NATIONAL GRID SA

Title: Checklist Index Number:


CL-NG-6460-002-064
Checklist for Over-Current & Earth Fault Protection Relay Revision Number: Page Number:
Commissioning 01 1 of 2
APPROVED
09 MAY 2023
1.0 Equipment General Data and Information
Substation NARJIS S/S 132/13.8KV
Bay/Panel METERING CONSUMER OUTGING FEEDER -2 (H13)
Equipment 51/51N & 87L Serial No 2207502652

2.0 Mechanical Check and Visual Inspection


Item Description Done Remarks
General Visual Inspection. (marked check list CL-NG-6460-002- DONE
1. -------
056 should be attached )
On Units fitted with hand reset flag indicators, check that the flag is NOT N/A
free to fall before, or just, any contacts closes. Make sure that the DONE
2.
reset mechanism in the cover is correctly located with respect to
the relay element and the flag (or mechanism) can be reset.
3. Check condition of any connectors, contacts alignment and travel. DONE -------
4. Check armature gap. DONE -------
3.0 Electrical Tests
Item Description Done Remarks
General Electrical Tests. (Marked check lists CL-NG-6460-002-057 DONE
1. -------
And CL-NG-6460-002-058 should be attached)
Check for External resistors, where applicable. NOT NA
2.
DONE
3. Check relay configuration. DONE -------
Check displayed measurements in primary or secondary values if DONE
4. -------
applicable. error % = (measured – expected) /expected
Perform relay self-test procedure and external communications NOT
5. NA
checks on digital/numerical relays. DONE
Check Pick-up, Drop off and reset factor Values of Over Current for DONE
6. all phases & Earth fault (Low set stage) for definite time over current -------
and earth fault relay/curve (for several setting adjustments).
Check Tripping Time of Over Current for all phases & Earth fault NOT NOT
7. (Low set stage) for definite time over current and earth fault DONE INFINAL
relay/curve ( for several setting adjustments ) SETTING
Check Pick-up, Drop off and reset factor Values of Over Current for NOT NOT
8. all phases & Earth fault (High set stage) for definite time over DONE INFINAL
current and earth fault relay/curve ( for several setting adjustments ) SETTING
Check Tripping Time of Over Current for all phases & Earth fault NOT NOT
9. (High set stage) for definite time over current and earth fault DONE INFINAL
relay/curve ( for several setting adjustments ) SETTING
10. Check binary inputs and outputs and annunciations. DONE -------
11. For Inverse Time Over Current Elements. DONE -------
Check Normal inverse characteristics on different multiples of plug DONE
a) -------
setting /current setting. (For all 3 phase over current & earth fault )
NATIONAL GRID SA

Title: Checklist Index Number:


CL-NG-6460-002-064
Checklist for Over-Current & Earth Fault Protection Relay Revision Number: Page Number:
Commissioning 01 2 of 2

Check Very inverse characteristics on different multiples of plug NOT NOT IN


b) setting /current setting. (For all 3 phase over current & earth fault ) DONE FINALL
SETTING
Check Extremely inverse characteristics on different multiples of NOT NOT IN
c) plug setting /current setting. (For all 3 phase over current & earth DONE FINALL
fault ) SETTING
Check Long time inverse characteristics on different multiples of NOT NOT IN
d) plug setting /current setting. (For all 3 phase over current & earth DONE FINALL
fault ) SETTING
Check Tripping Time of Over Current for all phases & Earth fault DONE
e) -------
(High set stage.) ( for several setting adjustments )
12. Check binary inputs and outputs and annunciations. DONE -------
13. Check tripping indication. DONE -------

CSD T&C Contractor Item Number


Name YASSER A.REHMAN(106931) AHMED SABRY/JAL-066
Sign.
Date 07/01/2024 07/01/2024
Name
Sign.
Date