance of piping, tanks and to insulation vapor barrier on 3m intervals or as required
by code or specification).
instrumentation. This set of instructions covers typical
piping applications. For installation details on tanks and 8. Thermal insulation4 and vapor barrier (by others).
instrumentation, refer to the Installation Guides on our The absence of any of these items can cause a system to
website www.thermon.com. malfunction or represent a safety hazard.
2. Heat tracing cables may be installed in ordinary Notes . . .
1. Refer to Page 1 for cable types and approval.
(nonclassified) and hazardous (classified) locations
2. Illustration depicts a typical self-regulating heating circuit.
depending on the specific cable options and approvals1. 3. Temperature control is recommended for all freeze protection and temperature
maintenance heat tracing applications.

Site Practice . . . 4. All heat-traced lines must be thermally insulated.


5. Refer to Thermon form number PN50273U for installation instructions for MI
1. Provide protective clothing, and other protective heating cable.
equipment needed to isolate employees from potential
Illustration A: Typical Heat Tracing Installation
arc flash and shock hazards identified in the analysis.
2. Provide training to employees for understanding the 5a
4
purpose/function of the electrical heat tracing and the
electrical power supply/control equipment. In addition,
how to recognize and avoid the hazards associated with 5
operation and maintenance.
3. Apply safe work practices including the following:
• Identify the circuit or equipment to be de-energized and
all possible sources of electrical energy supplies to the
specfic circuit or equipment. 8

• Disconnect both legs of the power supply cable at the 6


circuit breakers, disconnect switches, and any other
applicable points. 7

• Apply lockout/tagout devices according to established


procedures.
• Visually verify that the circuit disconnect devices are
open prior to connecting power cable to heat tracers.
1
• Test for absence of voltage with an approved voltmeter 3
(where the voltmeter is tested on a known circuit voltage
prior to and immediately following application).
• For protection against accidental energizing of supply
conductors, apply temporary jumpers rated for the
available fault duty between each supply conductor and 2
earth/ground.

2
Electric Heat Tracing
Upon Receiving Cable . . . Before Installing Cable . . .
1. Upon receiving heating cable, check to make sure the 1. Be sure all piping and equipment to be traced is
proper type and output have been received. All flexible completely installed and pressure tested.
cables have the catalog number, voltage rating and watt 2. Surface areas where heat tracing is to be installed must be
output printed on the jacket. reasonably clean. Remove dirt, rust and scale with a wire
2. Visually inspect brush and oil and grease films with a suitable solvent.
cable for any
damage incurred
Initial Installation . . .
during shipment. 1. Locate the cable on the lower quadrant of the pipe at the
The heating cable should be 4 or 8 o’clock position. If accessibility is a problem the
tested to ensure electrical integrity cable may be installed at the 10 or 2 o’clock position.
with at least a 500 Vdc megger Temperature sensor should be located at least 90° from
between the heating cable bus wires and the heating all heating cables. Refer to Illustration B for Heating Cable
cable metallic braid. IEEE 515 and EN-IEC 60079-30 vs. Sensor Location.
recommend that the test voltage for polymer insulated
heating cables be 2500 Vdc. Minimum resistance should 2. Begin temporary installation at the proposed end-of-
be 20 megohms. Connect the positive lead of the megger circuit location and lay out heating circuit on the pipe,
to the cable bus wires and the negative lead to the allowing extra cable for the power connection and for
metallic braid. any splice locations1. Refer to Illustration C for temporary
(Record 1 on Insulation Resistance Test Page 9 and 10) installation.

3. Store in dry location. 3. Make heating cable allowances for valves, flanges, elbows
and supports as per the applicable drawings and table on
pages 5 and 6 of these installation procedures.

