1. Input Data:
2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa
5. Calculations:
Abo Flow area between the building and outside per floor = 0.088 m2
Asb Flow area between stairwell and the building per floor = 0.032 m2
Project No. Date
In this system, an exterior stairwell door opens automatically uopn system activation. In addition, the low
two floors will be considered opened, while the others doors will be considered closed.