You are on page 1of 55

Operating and service manual

Controlled Atmosphere
Star Cool refrigeration unit Model SCI - XX - X - CA

24-hour hotline support

Call us at +45 7364 3500 or send us an e-mail at service@starcool.


dk. Our service department is available 24 hours a day, 7 days a week -
providing easy access to the answers you need.

Guideline: Order procedure

Purchase spare parts for the Star Cool reefer machine fast and reliable
via the internet.

Customers, service providers and other repair shops order directly from
Star Cool. Vessels shall contact the relevant customer (shipping line) for
ordering.

All orders are placed centrally with Star Cool where our staff will assign
the order to the distribution centre located closest to the required
delivery address and arrange shipment from there.

To be able to order spare parts from www.starcool.dk, please


register at the site, to receive a login and password.

Bjerndrupvej 47
6360 Tinglev, Denmark
Phone: +45 73 64 34 00
Fax.: +45 73 64 35 69
E-mail: starcool@starcool.dk
www.starcool.dk

Version 810800A - Dec 2010


Version 810800A - Dec 2010 © Copyright 2010 Maersk Container Industry AS
Operating and service manual, Controlled Atmosphere

Preface
The Star Cool CA is a controlled atmosphere system designed to prolong the shelf life of perisha-
bles by regulating the internal atmosphere of the container. The container’s atmosphere obtains the
desired gas composition based on entered set points for O2 and CO2 via the controller.
The desired atmospherical composition of the gas serves to lower the respiration of the perishables,
and thereby providing a prolonged shelf life.

ATTENTION! Due to regulation of the cargo atmosphere during transport, oxygen level
may be low and/or carbon dioxide level high inside the container! Please check gas levels
and flush with fresh air before entering and unloading. Exposure to low oxygen/high car-
bon dioxide may cause loss of consciousness and suffocation.

This version of the manual is dated December 2010, edited by Maersk Container Industry AS.
All rights reserved. This user’s manual is valid for software version 0345 or newer versions.
The information herein is subject to change without notice and does not represent a commitment on
any part of Maersk Container Industry AS.
While the information herein is assumed to be accurate, Maersk Container Industry AS assumes no
responsibility for any errors or omissions that may appear in this documentation.

This manual is valid for:

Model SCI - XX - X - CA
Release Date 01.12.2010

Warnings
Do not operate or maintain this refrigeration unit until you have familiarized your-
self completely with the equipment and operating of this unit by reading the in-
struction in this addendum and the Operating and service manual for Star Cool
units.

Do not enter the container - including opening the service hatches - when
oxygen level is below 20.9%.

Do not perform any welding on the unit before disconnecting the power plug.

Disconnect main power supply to unit before inspecting the interior of the con-
troller box.

The unit is charged with R134a and ester oil BSE 55. Do not use any other refrig-
erant or oil.

Do not use contaminated refrigerant or oil.

Do not release R134a into the atmosphere. Use recovery equipment according to
present legislation.

During maintenance please observe that R134a is operating with high and low
temperatures in combination with high pressures, which may cause personal in-
juries if not handled properly.

During recovery and maintenance of R134a unit personal protection equipment


has to be worn.

Do not trap any liquid refrigerant inside pipes during soldering work. This may
lead to explosion of pipe.

1
Operating and service manual, Controlled Atmosphere

Contents
Preface .......................................................................................................................................................1
Warnings ....................................................................................................................................................1
Legend........................................................................................................................................................3
CA function overview - two versions ...............................................................................................................3
Container venting procedure .........................................................................................................................5
Menu structure ............................................................................................................................................7
Setpoints ....................................................................................................................................................8
CA function on/off ........................................................................................................................................8
Additional menu information for CA ................................................................................................................8
Data log ......................................................................................................................................................9
Warning ......................................................................................................................................................9
Pre Trip Inspection, PTI.................................................................................................................................9
Manual inspection ...................................................................................................................................... 10
Function test ............................................................................................................................................. 10
Operation .................................................................................................................................................. 10
Manual mode ............................................................................................................................................. 10
CA curtain ................................................................................................................................................. 11
Vacuum system test ................................................................................................................................... 11
Problem surrounding the vacuum hose ......................................................................................................... 12
Problem located at membrane ..................................................................................................................... 12
Simple trouble shooting vacuum pump / controller module ............................................................................. 12
Container leak test ..................................................................................................................................... 12
Oil charge and drain ................................................................................................................................... 13
Replacement of vacuum pump heating element ............................................................................................. 13
Locations of components ............................................................................................................................. 14
Components .............................................................................................................................................. 15
Replacing the controller module ................................................................................................................... 18
Temperature sensor alarms (1XX) ................................................................................................................ 19
Pressure sensor alarms (2XX)...................................................................................................................... 22
Other sensor alarms (3XX) .......................................................................................................................... 26
Power alarms (4XX) ....................................................................................................................................28
Operation alarms (6XX) .............................................................................................................................. 29
Communication alarms (7XX) ...................................................................................................................... 36
Test alarms (8XX).......................................................................................................................................39
Controller alarms (9XX) .............................................................................................................................. 47
Controller overview .................................................................................................................................... 49
Overall wiring schematic ............................................................................................................................. 53
Overall wiring schematic (alternate) .............................................................................................................54

2
Operating and service manual, Controlled Atmosphere

Legend
Short name Name
Pmem Membrane pressure
Tpump Vacuum pump temperature
Mpump Vacuum pump
Hpump Heating element
Mair Fresh air motor

CA function overview - two versions

Inside Container

O2 CO2

CA membrane
Fresh air valve

RS 485

Pressure sensor
P

Output

Vacuum Pump PTC Controller


module SMC6

RS 485
Thermal circuit switch
(Only available for some models)

RS 485

Signals
PTC Controller
Temperature sensor module SSC6-
Vacuum Vacuum pump CA
Air flow Heating element

3
Operating and service manual, Controlled Atmosphere

Inside Container

O2 CO2

CA membrane
Fresh air valve

RS 485

Pressure sensor
P

Output

Vacuum Pump PTC

RS 485

Controller
module SMC6.1

PTC
Signals
Temperature sensor
Vacuum Vacuum pump

Air flow Heating element

4
Operating and service manual, Controlled Atmosphere

The basic principle is that the fruit will generate CO2 from O2 via respiration. This will increase the
CO2 level and decrease O2 level inside the container. When the CO2 level reaches above the CO2
set point the vacuum pump will activate and evacuate CO2 with the selective membrane. In case
the O2 level goes below the O2 set point the fresh air valve will open and let in ambient air (20,9%
O2). This described mechanism will regulate the gas concentration within the container as illustrated
below:
Gas
Concentration
O2 level
CO2 level

Time
Warning
Due to low oxygen levels inside the container, ventilation is necessary before entering, either
for repairing the unit or unloading. Stay away from doors while venting.