Illustration B: Heating Cable vs. Sensor Location Temperature Sensor


(Typical)

45º Pipe Wall

90º

45º
45º
90º 45º 45º 45º 45º
Heating Cable
(Typical)
Single Cable Installation Dual Cable Installation Triple Cable Installation

Proposed End-of-Circuit
Illustration C: Temporary Installation Location

Pipe Support

Notes . . .
1. Termination kits to fabricate a heat tracing circuit are not
addressed in detail in these installation procedures. Refer
Cable Allowance for
to installation instructions included with cable termination
In-Line Heat Sinks kits or contact Thermon for specific instructions to
Proposed Power fabricate heating cable.
Connection Location

3
Electric Heat Tracing
Installation on Elbows, Supports and Flanges . . .
1. Install heating cable in accordance with Illustrations D, 4. Flanges: Allow cable to be looped around pipe on each
E and F below. Secure heating cable to piping using side of and adjacent to the flange. Heating cable must
attachment tape. maintain contact with flange when bending around pipe
flanges to compensate for additional heat loss.
2. Elbows: Locate the cable on the outside radius of an
elbow to provide sufficient heat to compensate for the 5. Refer to the product specifications sheet for minimum
added piping material. Secure the cable to the pipe on bend radius for the specific cable type. Do not exceed
each side of the elbow with attachment tape. bend radius when completing installation.
3. Pipe Supports: Insulated pipe supports require no
additional heating cable. For uninsulated supports, allow
two times the length of the pipe support plus an additional
40 cm of heating cable.

Illustration D: Pipe Elbow Illustration E: Pipe Support1


Attachment Tape
(Typical)

Heating Cable Heating Cable

Attachment Tape
(Typical)

8 cm

Illustration F: Pipe Flange Support


8 cm Length

Attachment Tape
(Typical)

Heating Cable

Circuit Layout on Support

Note . . .
1. Only applicable for pipe ≥ 50mm.

30 cm
Note: Flange allowance will vary based on method of
insulating flange and adjacent piping.

4
Electric Heat Tracing
Installation on Valves and Pumps . . . Table 1: Valve and Pump Allowances1
Pipe Valve Allowance (M) Pump Allowance (M) Flange
1. Install heating cable in accordance with Illustrations G and
Size Screwed Allowance
H below. Secure heating cable to piping using attachment (mm) or Welded Flanged Butterfly Screwed Flanged (M)
tape. 12 0.20 0.30 0.00 0.30 0.61 0.38
2. Additional cable is required to provide extra heat at 20 0.20 0.46 0.00 0.46 0.91 0.46
25 0.30 0.61 0.30 0.61 1.22 0.46
valves, pumps and miscellaneous equipment to offset the
32 0.50 0.61 0.30 0.91 1.37 0.61
increased heat loss associated with these items. Refer to
40 0.50 0.76 0.46 0.91 1.52 0.61
Table 1 for estimated cable requirements for installation
50 0.60 0.76 0.61 1.22 1.68 0.69
on typical valves and pumps. Allowances shown in
80 0.80 1.07 0.76 1.52 2.13 0.69
Table 1 are for 150 pound valves. More cable is required 100 1.20 1.52 0.91 2.44 3.05 0.84
for higher rated valves. Refer to heat trace isometric 150 2.10 2.44 1.07 4.27 4.88 0.99
drawing for project specific allowances. 200 2.90 3.35 1.22 5.79 6.71 1.14
3. Install heating cable on valves and pumps utilizing a 250 3.80 4.27 1.22 7.62 8.53 1.30
300 4.60 5.03 1.52 9.14 10.06 1.52
looping technique (this allows the valve or pump to be
350 5.50 5.94 1.68 10.97 11.89 1.68
removed if required). Crossing constant watt heating
400 6.60 7.01 1.83 13.11 14.02 1.83
cable over itself should be avoided.
450 7.80 8.23 1.98 15.54 16.46 1.98
4. Refer to the product specifications sheet for minimum 500 8.70 9.14 2.13 17.37 18.29 2.21
bend radius for the specific cable type. Do not exceed 550 10.40 10.97 2.44 20.73 21.95 2.51
bend radius when completing installation. 600 12.20 12.80 3.05 24.38 25.60 3.05
Note . . .
1. The valve allowance given is the total amount of additional cable to be installed on
the valve. If multiple tracers are used, total valve allowance may be divided among
the individual tracers. The total valve allowance may be alternated among tracers for
multiple valves in a heat trace circuit. Allowances are for 150 pound valves. More
cable is required for higher rated valves. Refer to heat trace isometric drawing for
project specific allowances.

