I. INTRODUCTION
This Performance Innovative Task (PIT) of the subject CE67: Reinforced Concrete
Design 2 is a Proposed Two-Storey Commercial Building as a requirement for the 2nd Semester
of S.Y 2018-2019. The commercial building includes a space for a 2 floors fastfood chain with a
roof deck and 3 space for space for lease in each floor. It is also incorporated with utilities and
comfort rooms.
The submitter suggested that the location will be in Poblacion, Ubay, Bohol which
is 24.8 km away from its nearest fault, East Bohol Fault. The other data of the project will be
indicated and classified below.
REINFORCEMENTS
Steel reinforcing deformed bars shall conform to AASHTO M31/ATSM A615
Grade 40 (276 MPa) for 10mm diameter below and Grade 60 (414 MPa) for 12 mm
diameter above.
(Source:http://www.academia.edu/5267142/DESIGN_CRITERIA_Structural_Desig
n_Criteria_of_the_Proposed))
Structural Analysis and Design Criteria of the Proposed NOVEMBER 2018
By: Javier, Jennifer D.
TWO-STOREY COMMERCIAL BUILDING BSCE5a_b1
IV. LOADS
DEAD LOADS
The actual weights of materials and constructions shall be used in determining the
dead loads for the purpose of design. The submitter only listed the materials that are
essential in this project to summarized the table. In the absence of definite information,
values for materials will be based in Table 204-1 and 204-2 from the NSCP 2015.
Material/Component Density/Load
Aluminum 26.7 kN/m3
Concrete, Reinforced:
Stone, including gravel 23.6 kN/m3
Covering:
Roof, Bituminous gravel covered 0.24 kN/m2
Floor Finishes:
Ceramic or quarry tile (20mm) on
13mm mortar bed 0.26 kN/m2
Walls:
Masonry 21.2 kN/m3
-4” CHB wall
-Plaster
-Grout
Glass 0.38 kN/m2
LIVE LOADS
Floors shall be designed for the unit live loads as a set forth in Table 205-1. These
loads shall be taken as the minimum live loads of horizontal projection to be used in
the design of buildings for the occupancy listed and loads at least equal shall be
assumed for uses not listed in this section but that creates or accommodates similar
loading.
For additional information of data, notes are indicated below the table 205-1 for the
conditions indicated for the live loads.
Site Location
-The Philippine archipelago is divided into two seismic zone, zone 2 covers
provinces of Palawan, Sulu and Tawi-Tawi while the rest of the country is under
Zone4.
Each structure shall be assigned a
seismic zone factor Z, in accordance to Table
208-3.
Source: http://faultfinder.phivolcs.dost.gov.ph/
Structural Analysis and Design Criteria of the Proposed NOVEMBER 2018
By: Javier, Jennifer D.
TWO-STOREY COMMERCIAL BUILDING BSCE5a_b1
- the location shown in the map will indicate that the values to be used for the near
source factors, Na & Nv, will be in accordance with the Tables 208-5 and 208-6 as set
forth in section 208.4.4.2.
Combination of Loads
- The required stength, U, shall be atleast equal to the effects of factored loads in
Table 405.3.1 with exceptions and additions in section 405.3.3 through 405.3.12 (based
on NSCP 2015).