Container venting procedure


TO BE PERFORMED WHENEVER ENTERING THE UNIT/CONTAINER IS NECESSARY

1. Press for operation and select O03 and set Air flow mode to “NORMAL”.
2. Open fresh air module fully. AL 834 may appear.
3. Wait for O2 level to reach 21% +/- 2% before entering.
4. Close air module and clear AL 834.
General specification
Additional components to a standard unit:

• O2 sensor
• CO2 sensor
• Vacuum pump
• Membrane
• Vacuum hose
• Fresh air module incl. motor

Fresh air motor


Type Gear motor
Supply 12-24 V DC

CO2 sensor
Type Nondispersive infrared sensor
Operating range 0 - 20%

5
Operating and service manual, Controlled Atmosphere

Accuracy CO2 (5%) +/- 0,3%


CO2 (0,5%) +/-0,1%
Supply 8-15V DC
Output RS-485

O2 sensor
Type Ziconium Oxide
Operating range 0 - 21%
Accuracy At O2 (3%) +/- 0,5%, temperature ranges
from -1 - 15°C
Supply 8-15V DC
Output RS-485

Pressure transmitter
Type Ratiometric
Operating range -1 - 0 Bar
Accuracy ±10 mBar
Supply 5V DC
Output Ratiometric

Temperature sensor
Type NTC, 10 kOhm at 25°C (77°F) 10K3A1
Operating temp. -40°C to 100°C (-40°F to 212°F)
Accuracy ±0.15°C, range -30°C to 100°C (±0.5°F,
-22°F to 212°F)

Vacuum pump, including heating element


Capacity 16 m3/h at 50 Hz and 19 m3/h at 60 Hz
Supply 3 phase AC 50 Hz 340 – 460 Volts and 60 Hz
400-520 Volt
Oil (type/amount) Anderol FGC 32 - 0.35 L

6
Operating and service manual, Controlled Atmosphere

Menu structure
MAIN PAGE INFORMATION PROGRAMS
I01 Relative humidity P01 Active program
I02 Air exchange P02 Multi. Temp setp. >
I03 O2 P03 Cold treatment >
I04 CO2
I05 Last defr interval
AIR EXCHANGE I06 USDA 1 temp
I07 USDA 2 temp

888m3/h
I08 USDA 3 temp
I09 Cargo temp COLD TREATMENT
I10 Time to defrost
B01 Duration
I11 Ambient temp
B02 Maximum USDA temp.
I12 Supply air 1 temp
Press (X) to leave B03 Treatment setpoint
I13 Supply air 2 temp
B04 Final temperature
I14 Return air temp
B05 CT status
I15 Evaporator temp
I16 Suction temp
I17 Suction press
I18 Membrane pressure
I19 Discharge press
I20 Expansion valve MULTI. TEMP. SETP.
I21 Evap superheat
Hour Set %Rh
I22 Compressor freq
D01 OFF 0.0 OFF
I23 Power frequency
D02 OFF 0.0 OFF
I24 Current phase 1
D03 OFF 0.0 OFF
I25 Current phase 2
D04 OFF 0.0 OFF
I26 Current phase 3
D05 OFF 0.0 OFF
I27 Voltage phase 1-2
D06 OFF 0.0 OFF
I28 Voltage phase 2-3
I29 Voltage phase 1-3
I30 Phase direction
I31 Battery voltage
I32 FC temp
I33 Condenser fan
I34 Evaporator fan
I35 Evaporator heater
I36 Pump temperature
MANUAL OPERATION
OPERATION M01 Operating mode
M02 Evaporator heater
O01 Setpoint M03 Evaporator fan
O02 QUEST M04 Condenser fan
O03 Airflow mode M05 Compressor freq
O04 Humidity setpoint M06 Expansion valve
O05 Datalog interval M07 Hotgas valve
O06 PROGRAMS > M08 Economizer valve
O07 O2 setpoint M09 Airex motor
O08 CO2 setpoint M10 Vacuum pump
O09 Active application

DATALOG VIEW
ALARM
L01 Text Temperatures >
A01 Alarm text L02 Text Atmosphere >
A02 ... L03 Graph Temperatures >
... L04 Graph Atmosphere >
A16

TIME ADJUST
SERVICE
C01 GMT-Year
S01 MANUAL OPERATION > C02 GMT-Month
S02 DATALOG VIEW > C03 GMT-Day
S03 TIME ADJUST > C04 GMT-Hour
S04 RUNTIME COUNTERS > C05 GMT-Minute
S05 CONFIGURATION >

RUNTIME COUNTERS
PRE TRIP INSPECTION
R01 Unit
T01 PTI test R02 Compressor
T02 Last R03 Evaporator fan
T03 Function test R04 Condenser fan
T04 Abort the test R05 Evaporator heater
T05 Test status R06 Airex motor sw times
T06 10: Init R07 Vacuum pump
T07 20: Controller
T08 30: Power
T09 40: Evap fan
CONFIGURATION
T10 50: Cond fan
T11 60: Evap heater F01 Container
T12 70: CA F02 Software version
T13 80: Compressor F03 FC type
T14 90: FT status F04 FC ID
T15 105: T set 13 °C F05 Phase detection
T16 100: T set 5 °C F06 AirEx calibration
T17 110: T set 0 °C F07 Low pres type
T18 111: Hold 0 °C F08 High pres type
T19 120: T set -18 °C F09 Main PCB
T20 130: Defrost F10 Model code
T21 140: PTI status

7
Operating and service manual, Controlled Atmosphere

Setpoints
Setpoints are entered via the operation menu

O2 range 3 - 21%
CO2 range 5 - 12%

Setting setpoint: O2 level is set in O07 and CO2 level is set in O08 (Menu structure)

CA function on/off
If the setpoints for O2 and CO2 is set to OFF the CA function is turned off

Additional menu information for CA


In addition to the standard log the following information can be viewed in the log:
Please note that it will take approx. 5 minutes before CO2 and O2 can be viewed in the
display.