Illustration G: Typical Valve Detail Illustration H: Typical Pump Detail

Attachment Tape
(Typical)

Heating Cable

Heating Cable

Attachment Tape Heating Cable Serpentined on Pump


(Typical)

Heating Cable Serpentined on Valve

Circuit Layout on Valve Circuit Layout on Pump

5
Electric Heat Tracing
Completing the Installation . . .
1. Begin final cable attachment by securing the end-of-circuit 3. Complete splice connections (if required) in accordance with
termination kit and working back toward the power supply. the installation instructions provided with the splice kit.
Refer to Illustration I. 4. Before making power connections, The heating cable
• Flexible heating cables are to be installed using attachment should be tested to ensure electrical integrity with at
tape. Circumferential bands of tape should be installed at least a 500 Vdc megger between the heating cable
30 cm intervals to keep the cable in good contact with bus wires and the heating cable metallic braid. IEEE
the pipe. Refer to Table 2 below to calculate the number 515 and EN-IEC 60079-30 recommend that the test
of rolls of attachment tape required based on the pipe voltage for polymer insulated heating cables be 2500
diameter1. Vdc. Minimum resistance should be 20 megohms.
• Avoid crossing series constant watt heating cables. (Record 2 on Insulation Resistance Test Page 9 and 10)
• If applicable, refer to installation details provided with 5. Install power connection kit in accordance to the detailed
the project drawings or contact Thermon for additional installation instructions provided with the kit.
information regarding installation. 6. Secure temperature sensor (if required) to pipe utilizing
2. In addition to the circumferential tape requirements, a attachment tape.
continuous covering of aluminum foil tape may be required Notes . . .
when: 1. Table 2 assumes circumferential bands every 30 cm along the length of the process
piping.
• Spray or foam2 thermal insulation is applied.
2. Verify exposure temperature of heating cable versus curing temperature of
• Heat tracing nonmetallic piping. insulation.
• Design requirements dictate the use of aluminum tape.

Illustration I: Final Cable Attachment

Proposed End of Circuit

Attachment Tape

Proposed Power Supply

Table 2: Attachment Tape (Value Represents Approximate Linear Pipe Length Allowance Per Roll)

Pipe Size
12-25 32 40 50 80 100 150 200 250 300 350 400 450 500 600 750
mm
Length of Pipe/
Roll of Tape 109.7 79.2 67.0 54.9 45.7 36.6 27.4 21.3 18.2 15.2 12.2 10.7 9.1 7.6 6.0 4.6
m

