2. Verify that installations have been made in accordance with the 90.7, 110.3(B)
instructions included in listing and labeling of materials and
equipment.
3. Identify installations and equipment requiring special approval or
90.4, 90.7,
investigation.
110.2, 110.3
4. Verify that interrupting ratings and short-circuit current ratings 110.9, 110.10,
are adequate for the conditions of the installation. 110.24
7. Check for secure mounting and adequate ventilation space for 110.13
equipment.
Copyright © 2015 by Jones & Bartlett Learning, LLC, an Ascend Learning Company 1 of 2
General Requirements Inspections
8. Check for proper use and ratings of splices and terminations. 110.14(A) and
(B)
11. Check for markings on enclosures and verify appropriate ratings 110.28
for the environment.
13. Verify that working space and dedicated space are not used for 110.26(B)
storage.
14. Check adequacy of entrance to and egress from working space in 110.26(C),
general and verify that spaces containing large equipment have at 110.26(C)(2)
least two entrances/exits or the equivalent.
15. Verify that working spaces have adequate illumination. 110.26(D)
16. Check for identification of disconnecting means and circuit 110.22, 408.4
directories for panelboards, switchboards, switchgear and similar
equipment.
Source: Data from NFPA 70E, Electrical Safety in the Workplace, 2009.