I03 O2 level
Function:
Shows the O2 level [%]
Value:
An actual value of the O2 level inside the container.

I04 CO2 level


Function:
Shows the CO2 level [%]
Value:
An actual value of the CO2 level inside the container.

I18 Membrane pressure


Function:
Membrane pressure.
Value:
Actual vacuum pressure between vacuum pump and membrane. Under normal conditions: 40-100
mBar.
StarView enables the display of the following additional information.

O07 O2 set point


Function:
O2 set point.
Value:
-

O08 CO2 level


Function:
CO2 set point.
Value:
-

8
Operating and service manual, Controlled Atmosphere

Data log

Title Info displayed


CO2Set CO2 set point [%]
O2Set O2 set point [%]
Input CO2 CO2 level [%]
Input O2 O2 level [%]
Input Pmem Membrane pressure [mBar]
Input Tpump Oil temperature in the vacuum pump [°C]
Application CAType 0 = CA off 1 = CA on
Control MpumpCA 0 = vacuum pump off 1 = vacuum pump on
Control HpumpCA 0 = heating element off 1 = heating element on
Control MairPct (time opened [%]) 0 = fresh air valve closed 100 = fresh air valve open

Warning
Do NOT enter the container, including opening the service hatches, when the oxygen level is below
20.9% (equal ambient air).

Human response to oxygen low atmosphere:


Oxygen content of Air Symptoms of a person exposed
20.9% Level in ambient air - no effect
15% - 19% May impair coordination and may induce early symptoms
in persons who have coronary, pulmonary or circulatory
problems.
12% - 15% Respiration and pulse increase; impaired coordination, perception
and judgement occurs.
10% - 12% Respiration further increases in rate and depth; poor judgement
and bluish lips occur.
8% - 10% Mental failure, fainting, unconsciousness, an ash-coloured face,
blue lips, nausea and vomiting.
6% - 8% 8 minutes - 100% fatal; 4-5 minutes - recovery with treatment.
4% - 6% Coma within 40 seconds, convulsions, respiration ceases - death

Pre Trip Inspection, PTI


Ensure the following manual inspection and function test is performed before taking the Star Cool
CA unit into operations.
The progress of the pre trip test can be followed in the display T04 in steps.

9
Operating and service manual, Controlled Atmosphere

Manual inspection
1. Check for structural damages on sides, doors and roof on the container.
2. Secure tight plugs at each of the floors drain plugs, placed near corners. Cut-out views from
front end (left picture) and rear end (right picture)

3. Make sure service hatches are in perfect condition and installed correctly.
4. Inspect the fresh air module to ensure it is in perfect condition. Make sure the butterfly is
operational and that the valves are intact.
5. Check drain hose for any damage.
6. Make sure lead-ins (cables and vacuum hose) are intact.
7. Check oil in the vacuum pump.

After ensuring steps 1-7 the unit is now ready for PTI.
Three types of pre trip inspections are available for the Star Cool CA unit: Full PTI, Short PTI and
CA PTI. Please see Star Cool service manual for descriptions on Full PTI and Short PTI.

Function test
Two function tests are available for the Star Cool CA unit: STD and CA.
The CA function test has the following steps:
1. STD function test
2. CO2 sensor test
3. O2 sensor test
4. AirEx motor test

Operation
Set points:
CO2 and O2 set points are entered in the menu structure O07 an O08.
O2 levels below 2% can not be entered.
CO2 levels below 5% can not be entered.

Level readings:
O2 and CO2 concentrations can be viewed in the menu structure I03 and I04. The membrane pres-
sure can be viewed in the menu structure I18 - this displays the vacuum level created. Vacuum
pump oil temperature can be viewed in the menu structure I36.

Manual mode
The AirEx motor can be activated in manual mode in the menu structure M09.

0%: Valve closed


100%: Valve open

10
Operating and service manual, Controlled Atmosphere

The vacuum pump can be activated in the menu structure M10. Activating the vacuum pump should
result in a pressure drop which can be viewed in the menu structure I18.
Only manually activate the vacuum pump when absolutely necessary! The vacuum pump
is not pre-heated if manually activated - this can cause damage to the vacuum pump over
time.

CA curtain
When CA is activated a CA curtain must be installed. Ensure the CA curtain is installed in accord-
ance with the guide included with the CA curtain.

Vacuum system test


Note: BE AWARE OF HOT SURFACES - when handling the vacuum pump.
The vacuum system consists of a membrane connected with a hose to a vacuum pump. Below you
will find a step-by-step method to determine the root cause of a vacuum fault. Please be aware that
there can be more than one problem in a vacuum system, and you might need to go through the
tutorial several times to eliminate the problem.

A vacuum fault alarm can be caused by a single or a combination of the following:

1. Insufficient amount of oil in vacuum pump


2. Defective pressure transmitter
3. Defective or leakage in vacuum pump
4. Leak in fittings or connections
5. Leak in membrane

Method to determine the cause:

1. Check oil level in the vacuum pump. Refill if needed.


2. Go to menu structure M10 and turn on the vacuum pump and verify that it rotates in the right
direction. If vacuum pump does not activate, see section
“Simple trouble shooting vacuum pump / controller module” on page 12. If vacuum pump acti
vates proceed to 3.
3. Disconnect the vacuum hose at the vacuum pump and plug the vacuum pump inlet.
a. If the pressure is above 30 mBar, proceed to 4
b. A pressure below 30 mBar indicates the vacuum pump is OK, proceed with the following:
Connect the hose to the vacuum pump again and ensure the connection is tight.
4. Install a manometer at the transmitter inlet and ensure the reading is similar to the display
reading. If not, the pressure transmitter is defect. If pressure is OK, change the vacuum pump.
Go to menu structure M10 and turn on the vacuum pump.

If the vacuum fault alarm is still present - 2 options from here:

If unit is in operation with cargo: Do nothing! Either the membrane or the connection to the
membrane is leaking. It is not possible to correct this fault during operation, due to low oxygen
level inside container.

Do not enter the container - including opening the service hatches - when
oxygen level is below 20.9%.

