Isolated footing is defined as an independent footing for each column. It may be pad
footing or sloped footing.
Gross bearing capacity: It is defined as total pressure acting at the base of footing
including self weight, weight of column, overburden pressure of soil above footing,
etc.
Safe bearing capacity: It is defined as a net pressure at the base of the footing after
deducting weight of the excavated soil (overburden pressure).
Critical Section:
= 𝑝 × 𝑏𝑓
2. Critical Section for one way shear
𝜏𝑐 = 0.25 𝑓𝑐𝑘
If 𝜏𝑣 < 𝜏𝑐 ′ … … 𝑆𝑎𝑓𝑒 𝑖𝑛 𝑡𝑤𝑜 𝑤𝑎𝑦 𝑠𝑒𝑎𝑟.
∴ 𝑃𝑡 = 0.177 %
Also, for Fe 415, 𝑃𝑡 (𝑚𝑖𝑛 .) = 0.205 %
∴ 𝑝𝑟𝑜𝑣𝑖𝑑𝑒 𝑝𝑡 = 0.205 %
0.205
∴ 𝐴𝑠𝑡 = × 2100 × 412 = 1774 𝑚𝑚2
100
Provide 16 – 12 mm diameter bar [ 𝐴𝑠𝑐 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 = 1810 𝑚𝑚2 ]
(f) Check for cracking
2100 −100−12
c/c distance between bars = = 132.53 𝑚𝑚
15
Here, 𝝉𝒗 < 𝝉𝒄 … . 𝑶𝑲
By: CHIRAG PATEL Page 4
(h) Check for two way shear
Average Depth = 𝑑𝑎𝑣𝑔 = 0.5 (424 + 412)
= 418 𝑚𝑚
𝑏 ′ = 350 + 209 + 209 = 768 𝑚𝑚
𝑏0 = 𝑙𝑒𝑛𝑔𝑡 𝑜𝑓 𝑐𝑟𝑖𝑡𝑖𝑐𝑎𝑙 𝑠𝑒𝑐𝑡𝑖𝑜𝑛 = 4𝑏 ′ = 4 × 768
= 3072
𝑉𝑢 = 𝑝 × 𝑎𝑡𝑐 𝑎𝑟𝑒𝑎 = 272.1 × 2.12 − 0.7682
= 1040 𝐾𝑁
𝑉𝑢 1040 ×10 3
Now, 𝜏𝑣 = =
𝑏0 𝑑 3072 ×418
𝐴1 4.41
∴ = = 6 > 2.
𝐴2 0.1225
𝐴1
∴ 𝑡𝑎𝑘𝑒 =2
𝐴2
𝐴1
∴ 𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑒 𝑏𝑒𝑎𝑟𝑖𝑛𝑔 𝑓𝑜𝑟𝑐𝑒 = 0.45 𝑓𝑐𝑘 × 𝐴𝑐
𝐴2
0.5
Minimum dowel area (0.5%) = × 350 × 350 = 612.5 𝑚𝑚2
100
∴ 𝑃𝑡 = 0.476 %
Also, for Fe 415, 𝑃𝑡 (𝑚𝑖𝑛 .) = 0.205 %
∴ 𝑝𝑟𝑜𝑣𝑖𝑑𝑒 𝑝𝑡 = 0.476 %
0.476
∴ 𝐴𝑠𝑡 = × 500 × 532 = 1266 𝑚𝑚2
100
Provide 12 – 12 mm diameter bar [ 𝐴𝑠𝑐 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 = 1356 𝑚𝑚2 ]
(f) Check for cracking
2100 −100−12
c/c distance between bars = = 180.72 𝑚𝑚
11
𝑁𝑜𝑤 , 𝜏𝑐 ′ = 𝑘𝑠 . 𝜏𝑐
𝐴1 4.41
∴ = = 6 > 2.
𝐴2 0.1225
𝐴1
∴ 𝑡𝑎𝑘𝑒 =2
𝐴2
𝐴1
∴ 𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑒 𝑏𝑒𝑎𝑟𝑖𝑛𝑔 𝑓𝑜𝑟𝑐𝑒 = 0.45 𝑓𝑐𝑘 × 𝐴𝑐
𝐴2
0.5
Minimum dowel area (0.5%) = × 350 × 350 = 612.5 𝑚𝑚2
100
As the footing is rectangular, size of footing may be selected such that the
effective cantilever projection on both sides are equal.
Difference between dimension of column = 0.75 – 0.25 = 0.5 m.
If b is width of footing,
∴ 𝑏 𝑏 + 0.5 = 10
∴ 𝑏 2 + 0.5𝑏 − 10 = 0
∴ 𝑏 = 2.92 𝑚 ≈ 2.95 𝑚
Provide size of footing = 2.95 m × 3.45 m.
∴ Area of footing = 10.17 𝑚2 > 10 𝑚2 …..O.K.
(b) Net upward pressure
𝑓𝑎𝑐𝑡𝑜𝑟𝑒𝑑 𝑙𝑜𝑎𝑑 1.5 ×2000
∴𝑝= = = 294.8 𝑘𝑁/𝑚2
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑓𝑜𝑜𝑡𝑖𝑛𝑔 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 2.95 ×3.45
∴ 𝑃𝑡 = 0.831 %
∴ 𝑃𝑡 = 0.399 %
Also, for Fe 415, 𝑃𝑡 (𝑚𝑖𝑛 .) = 0.205 %
∴ 𝑝𝑟𝑜𝑣𝑖𝑑𝑒 𝑝𝑡 = 0.399 %
0.399
∴ 𝐴𝑠𝑡 = × 900 × 882 = 3167 𝑚𝑚2
100
Provide 28 – 12 mm diameter bar [ 𝐴𝑠𝑡 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 = 28 × 113 = 3164 𝑚𝑚2 ]
Check for cracking along y -direction
3450 −100−12
c/c distance between bars = = 123.62 𝑚𝑚
27
𝑁𝑜𝑤 , 𝜏𝑐 ′ = 𝑘𝑠 . 𝜏𝑐
𝑘𝑠 = 0.5 + 𝛽𝑐 , 𝑏𝑢𝑡 𝑘𝑠 𝑠𝑜𝑢𝑙𝑑 𝑛𝑜𝑡 𝑒𝑥𝑐𝑒𝑒𝑑 1.
∴ 𝜏𝑐 ′ = 0.83 × 0.25 𝑓𝑐𝑘 𝑠𝑜𝑟𝑡 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛 250
𝛽𝑐 = = = 0.33
𝑙𝑜𝑛𝑔 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛 750
∴ 𝜏𝑐 ′ = 0.83 × 0.25 × 20
∴ 𝜏𝑐 ′ = 0.928 𝑁/𝑚𝑚2 ∴ 𝑘𝑠 = 0.5 + 𝛽𝑐 = 0.5 + 0.33 = 0.83 < 1