Input Data:
No. of levels (including ground floor) : 3
Average level height : 6 m
2
Floor Area : 8500 m
2
Exterior building wall area per floor : 700 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
Stairwell wall area per floor : 16 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
Elevator shaft walls : 14 m2
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
The area gap around each stairwell door : 0.024 m2
Outside design temperature : 40.5 deg C
Stairwell temperature : 35 deg C
Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 20 Pa
Calculations:
Abo Flow area between the building and outside per floor = 0.147 m2
Asb Flow area between stairwell and the building per floor = 0.026 m2
In this system, an exterior stairwell door opens automatically upon system activation. In addition,
the lower two floors will be considered opened, while the others doors will be considered closed
(= 9523 cfm)