Empty container: Disconnect the vacuum hose at the membrane and plug the hose.
Go to menu structure M10 and turn on the vacuum pump.
If readings are:
- Above 30 mBar: ”Problem surrounding the vacuum hose” on page 12
- Below 30 mBar: ”Problem located at membrane” on page 12

11
Operating and service manual, Controlled Atmosphere

Vacuum pump CA membrane

Problem area if reading above 30 mBar Problem area if reading below 30 mBar

Problem surrounding the vacuum hose

In case of a defective vacuum hose:


1. Check hose for leaks. Repair or replace.
2. After repair or replacement of the vacuum hose, perform “Container leak test” on page 12

Problem located at membrane


1. Ensure vacuum hose is connected correctly.
2. If this does not solve the problem, replace membrane.

Please note that this step by step only resolves one leak in the system, and may need to be repeat-
ed until the leak is fully terminated. See “Container leak test” on page 12

Simple trouble shooting vacuum pump / controller module


1. Check contactor coil K9.
2. Measure wirering, see wire diagram.
3. Measure bi-metallic switch (optional component). If no connection, replace switch.
4. Pull contactor K9 manually. If pump starts, replace controller module
5. Pull contactor K9 manually. If pump does not start, replace the pump.

Container leak test


A container leak test needs to be performed when:
• After replacing vacuum hose
• After replacing wiring going through the unit
• After replacing hoses and or piping going through the unit
• After replacing or opening service hatch
• After repairing structural damage on the unit and or container
• After replacing fresh air valve and or module
• When a container is suspected of leakage

12
Operating and service manual, Controlled Atmosphere

Equipment needed:
• Star Cool test damper
• Test manometer - differential pressure gauge (for instance a Dwyer Magnehelic model 2002)
• CA curtain
• Drain plugs

Method:
1. Install drain plugs
2. Install CA curtain according to instructions supplied along with the curtain
3. Install Star Cool test damper
4. Connect test manometer
5. Apply air pressure 500 Pa
6. Close air supply, and wait 12 min
7. Ensure pressure is min. 250 Pa after 12 min

Test criteria:
Pressure drop: 2” water column to 1” water column (500 Pa to 250 Pa)
Min. test time: 720 sec (12 min)
If test fails, leak must be located, repaired and test performed over again.

Oil charge and drain


Oil filter should be replaced at every oil change.
1. BE AWARE OFF HOT SURFACES.
2. Remove cover shield from vacuum pump by the 4 bolts.
3. Remove the plug for oil charge, see Vacuum pump in “Components” on page 15.
4. Charge oil while watching the sight glass - do not overcharge.
5. Fasten plug immediately after oil charge.

Replacement of vacuum pump heating element


1. Turn power off!
2. BE AWARE OFF HOT SURFACES.
3. Remove cover shield from vacuum pump by the 4 bolts. Release vacuum pump from its
socket
4. Unplug sensor cables from terminal box on top of the vacuum pump and tilt
vacuum pump to avoid oil spill when replacing the heating element.
5. Attach cables to terminal box on top of the vacuum pump according to illustration below.
6. Turn on power.

13
Operating and service manual, Controlled Atmosphere

Locations of components

14
Operating and service manual, Controlled Atmosphere

Components
CA membrane module

Pressure transmitter

CO2 sensor O2 sensor

Displayed sensors may vary from currently used models

15
Operating and service manual, Controlled Atmosphere

Vacuum pump

Terminal box

Pressure tranmitter
connection

Pump in-let

Oil in-let

Oil filter

Sight glass

Temp. sensor pocket

Heating element

Oil out-let

Tightening torques for M6 screws at vacuum pump console: 6 Nm


Tightening torques for plugs and heating element: 15 Nm

CA related alarms
Alarm list:
Id Display text Description Alarm type
1. Temperature sensor alarms
130 Tpump open Vacuum pump temperature sensor open circuit Warning
131 Tpump short Vacuum pump temperature sensor short circuit Warning
132 Tpump invalid Vacuum pump temperature sensor invalid Warning
2. Pressure sensor alarms
211 Pmem open Vacuum pump pressure transmitter open circuit Warning
212 Pmem short Vacuum pump pressure transmitter short circuit Warning
213 Pmem invalid Vacuum pump pressure transmitter invalid Warning
214 Pmem fault Pressure system fault Warning
3. Other sensor alarms
310 CO2 invalid CO2 sensor communication missing Alarm
313 O2 invalid O2 sensor communication missing Alarm
4. Power alarms
403 Mpump over heat Vacuum pump motor overheat Warning
6. Operations alarms
650 O2 low O2 sensor measures low O2 level in container Alarm
651 CO2 high CO2 sensor measures high CO2 level in container Alarm
652 Vacuum fault The pressure sensor measures high pressure in Alarm
the vacuum system
16
Operating and service manual, Controlled Atmosphere

653 Mpump temp low Vacuum pump operating temperature is low Alarm
654 Mpump temp high Motor for vacuum pump is overheated Alarm
656 Mpump service Vacuum pump needs oil change Fatal
alarm
657 Mpump wrong phase Vacuum pump operating in wrong direction Fatal
alarm
7. Communication alarms
740 CO2 sensor CO2 sensor is missing or communication lost Alarm
missing
750 CA module missing CA module is missing or communication lost Alarm
760 O2 sensor missing O2 sensor is missing or communication lost Alarm
8. Test alarms
826 Hpump current ON Heat vacuum pump too high or too low Alarm
827 Hpump current OFF Current in off position is too high Alarm
831 Pmem sensor Pmem above or below 1000 mBar (+50/-50) after Alarm
Mpump off for 300 sec
832 CO2 sensor No reading or value above 1% Alarm
833 O2 sensor No reading or value out of range Alarm
834 Mair open Readings for fresh air valve position is outside Alarm
specified range
835 Mair closed Readings for fresh air valve position is outside Alarm
specified range
836 Pmem vacuum Unable to create vacuum Alarm
837 Pmem ambient Not measuring Pmem pressure 1000 mBar Alarm
(-50/+50 mBar)
838 Mpump ON current Current failure Alarm
839 Mpump OFF current Current in off position is too high Alarm
890 PTI Tset-13 Unable to reach set point (13°C) (55°F) within 3 Alarm
hours and staying in-range for 30 min
9. Controller alarms
977 Pmem sens sup LOW Controller internal voltage reference fault Warning
978 Pmem sens sup HIGH Controller internal voltage reference fault Warning
998 Could not detect CA Unable to detect CA Warning

