SUMMARY

FEEDER NAME TR MAINS 5H FLR SUBSTN

CHANNEL CURRENT VOLTAGE


ANALYSER PROBE R‐A1 Y‐A2 B‐A3 N‐AN R‐ V1 Y‐V2 B‐V3 N‐VN E‐E
FEEDER PHASES R Y B N R Y B N BODY EARTH

CASE‐ (CONCERN POINTS) CASE DESCRIPTION
C.1
CASE # C.1 ‐ TO UNDERSTAND TREND FOR 24 HRS
425 OVERALL OBSERVATION
C1.1‐ LOW VOLTAGE VALUE OF 402 V FOUND AND RELATED CHANGE IN CURRENT SEEN, THIS IS 
420 POSSIBLY FROM SOURCE SIDE.
V C1.2‐ THERE IS CYCLIC LOAD , LIKELY DUE TO HVAC LOAD. REFER TRANSIENT TO SEE EFFECTS.
415
C1.3 ‐ N‐E VOLTAGE EXCEEDING 5 V
410

405 RECOMMENDATION
A‐ 
12-Nov-19 23:59:35 (h:min:s) 13-Nov-19
12:37:20 PM 4 h/Div 12:36:55 PM B

C1.1 C

426 680
D
424 660 CASE # C.2 ‐ TO UNDERSTAND TREND FOR 24 HRS
422
640 OVERALL OBSERVATION
420
418 620
1
416
V A 600
414 2
580
412
410 560 3
408 540 4
406 520
404 RECOMMENDATION
500
13-Nov-19 21:57.055 (min:s) 13-Nov-19 13-Nov-19 21:57.055 (min:s) 13-Nov-19 A
11:36:11.273 AM 4 min/Div 11:58:08.328 AM 11:36:11.273 AM 4 min/Div 11:58:08.328 AM
B

C1.2 C
680 D
425
660
640
420
620
V 415 A 600

580
410 560
540
405 520

12-Nov-19 2:05:05 (h:min:s) 12-Nov-19 12-Nov-19 2:05:05 (h:min:s) 12-Nov-19


12:37:20 PM 25 min/Div 2:42:25.339 PM 12:37:20 PM 25 min/Div 2:42:25.339 PM