You are on page 1of 4

Electrical, insulation and

thermal measurements
for motors and drives
Insulation multimeters and thermal imagers: Application Note
Two testers that go great together.

Most facilities need to get Handheld thermal imag- An insulation multimeter


maximum life out of their ers such as the Fluke Ti25 like the Fluke 1587 can
motors, because they are can collect heat signatures perform most of the other
expensive to replace in from a range of motors, tests you need to trouble-
terms of both money and from 1000 hp down to 5. shoot and maintain motors.
labor. Electrical, insulation A thermal imager is good When a motor is having
resistance and thermal for spot checks, to see problems, check the sup-
measurement are three if motors and associated ply voltage and then use
tests that can troubleshoot panels and controls are insulation testing to check
motors, drives, and associ- operating too hot, and for the starter and control con-
ated electrical panels and troubleshooting, to track tacts, measure the insula-
prolong their operational down the specific failed tion resistance of the line
lifetime. Use together, ther- component at fault. It can and load circuits to ground,
mal imagers can detect also check for phase imbal- and winding resistance
potential problems and ance, bad connections, and phase to phase and phase
insulation resistance and abnormal heating on the to ground.
electrical tests can deter- electrical supply.
mine the cause.

From the Fluke Digital Library @ www.fluke.com/library


About thermal measurements

A motor’s heat signature will Examples


tell you a lot about its qual-
ity and condition. If a motor is This thermal image shows a drive cabinet with hot connections on both A
overheating, the windings will and B phases. The exact cause can’t be determined solely from the image,
rapidly deteriorate. In fact, every although it may be a load or balance issue.
increase of 10 °C on a motor’s
windings above its design oper-
ating temperature cuts the life
of its windings’ insulation by 50
percent, even if the overheating
is only temporary.
If a temperature reading in
the middle of a motor housing
comes up abnormally high, take
a thermal image of the motor and
find out more precisely where
the high temperature is coming
from, i.e. windings, bearings or This image shows a warm bearing (or seal) on the pump. Clearly the access
coupling. (If a coupling is running is tight but we can still compare the bearing to the housing around it.
warm it is an indicator of mis-
alignment.)
There are three primary causes
for abnormal thermal patterns;
typically most are the result of
a high-resistance contact sur-
face, either a connection or a
switch contact. These will usu-
ally appear warmest at the spot
of high-resistance, cooling off the
further away from the spot. This
thermal image shows a clas-
sic pattern in the center phase
connection on the line-side of a This image shows another bearing prob- This image shows the motor itself
breaker; note how the conductor lem with heat also transferring into the heating up, due to reduced airflow
cools off at the top of the image. coupling on the right side. or, more probably, to misalignment.
Load imbalances, whether
normal or out of specification,
appear equally warm throughout
the phase or part of the circuit
that is undersized/overloaded.
Harmonic imbalances create
a similar pattern. If the entire
conductor is warm, it could be
undersized or overloaded; check
the rating and the actual load to
determine which.
Failed components typically
look cooler than similar, nor-
mally functioning ones. The most
common example is probably a
Fluke thermal imagers now include IR-Fusion®*,
blown fuse. In a motor circuit
a technology that fuses a visual, or visible light,
this can result in a single phase
image with an infrared image for better identifi-
condition and, possibly, costly
cation, analysis and image management.
damage to the motor. *The Fluke Ti20 comes with InSideIR™ analysis and reporting
software with free updates for the life of the product.

2 Fluke Corporation Electrical, insulation and thermal measurements for motors and drives
About insulation resistance testing

Insulation problems on motors


and drives are usually caused
by improper installation, envi-
ronmental contamination,
mechanical stress or age. Insu-
lation testing can easily be
combined in with regular motor
maintenance, to identify degra-
dation before failure, and during
installation procedures to verify
system safety and performance.
When troubleshooting, insula-
tion resistance testing can be the
missing link that enables you to
get a motor back into operation
the easy way, by simply replac-
ing a cable.
Insulation testers apply a dc
voltage across an insulation
system and measure the result-
ing current. This allows them to
calculate and display the resis-
tance of the insulation. Typically,
the test verifies high insulation
resistance between a conductor
and ground or high insulation
resistance between adjacent
conductors. Two common Electrical and insulation resistance
examples include testing motor tests on motors
windings for insulation from the 2. Control contacts
motor frame and checking phase
1. Visual inspection
conductors for resistance from First, look for a reason NOT check
bonded conduit and enclosures. to energize. Remove power Next, check the control con-
Insulation multimeters combine from the motor and starter tacts for quality of contact:
the insulation resistance func- (or drive), following lockout/ 1. Lockout and tagout the
tions above with the other tests tagout procedures, and dis- disconnect to the starter.
needed to investigate motor, engage the motor from the
load. 2. Manually engage the
drive, and electrical trouble, from
starter, so the contacts
basic supply measurements to
contact temperature. The key
• Conduct a visual, smell, close.
and heat inspection, inter-
difference is that insulation view the client and check 3. Set the insulation tester
resistance tests are performed the nameplate. Look for to the low ohms range.
on de-energized systems, while loose connections at 4. Measure the resistance
electrical tests (and thermal) are the starter and check all across each set of con-
almost always performed on live, fasteners. tacts.
operating systems.
• Use a DMM to check the 5. The reading should be
supply voltage, then the nearly zero. If it’s higher
voltage starter contacts. than 0.1 ohms, that set
Don’t risk a fire from a pos- of contacts needs to be
sibly shorted motor. If the replaced.
supply is good, then there’s
a motor problem.

3 Fluke Corporation Electrical, insulation and thermal measurements for motors and drives
3. Resistance of line and To pass these tests, the line 4. Winding resistance
load circuits to ground and load circuits need to phase to phase and
show high resistance. phase to ground
Then, measure the insulation As a general rule, ac
resistance of the line and devices need a minimum Take insulation resistance
load circuits to ground. 2 megohms to ground measurements phase to
However, before doing ANY and DC devices need phase and phase to ground.
insulation resistance test- 1 megohm to ground to Good results:
ing, you MUST isolate any
electronic controls and
ensure safe operation. • Balanced comparative low
Note: Different companies have differ- resistance values on all
other devices from the cir- ent threshold minimums for insulation three stator phases
cuit under test. Then: resistance on used equipment, ranging
1. Lockout and tagout the from 1 to 10 megohms. Resistance • High resistance values
on new equipment should test much on the phase to ground
disconnect to the starter. higher—from 100 to 200 megohms insulation test
or more.
2. Set the insulation tester Problems:
to the appropriate test
voltage (250, 500 or
If the load side resistance • Gross resistance deficien-
values are acceptable then cies, such as a phase on
1000 V). proceed to the next test. phase short.
3. Identify the resistance If they aren’t, then start
between these points: tracing the problem: is the • Any winding to winding

resistance imbalance. If
insulation breakdown in the
• Line side of starter load side of the starter, the
the readings differ by more
to ground than a few percent, the
cables, or the motor?
• Load side of starter motor is probably unsafe
to ground to energize.

Fluke. Keeping your world


up and running.®

Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2005, 2007 Fluke Corporation.
Specifications subject to change without notice.
Printed in U.S.A. 1/2008 2517897 A-EN-N Rev B

4 Fluke Corporation Electrical, insulation and thermal measurements for motors and drives

You might also like