17
Operating and service manual, Controlled Atmosphere

Replacing the controller module

Failure scenario Replacement action

SMC6 SCC6-CA SSC6-CA Or SMC6.1


Defective

Recommended

SMC6 SSC6-CA SMC6 Or SMC6.1


Defective

Recommended

SMC6 SMC6 Or SMC6.1


Defective

Recommended

SMC6.1 SMC6.1
Defective

18
Operating and service manual, Controlled Atmosphere

Temperature sensor alarms (1XX)


130 Tpump open Warning
Description Vacuum pump temperature sensor open circuit
Cause Indication of loose connection, defective temperature sensor
Trouble Possible causes:
shooting
• Temperature sensor Tpump or its cable is defective
• Controller module is defective
Accompanied alarms:
• AL 132
Trouble shooting:
1. Disconnect the sensor cable for sensor Tpump from the connector on
the controller module, according to the wiring schematics inside in
the control cabinet
2. Measure the resistance between the two wires
a) If this resistance is more than 1.5 MΩ, the cable or the sensor is
defect, replace sensor
b) If this resistance matches the resistance and temperature in
Tables (Star Cool manual), the temperature sensor and cable are
OK
3. Measure the voltage over the connector for Tpump. It should be
between 3.2 and 3.4 V DC
a) If the voltage is within the specified range, connect sensor again.
Measure the voltage over the sensor and check voltage/
temperature according to Tables (Star Cool manual)
b) If the voltage is outside the above range, the controller module,
is defect or other sensors may be defect and pulling the voltage
down. Check other alarms and see Trouble shooting for Star
Cool Main Controller (Star Cool manual) before replacing
controller door
Criteria Value below low alarm limit -35°C (-31°F)
None
Controller
action
Log X Alarm X Alarm light Off
Consequence It is not possible to control the heating element in the vacuum pump
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Current

19
Operating and service manual, Controlled Atmosphere

131 Tpump short Warning


Description Vacuum pump temperature sensor short circuit
Cause Indication of short-circuited temperature sensor
Trouble Possible causes:
shooting
• Temperature sensor Tpump or its cable defective
• Controller module defective
Accompanied alarms:
• AL 132
Trouble shooting:
1. Disconnect the sensor cable for sensor Tpump from the connector on
the controller module, according to the wiring schematics inside in
the control cabinet.
2. Measure the resistance between the two wires.
a) If the resistance is less than (<) 230 Ω, the cable or the sensor is
defect, replace sensor
b) If the resistance matches the resistance and temperature in
Tables (Star Cool Manual), the temperature sensor and cable are
OK.
3. Measure the voltage over the connector for Tpump, it should be
between 3.2 and 3.4 V DC.
a) If the voltage is inside the above range, connect sensor again.
Measure the voltage over the sensor and check voltage/
temperature according to Tables (Star Cool Manual).
b) If the voltage is outside the above range, the controller module
is defect or other sensors may be defect and pulling the voltage
down.
Check other alarms and see Trouble shooting for Star Cool
Main Controller (Star Cool Manual) before replacing controller
door.
Criteria Value above high alarm limit +140°C (+284°F).
None
Controller
action
Log X Alarm X Alarm light Off
Consequence It is not possible to control the heating element in the vacuum pump
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Current

20
Operating and service manual, Controlled Atmosphere

132 Tpump invalid Warning


Description Vacuum pump temperature sensor invalid
Cause Indication of defective temperature sensor or its measuring circuitry
Trouble Possible causes:
shooting
• Active alarms AL 130 or AL 131
• Temperature sensor reading is out of valid range:
-35°C (-31°F) or above +130°C (266°F)
Accompanied alarms:
• AL 130 or AL 131 may also be active.
Trouble shooting:
1. Check accompanied alarms
2. Disconnect the sensor cable for sensor Tpump from the connector on
the controller module, according to the wiring schematics inside in
the control cabinet.
3. Measure the resistance between the two wires.
a) If the resistance is out of range of the resistance and temperature
table in Tables (Star Cool Manual), the temperature sensor and
cable are defect and should be replaced.
b) If the resistance is within range, perform controller door check
Trouble shooting for Star Cool Main Controller (Star Cool
Manual) before replacing controller door.
Criteria Reading below -35°C (-31°F) or above +130°C (266°F)
None
Controller
action
Log X Alarm X Alarm light Off
Consequence It is not possible to control the heating element in the vacuum pump
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and may then
be deleted. Value must be valid for 60 sec. to set alarm inactive.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive

21
Operating and service manual, Controlled Atmosphere

Pressure sensor alarms (2XX)


211 Pmem open Warning
Description Vacuum pump pressure transmitter open circuit
Cause Indication of loose connection, defective or lack of vacuum pump
pressure transmitter
Trouble Possible causes:
shooting
• See AL 212
Accompanied alarms:
• AL 213
Trouble shooting:
1. Check that the connector is mounted correctly according to wiring
schematic.
a) Check the cable (measure the resistance in the cable).
If the cable is defective, replace cable.
b) Disconnect signal wire on controller module according to wiring
schematic.
Measure voltage between dissconnected signal wire and GND on
controller module.
If voltage is above 4.7 V DC, transmitter or connection between
transmitter and cable is defective.
If not, then mount signal wire. Measure voltage between SIGNAL
and GND.
If voltage is between 0.2 V DC and 4.7 V DC and this alarm is still
active, then replace controller module.
Criteria Pmem > 1150 mBar
None
Controller
action
Log X Alarm X Alarm light Off
Consequence No consequence as to control
Elimination When transmitter value becomes valid, it is marked as inactive in the alarm list and may
then be deleted.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Present

22
Operating and service manual, Controlled Atmosphere

212 Pmem short Warning


Description Vacuum pump pressure transmitter short circuit
Cause Indication of short-circuited vacuum pump pressure transmitter
Trouble Possible causes:
shooting
• Connector for pressure transmitter Pmem not correctly mounted
• Vacuum pump pressure transmitter Pmem defective
• Cable for vacuum pump pressure transmitter Pmem defective
• Controller module defective
Accompanied alarms:
• AL 213
Trouble shooting:
1. Check that the connector is mounted correctly according to wiring
schematic.
a) Check the cable (measure the resistance in the cable).
If the cable is defective, replace cable.
b) Disconnect signal wire on controller module according to wiring
schematic.
Measure voltage between dissconnected signal wire and GND on
controller module.
If voltage is below 0.2 V DC, transmitter or connection between
transmitter and cable is defective.
If not, then mount signal wire. Measure voltage between SIGNAL
and GND.
If voltage is between 0.2 V DC and 4.7 V DC and this alarm is still
active, then replace controller module.
Criteria Pmem < 10 mBar
None
Controller
action
Log X Alarm X Alarm light Off
Consequence None
Elimination When transmitter value becomes valid, it is marked as inactive in alarm list and may
then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Present

