You are on page 1of 3

Electrical Science Solutions  

ESS_DEC_2016    

Why Voltage Monitoring Is Required Part‐I. 
 

Author: Prasad Gore                                                                                                     Edition: ESSDEC2016 
 

Abstract: Offices are 1 ph loads almost evenly distributed on 3 phase supply. However when system 
comes in operations there exist an unbalance situations. As we know with advancement in 
technology, working Voltage limits of components are shortened. This paper explain you how above 
situation makes it difficult for very sensitive electronic equipment. 

This is a case we are sharing through this paper and hence theoretical aspect shall not be 
discussed in details. Its an attempt to share our findings. 

1. General :  
In offices/stores we have all single phase equipment and evenly distributed on 3 phase supply. When 
we see design aspect we see cable size as per its ampacity and voltage drop at full load. Everything 
looks normal when we see a steady state conditions. However we will explain here what may 
happen with voltage in transient/ inrush current and even when unbalance loading.  

2. Case I 
We see a design where lets say 6 sqmm cable is used and ACs/lights/PCs (15 kva Loads ) are evenly 
distributed and in steady state condition load unbalance is not more than 25%.  

Now we know if we considered 415V as base +‐10% is the range where utility supply voltage. 

415  456.5  373.5 

Looks fine as below 

Developed By : PRASAD GORE ELECTRICAL SCIENCE SOLUTIONS

Source Voltage Line Resistance Load Expected Voltage At Load Load Current


V Angle W/VA PF V Angle A Angle
Cable Size 
435 Er R Ph V 251 0 In Sqmm 6 R Ph Load  5000 0.7 Vr R ph Load  248 1 Ir 19.32 ‐44
Length In 
435 Ey Y Ph V 251 ‐120 km 0.08 Y Ph Load 5000 0.7 Vy Y Ph Load 248 122 Iy 19.32 77
435 Eb B Ph V 251 120 Core 4 B Ph Load  5000 0.7 Vb B Ph Load  248 ‐118 Ib 19.32 ‐163

Cu 
E en V 0 0 Conductor 0.25 0.03 Total Load 15 Vne 0 ‐41 In 0 ‐43
Inrush 
AL  Current 6 
Conductor 0.42 0.02 time 115 ‐1.4% 240 264 10%
Select 
Voltage Change %
Cond 0.25 0.03 ‐1.4% 240 216 ‐10%
DC 
Resistanc Inductanc
e e ‐1.4% 415 456.5 373.5
Standard Voltage  
Source Voltage 435V/ 251V 15 kVA Load side voltage 248V Voltage drop 1.4%, Looks OK. 

See Load Voltage graph below. 

prasad@electricalsciencesolutions.com   
Electrical Science Solutions  
ESS_DEC_2016    

 
 

3. Case II 
Now as mentioned earlier there are loads with 4‐6 times starting/ inrush currents, particularly ACs. 
Now when this situation comes, we may see below situation which definitely last for few cycles only, 
but certainly damaging sensitive electronic equipment. Due to this inrush R ph voltage drops but 
neutral gets shifted and B phase voltage raises. 

Developed By : PRASAD GORE ELECTRICAL SCIENCE SOLUTIONS

Source Voltage Line Resistance Load Expected Voltage At Load Load Current


V Angle W/VA PF V Angle A Angle
Cable Size 
435 Er R Ph V 251 0 In Sqmm 6 R Ph Load  25000 0.2 Vr R ph Load  241 10 Ir 92.11 ‐63
Length In 
435 Ey Y Ph V 251 ‐120 km 0.08 Y Ph Load 4000 0.7 Vy Y Ph Load 235 114 Iy 14.71 69
435 Eb B Ph V 251 120 Core 4 B Ph Load  3000 0.7 Vb B Ph Load  269 ‐121 Ib 12.68 ‐166

Cu 
E en V 0 0 Conductor 0.25 0.03 Total Load 32 Vne 21 ‐72 In 81 ‐73
Inrush 
AL  Current 6 
Conductor 0.42 0.02 time 115 ‐4.1% 240 264 10%
Select 
Voltage Change %
Cond 0.25 0.03 ‐6.5% 240 216 ‐10%
DC 
Resistanc Inductanc
e e 7.2% 415 456.5 373.5
Standard Voltage  
See voltage graph below, 

  

prasad@electricalsciencesolutions.com   
Electrical Science Solutions  
ESS_DEC_2016    

1. Case III 
Now everything remains same as per case II i.e. inrush current and other loads but we replace 6 
sqmm with 25 sqmm and with this B phase voltage reduce from 269 V to 256 V which comes well 
below 264V. 

Developed By : PRASAD GORE ELECTRICAL SCIENCE SOLUTIONS

Source Voltage Line Resistance Load Expected Voltage At Load Load Current


V Angle W/VA PF V Angle A Angle
Cable Size 
435 Er R Ph V 251 0 In Sqmm 25 R Ph Load  25000 0.2 Vr R ph Load  248 2 Ir 94.21 ‐75
Length In 
435 Ey Y Ph V 251 ‐120 km 0.08 Y Ph Load 4000 0.7 Vy Y Ph Load 247 119 Iy 15.53 73
435 Eb B Ph V 251 120 Core 4 B Ph Load  3000 0.7 Vb B Ph Load  256 ‐120 Ib 12.09 ‐166

Cu 
E en V 0 0 Conductor 0.06 0.10 Total Load 32 Vne 5 ‐77 In 85 ‐83
Inrush 
AL  Current 6 
Conductor 0.10 0.06 time 115 ‐1.1% 240 264 10%
Select 
Voltage Change %
Cond 0.06 0.10 ‐1.8% 240 216 ‐10%
DC 
Resistanc Inductanc
e e 1.7% 415 456.5 373.5
Standard Voltage  
 

This explains that even we have balance load system, single phase inrush current makes system 
unbalance for few cycle so below points shall be considered, 

1. Input voltage level: Recommend to keep at 400‐415V. 
2. Cable Impedance : Recommend to calculate inrush current drop magnitude and duration. 
3. Design limits of sensitive equipment.   

See actual data captured by us. 

   
In case of any queries please write us back on prasad@electricalsciencesolutions.com  
Know More About Us 
 
https://www.facebook.com/electricalsciencesolutions/  

 
https://www.linkedin.com/company/electrical‐science‐solutions
 
 

 
 
 
http://electricalsciencesolutions.blogspot.in/  

 
 

https://www.youtube.com/channel/UCMTTCqH2rDQ5iyeW5Iudbsg  

prasad@electricalsciencesolutions.com   

You might also like