6
Electric Heat Tracing
Circuit Protection Requirements . . . Final Inspection and Documentation . . .
1. Over-current protection (typically circuit breakers) is 1. After the installation of the thermal insulation and
required for each branch circuit. This protection must weather barrier but BEFORE ENERGIZING THE HEATING
isolate all power conductors from the supply. CIRCUIT, the insulation resistance test should be
2. For typical installations (with TT and TN grounding repeated. This should call attention to any damage to
systems), a means of protection against earth faults is the heating cable that may have occurred during the
required that includes a residual-current protective device insulation installation.
for each branch circuit. For fixed-level earth/ground- (Record 3 on Insulation Resistance Test Page 9 and 10.)
fault circuit interrupters, a minimum 30 mA trip level is For Series Heating Cables, measure the electric loop resistance
recommended. The preferred trip level for adjustable and record measured Ohms (Record 3 on Page 10.)
devices is 30 mA above any inherent capacitive leakage 2. It is recommended that the circuit be temporarily
characteristic of the heater as specified by the heat energized so that the volts, amps, pipe temperature and
tracing supplier. Where conditions of maintenance and ambient temperature may be recorded. Take the values
supervision ensure that only qualified persons will service after 5 minutes of energizing. This information may be of
the installed systems, and continued circuit operation value for future reference and should be maintained for
is necessary for the safe operation of the equipment the historical operating data log.
or processes, earth-fault detection without interruption (Record 4 on Insulation Resistance Test Page 9 and 10)
is acceptable if alarmed in a manner to assure an 3. Stabilized design can be used for self-regulating, power-
acknowledged response. limiting and constant watt heating cables without a limiting
3. For IT grounding systems, a means of protection device to determine the T-class through the use of the
against earth faults is required that includes an electrical Thermon CompuTrace software or Thermon Engineering.
insulation monitoring device that shall disconnect the 4. Series heating cable output and T-rating are dependent
supply whenever the electrical resistance is not greater upon supply voltage, cable resistance, temperature
than 50 ohms/volt of rated voltage. conditions as well as additional variables through the
Thermal Insulation . . . use of the Thermon CompuTrace software or Thermon
Engineering.
1. Before installing thermal insulation, insulation resistance
5. The maximum temperatures provided by Thermon’s
test should be conducted. The cable should be tested
CompuTrace software and by Thermon engineering are
with a test voltage of at least 500 Vdc. However,
calculated to the methods and requirements of
for polymer insulated heating cables, 2500 Vdc is
EN-IEC 62086-2 and EN-IEC 60079-30.
recommended. The minimum acceptable level should not
be less than 20 megohms. 6. If stabilized design is used, the end user must record the
system parameters and the area T-class, and keep these
2. The need for properly installed and well-maintained
records for the time the heating cable is in operation.
thermal insulation cannot be overemphasized. Without
insulation, heat losses are generally too high to be offset 7. Inspect system on a regular basis at least once per year.
by a conventional heat tracing system. Record all information after conducting test. If the system
fails any test, refer to Thermon’s Maintenance and Trouble
3. In addition to piping and in-line equipment such as pumps
Shooting Guide for assistance. De-energize circuits affected
and valves, all heat sinks must be properly insulated. This
and make the necessary repairs immediately.
includes pipe supports, hangers, flanges and, in most
cases, valve bonnets. 8. Verify the setting of the maximum control device, if
4. Regardless of the type or thickness of insulation used, a provided to limit the T-rating for the circuit design, to
protective barrier should be installed. This protects the ensure it limits the maximum surface temperature to be in
insulation from moisture intrusion, physical damage and compliance with clause 4.4.3 of EN-IEC 60079-30-1.
helps ensure the proper performance of the heat tracing Maintenance and Repair . . .
system. Seal around all penetrations through the thermal
insulation. 1. Refer to form TEP0066-Electric Heat Tracing Maintenance
5. Apply “Electric Heat Tracing Caution” labels to the and Trouble Shooting Guide.
insulation vapor barrier on 3m intervals or as required
by code or specification. The labels are supplied with
Thermon connection kits.

7
Cable Testing Report
1. Refer to these Installation Procedures for general installation procedures, requirements and guidelines.
2. Upon receiving heating cable, check the cable to make sure the proper type and output have been received. All flexible
cables have the catalog number, voltage rating and watt output printed on the outer jacket.
3. Visually inspect cable for any damage incurred during shipment. The heating cable should be tested to ensure electrical
integrity with at least a 500 Vdc megger between the heating cable bus wires and the heating cable metallic braid.
IEEE 515 and EN-IEC 60079-30 recommend that the test voltage for polymer insulated heating cables be 2500 Vdc.
Minimum resistance should be 20 megohms.
(Record 1 on Insulation Resistance Test Page 9 and 10)
A. Connect the positive lead of the megger to the cable bus
wires.
B. Connect the negative lead of the megger to the metallic braid.
C. Energize the megger and record the reading. Readings
between 20 megohms and infinity are acceptable. Readings
below 20 megohms may mean the electrical insulation has
been damaged. Recheck the heating cable for physical damage between the braid and the heating element; small cuts or
scuffmarks on the outer jacket will not affect the megger reading unless there was actual penetration through the braid
and dielectric insulation jacket.
4. Once the installation is complete, but prior to installation of thermal insulation, recheck the heating cable with at least a
500 Vdc megger between the heating cable bus wires and the heating cable metallic braid. IEEE 515 and EN-IEC 60079-30
recommend that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20
megohms. (Record 2 on Insulation Resistance Test Page 9 and 10)
5. After the thermal insulation is installed, the insulation resistance test should be repeated. Minimum resistance should be 5
megohms. (Record 3 on Insulation Resistance Test Page 9 and 10.) For Series Heating Cables, measure the electric loop
resistance and record measured Ohms (Record 3, Page 10.)
6. After the thermal insulation is installed and power supply is completed, record the panel and circuit breaker information.
Ensure all junction boxes, temperature controllers, cable glands, etc. are properly secured. Set the temperature controller
(if applicable) to the manual setting and apply rated voltage to the heat tracing circuit(s) for 5 minutes. Record the ambient
temperature, measure and record the circuit(s) voltage and current.
(Record 4 on Insulation Resistance Test Page 9 and 10)

NOTE: To ensure the heating cable warranty is maintained through installation, the testing outlined
on this sheet must be completed on the installed heating cables.