23
Operating and service manual, Controlled Atmosphere

213 Pmem invalid Warning


Description Vacuum pump pressure transmitter invalid
Cause Indication of defective Vacuum pump pressure Transmitter or its
measuring circuitry
Trouble Possible causes:
shooting
• See AL 212
Accompanied alarms:
• AL 211 or AL 212 may also be active
Trouble shooting:
1. Check that the connector is mounted correctly according to the
drawing.
a) Check the cable (measure the resistance in the cable).
If the cable is defective, replace cable.
b) Disconnect signal wire on controller module according to wiring
schematic.
Measure voltage between signal wire and GND on controller
module according to wiring schematic.
If voltage is below 0.2 V DC, transmitter or connection between
transmitter and cable is defective.
If not, then mount signal wire. Measure voltage between SIGNAL
and GND
If voltage is between 0.2 V DC and 4.7 V DC and this alarm is still
active, then replace controller module.
Criteria Pmem out of range for more than 30 sec
Replacement by new value from AAS system
Controller
action
Log X Alarm X Alarm light Off
Consequence None
Elimination When transmitter value becomes valid, it becomes marked as inactive in alarm list may
then be detected. Value must be valid for 60 sec. to set alarm inactive.
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive

24
Operating and service manual, Controlled Atmosphere

214 Pmem fault Warning


Description Pressure system fault
Cause Pressure <10 mBar or >1150 mBar
Trouble Possible causes:
shooting
• See AL 212
Accompanied alarms:
• AL 213 may be active
Trouble shooting:
1. See AL 212
Criteria 10 mBar or > Pmem > 1150 mBar
None
Controller
action
Log X Alarm X Alarm light Off
Consequence None
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Low limit High limit Act 0

25
Operating and service manual, Controlled Atmosphere

Other sensor alarms (3XX)


310 CO2 invalid Alarm
Description CO2 sensor communication missing
Cause Indication of defective CO2 sensor, or lack of or improper connection
Trouble Possible causes:
shooting
• Communication with CO2 sensor
• Defective CO2 sensor
• COMRH cable, RH-cable and or COMCA cable is defective
• Controller module is defective
Accompanied alarms:
• AL 740
Trouble shooting:
1. Verify that cable CO2-com is mounted correctly (and is not damaged)
according to wiring diagram inside the controller cabinet.
2. Verify that there are correct voltages 12 V DC between 1 and 4 on
X10.
3. Measure with a multimeter that there is a small DC signal between 2
and 3 on X10.
a) If there is signal: The CO2 sensor is defective and must be
replaced.
b) If there is no signal: The controller module is defective and must
be replaced.
Criteria Communication with CO2 sensor not possible
Run pump 40%
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence CO2 level can not be regulated
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive

26
Operating and service manual, Controlled Atmosphere

313 O2 invalid Alarm


Description O2 sensor communication missing
Cause Indication of defective O2 sensor, or lack of or improper connection
Trouble Possible causes:
shooting
• Communication with O2 sensor
• COMRH cable, RH-cable and or COMCA cable is defective
• Defective O2 sensor
• Controller module is defective
Accompanied alarms:
• AL 310, AL 302 and or AL 760, (See service manual).
Trouble shooting:
1. Verify that cable O2-com is mounted correctly (and is not damaged)
according to wiring diagram inside the controller cabinet.
2. Verify that plugs are properly connected.
3. Verify that there are correct voltages 12 V DC between 1 and 4 on
X10.
a) If there is signal: The O2 sensor is defective and must be
replaced.
b) If there is no signal: The controller module is defective and must
be replaced.
Criteria Communication with O2 sensor not possible
Open airex 4%
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence O2 level can not be regulated
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive

27
Operating and service manual, Controlled Atmosphere

Power alarms (4XX)


403 Mpump over heat Warning
Description Vacuum pump motor overheat
Cause Indication of an overheated motor or a loose thermistor cable connection
Trouble Possible causes:
shooting
• Vacuum pump motor defective.
• Cable for measuring vacuum pump motor overheat defect.
• Controller module defective.
Accompanied alarms:
• N/A.
Trouble shooting:
1. Turn off unit!
Take of the fan cover for the vacuum pump, see if the fan can easily
turn freely by finger. If not, perform oil check. See trouble shooting
AL 656. If the motor is hot, it may be overloaded and jammed or
defect.
2. If the cable for MpumpOH by inspection is defect, replace cable.
3. Disconnect the cable for MpumpOH from the controller module
according to the wiring schematics.
4. Measure the resistance in the cable.
If the resistance is more than 1 MΩ, the cable or the motor is defect
and should be replaced.
If the resistance is less than (<) 5 kΩ, the cable and motor should be
OK.
5. Turn unit on again.
Measure the voltage over the connector for MpumpOH. It should be
between 4.80 V DC and 5.05 V DC.
a) If the voltage is inside the above range, connect sensor again.
Measure the voltage over the sensor and check the voltage.
If the voltage is less than (<) 2.5 V DC, the measurement is OK.
If the alarm after 30 sec. is still active on the display, the
controller module is defect - replace controller module.
b) If the voltage is outside the range, controller module is defect or
another error might affect the voltage. Check other alarms before
replacing controller module.
Criteria Value above high alarm limit 10k Ohm
Vacuum pump is stopped until alarm is removed
Controller
action
Log X Alarm X Alarm light Off
Consequence Extraction of CO2 is stopped
Elimination When overheating stops, alarm will be marked as inactive in alarm list and may then be
deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive High limit Present

28
Operating and service manual, Controlled Atmosphere

Operation alarms (6XX)