8
Checklist for Self-Regulating and Power-Limiting Heat Tracing
General Information
Installation
Project Number: Contractor:
Thermon Reference
Unit Number: Number:
Customer Ref. Number: Inspector:

Record 1: Prior to Installation

Cable Type: Reel Number:


Insulation Resistance:
Reel Length (M): (M Ohms)*
Tested By/Date: Witnessed By/Date:

Record 2: After Cable Installation

Line Number: Thermostat Number:

Equipment Number: Junction Box Number:


Unused Entries
Circuit/Heater Number: Plugged Off:
Circuit Switch Number: Heater Length (M):
Metal Sheath Connected Insulation Resistance:
to Earth/Ground: (M Ohms)*
Tested By/Date: Witnessed By/Date:

Record 3: After Thermal Insulation is Installed


Insulation Resistance:
Insulation Watertight: (M Ohms)*
Tested By/Date: Witnessed By/Date:

Record 4: Final Commissioning

Panel Number: Ambient Temp. (°C):

Breaker Number: Pipe Temp. (°C):


Recorded Amps
Volts: (after 5 min.):
Tested By/Date: Witnessed By/Date:

*NOTE: Minimum acceptable insulation resistance should be 20 megohms for Records 1 and 2 and
5 Megohms for Record 3.

9
Checklist for Installation of Series Heating Cables
General Information

Project Number: Electrical Contractor:

Unit Number: Reference Number:

Customer Ref. Number: Inspector:

Record 1: Prior to Installation

Cable Type: Insulation Resistance (M Ohms):


1 2
Single Phase L-Earth
Reel Length (M):
L1-Earth
1 2
3 Phase L2-Earth
Reel Number:
L3-Earth
Tested By/Date: Witnessed By/Date:

Record 2: After Cable Installation

Line Number: Junction Box Number:


Unused Entries
Equipment Number: Plugged Off:
1 2
Circuit/Heater Number: Heater Length (M):

Circuit Switch Number: Insulation Resistance (M Ohms):


Braid Connected Single Phase L-Earth
to Earth/Ground: L1-Earth
3 Phase L2-Earth
Thermostat Number:
L3-Earth
Tested By/Date: Witnessed By/Date:

Record 3: After Thermal Insulation is Installed Insulation Watertight:

Insulation Resistance (M Ohms): Electrical Loop Resistance (Ohms):


Single Phase L-Earth Single Phase L-L
L1-Earth L1-L2
3 Phase L2-Earth 3 Phase L2-L3
L3-Earth L3-L1
Tested By/Date: Witnessed By/Date:

Record 4: Final Commissioning

Panel Number: Ambient Temp. (°C):

Breaker Number: Pipe Temp. (°C):


Recorded Amps
Volts: (after 5 min.):
Tested By/Date: Witnessed By/Date:

*NOTE: Minimum acceptable insulation resistance should be 20 megohms for Records 1 and 2 and
5 Megohms for Record 3.
10
For additional product information on Thermon heating cables, refer to the individual product specifications.
BSX™ (refer to Form TEP0067U)
RSX™ 15 (refer to Form TEP0048U)
HTSX™ (refer to Form TEP0074U)
KSX™ (refer to Form TEP0072U)
VSX™ (refer to Form TEP0008U)
HPT™ (refer to Form TEP0011U)
FP (refer to Form TEP0016U)
HTEK™ (refer to Form TEP0022U)
TEK™ (refer to Form TEP0021U)
TESH™ (refer to Form TEP0070U)

THERMON . . . The Heat Tracing Specialists®


www.thermon.com

European Headquarters Corporate Headquarters


Boezemweg 25 • PO Box 205 100 Thermon Dr. • PO Box 609 For the Thermon office nearest you
2640 AE Pijnacker • The Netherlands San Marcos, TX 78667-0609 • USA visit us at . . .
Phone: +31 (0) 15-36 15 370 Phone: +1 512-396-5801 www.thermon.com
Specifications and information subject to change without notice. PN50207U-0412