650 O2 low Alarm
Description O2 sensor measures low O2 level in container
Cause The system is not able to vent fresh air into the container
Trouble Possible causes:
shooting
• Lack of oil in the vacuum pump
• Automatic Fresh air defect
• O2 sensor defect
Trouble shooting:
1. See if automatic Air Exchange valves are open. If not, try to open in
manual mode
2. See if vacuum pump is running.
a) If the pump is running it will in time make sure there is enough
O2 in the box. Open the damper to accelerate this, open it until
O2 level is higher than O2 set point.
Criteria O2 level < O2 set point – 0.3 * O2 set point
Run pump 40%
Controller
action
Log X Alarm X Alarm light X
Consequence If not flushed with O2 cargo might experience anaerobic respiration and thereby
deteriorate
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Limit Act Set point

29
Operating and service manual, Controlled Atmosphere

651 CO2 high Alarm


Description CO2 sensor measures high CO2 level in container
Cause The system is not able to extract the CO2 through the membrane
Trouble Possible causes:
shooting
• Lack of oil in the vacuum pump
• Vacuum pump is not running or defective
• Membrane is defective
• CO2 sensor defective

Trouble shooting:
1. The vacuum pump is not running.
a) Check if the bi-metallic switch is connected according to the wire
schematic X78 (depending on model).
b) Push the contactor in the control cabinet, if the pump is then
activated replace controller module. If the pump is not running
when pushing the contactor, replace vacuum pump.
2. The vacuum pump is running.
a) Check oil level in vacuum pump.
b) Read out the pump pressure I18 if > 200 mbar the vacuum
system has a leak. Check entire system for air leaks. If no air
leaks is found the pump might be defect. See ”Vacuum system
test” on page 11
b) Read out the pump pressure I18 if < 200 mBar the membrane is
defect. Replace membrane.
Criteria CO2 level > CO2 set point + 0.5 * CO2 set point (and rising)
Run pump 100%
Controller
action
Log X Alarm X Alarm light X
Consequence If not CO2 is removed from the container, this will cause damage to the cargo
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Limit Act Set point

30
Operating and service manual, Controlled Atmosphere

652 Vacuum fault Alarm


Description Vacuum pump unable to reach required pressure
Cause The vacuum system might have a leak or the pressure sensor is defect
Trouble Possible causes:
shooting
• Lack of oil
• Leak in vacuum system or membrane
• Defective pressure sensor
• Vacuum pump is defective
Accompanied alarms:
• AL 403
Trouble shooting:
1. If AL 403 is active, see trouble shooting for AL 403.
If AL 652 does not turn inactive, proceed with 2.
2. The vacuum pump is not running.
a) Check if the bi-metallic switch is connected according to the wire
schematic X78 (depending on model)
b) Pushing the contactor in the control cabinet, if the pump is then
activated replace controller module. If the pump is not running
when pushing the contactor, check contactor and vacuum pump.
3. The vacuum pump is running.
a) Perform “Vacuum system test” on page 11
Criteria Pump on > 5 min AND Pmem > 135 mBar in 15 min, and CO2act > CO2set + 2%
None
Controller
action
Log X Alarm X Alarm light X
Consequence If the system can not achieve low pressure, the membrane does not work and therefore
not able to extract CO2 from the container
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data Limit Act Pump on
time

31
Operating and service manual, Controlled Atmosphere

653 Mpump heat element Alarm


Description Vacuum pump operating temperature is low
Cause The ambient temperature can be low and thereby difficult for the heating
element and vacuum pump to heat up. It could also be a defective
heating element
Trouble Possible causes:
shooting
• Defective temperature sensor Tpump
• Defective heating element
• Defective contactor K9
Trouble shooting:
1. Check contactor
2. Ensure that Tpump is correctly mounted and inserted completely in
the sensor pocket.
3. Defective heating element.
a) At the contactor measure the heating element, there should be
approx 0.9 kΩ. If not replace heating element.
Criteria Heating pump on for 50 minutes; Tpump < Tamb + 5°C
None
Controller
action
Log X Alarm X Alarm light X
Consequence Condensation of water vapor in the pump housing
Elimination When sensor value becomes valid, it is marked as inactive in the alarm list and
may then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data Limit Act Pump on
time

32
Operating and service manual, Controlled Atmosphere

654 Mpump temp high Alarm


Description Motor for vacuum pump is overheated
Cause Indication of an overheated motor, this can be caused by very high
ambient temperature or a defective pump
Trouble Possible causes:
shooting
• Vacuum pump motor is overheated
• Vacuum pump is defective or jammed
Accompanied alarms:
• N/A
Trouble shooting:
1. Check if the fan for the vacuum pump can turn freely.
If it cannot turn, remove any obstacle
2. Check that the vacuum housing is not blocked.
3. Check that the oil level in the pump is correct.
4. Check that heating element is turned off, and check heater contactor.
5. Check that the temperature sensor Tpump is installed correctly.
6. If none of the above solves the problem, and the pump seems to be
more than 115°C (239°F) - replace vacuum pump.
Criteria Tpump > 115°C (239°F)
Stop vacuum pump
Controller
action
Log X Alarm X Alarm light Off
Consequence The CA system will not be able to remove CO2 from the container
Elimination AL 654 will become invalid when temperature decreases
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive High limit Act

33
Operating and service manual, Controlled Atmosphere

656 Mpump service Fatal


alarm
Description Vacuum pump needs oil change
Cause Pump runtime > 2000 h
Trouble Possible causes:
shooting
• Pump runtime > 2000 h
Accompanied alarms:
• None
Trouble shooting:
1. Replace vacuum pump oil and filter. Filling 0.35 L.
2. Run vacuum pump in 6 min. (manually).
3. Check if oil is clean - if not, replace oil again and go to 2).
4. When oil is still clean after running in 6 minutes, press the alarm for
10 sec, then the alarm will become inactive.
5. Press again to delete service alarm.
Criteria Pump runtime > 2000 h
None
Controller
action
Log X Alarm X Alarm light Quick
Consequence Unit can not pass PTI.
Not performing oil-change every 2000 pump hours will decrease pump-lifetime
dramatically
Elimination When alarm becomes inactive, it can be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Limit Act

34
Operating and service manual, Controlled Atmosphere

657 Mpump wrong phase Fatal


alarm
Description Vacuum pump operating in wrong direction
Cause Pump ON > 7 sec and Pmem > 600 mBar
Trouble Possible causes:
shooting
• Wrong phase direction
• Pressure tansmitter defective
• Vacuum hose leak
• Leaks in the vacuum system
• Contactor defective
• Supply voltage to pump defective
Accompanied alarms:
• AL 213, AL 214 and AL 998
Trouble shooting:
1. Check contactor K10
2. Check pump connection according to wire schematic
3. See “Vacuum system test” on page 11
4. Check pressure transmitter Pmem
Criteria Pump ON > 7 sec and Pmem > 600 mBar
None
Controller
action
Log X Alarm X Alarm light Quick
Consequence Vacuum pump stop and CA non functionable
Elimination When alarm becomes inactive, it can be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data Limit Act Pump on CO2
time

35
Operating and service manual, Controlled Atmosphere

Communication alarms (7XX)


740 CO2 sensor missing Alarm
Description CO2 sensor is missing or communication lost
Cause None or bad communication with CO2 sensor
Trouble Possible causes:
shooting
• Communication to CO2 sensor lost
• CO2 sensor missing
• CO2 sensor defect
• COMRH cable, RH-cable and or COMCA are defective
• Main controller defective
Accompanied alarms:
• AL 302, AL 730, AL 750, AL 751 and AL 760 may accompany this
alarm
Trouble shooting:
1. Verify that cable CO2-com is mounted correctly (and is not damaged)
according to wiring diagram inside the controller cabinet.
2. Verify that there are correct voltages 12 V DC between 1 and 4 on
X10.
3. Measure with a multimeter that there is a small DC signal between 2
and 3 on X10.
a) If there is signal: The CO2 sensor is defective and must be
replaced.
b) If there is no signal: The controller module is defective and must
be replaced.
Criteria No communication for 2 min.
None
Controller
action
Log X Alarm X Alarm light X
Consequence Not possible to run CA
Elimination Alarm may be deleted when inactive
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
0 0 0 Err code

36
Operating and service manual, Controlled Atmosphere

750 CA module missing Alarm


Description CA module is missing or communication is missing
Cause CA module sensor is missing or communication lost
Trouble Possible causes:
shooting
• CA module missing
• Communication to CA module lost
• CA module defective
Accompanied alarms:
• AL 302, AL 730, AL 740 and AL 760 may accompany this alarm
Trouble shooting:
1. If one or more alarms are active, check wires, plugs and connectors.
2. Check voltage supply according to wire schematic.
3. If only AL 750 active, then check connection to CA module and
correct if faulty. If no change, then replace CA module.
Criteria No communication for 2 min.
None
Controller
action
Log X Alarm X Alarm light X
Consequence Not possible to run CA
Elimination
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
0 0 0 Err code

37
Operating and service manual, Controlled Atmosphere

760 O2 sensor missing Alarm


Description O2 sensor is missing or communication lost
Cause None or faulty communication with O2 sensor
Trouble Possible causes:
shooting
• Communication to O2 sensor missing
• Defective O2 sensor
• COMRH cable, RH-cable and or COMCA cable is defective
• Controller module defective
Accompanied alarms:
• AL 313, AL 730 and AL 740 may also be active
Trouble shooting:
1. If one or more alarms are active, check wires, plugs and connectors.
2. Check voltage according to wire diagram.
3. If only AL 760 active, then check connection to O2 sensor and correct
if faulty. If no change, then replace CA module.
Criteria No communication for 2 min.
None
Controller
action
Log X Alarm X Alarm light X
Consequence Not possible to run CA
Elimination Alarm may be deleted when inactive
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
0 0 0 Err code

38
Operating and service manual, Controlled Atmosphere

Test alarms (8XX)


826 Hpump current ON Alarm
Description Heat vacuum pump too high or too low
Cause Measured current is too high or too low when heater is turned on
Trouble Possible causes:
shooting
• Defective cables
• Defective heating element
• Defective controller module
• Defective power meas
Accompanied alarms:
• N/A
Trouble shooting:
1. Check connection according to wiring schematic.
2. Defective heating element, see AL 653.
3. Check supply [Amp] reading and compare with display reading.
If reading approx. 10 times normal value, replace controller module
Criteria Current < Imin = 0,5*(U/973,2) or current > Imax = 1,5*(U/973,2).
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID ILimit I1 I2 I3

39
Operating and service manual, Controlled Atmosphere

827 Hpump current OFF Alarm


Description Current in off position is too high
Cause Measured current is too high when heater is turned off
Trouble Possible causes:
shooting
• Mheat controller defective
• Defective controller module
• Defective contactor
Accompanied alarms:
• AL 800, AL 812, AL 817, AL 821 and AL 828 may also be active.
Trouble shooting:
1. If no accompanied alarms, check contactor K10.
Criteria 0.5 Amp if off
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID I limit I1 I2 I3

831 Pmem sensor Alarm


Description Pmem above or below 1000 mBar (+50/-50) after Mpump off for 300 sec
Cause Measure or hardware error
Trouble Possible causes:
shooting
• Pmem defective
Accompanied alarms:
• AL 211, AL 212, and AL 213 may also be active
• AL 214
Trouble shooting:
1. See trouble shooting for accompanied alarms AL 211 and AL 212
Criteria Reading out of range. 950 mBar < normal < 1050 mBar
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Airex motor Pmem CO2 O2

40
Operating and service manual, Controlled Atmosphere

832 CO2 sensor Alarm


Description No reading or value above 1%
Cause No communication or defective cable or sensor
Trouble Possible causes:
shooting
• See AL 740
Accompanied alarms:
• AL 740
Trouble shooting:
1. See trouble shooting for AL 740.
Criteria Reading out of range. Normal range 0-1% CO2
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Airex motor Pmem CO2 O2

833 O2 sensor Alarm


Description No reading or value is out of range
Cause No communication or defective cable or sensor
Trouble Possible causes:
shooting
• See AL 760
Accompanied alarms:
• AL 760
Trouble shooting:
1. See trouble shooting for AL 760.
Criteria Reading out of range. Normal 19-22 % O2
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Airex motor Pmem CO2 O2

41
Operating and service manual, Controlled Atmosphere

834 Mair open Alarm


Description Readings for fresh air valve position is outside specified range
Cause Current too high
Trouble Possible causes:
shooting
• Damaged or blocked airex module
Trouble shooting:
1. Check fresh air module and valves for damages.
2. If valves are open, check connections according to wiring schematic.
3. Disconnect SIGNAL wire at X23 and measure voltage between GND
and disconnected SIGNAL wire. If below 1.15 V DC replace controller.
4. Mount SIGNAL wire and test Mair in manual mode, open/close.
The value measured should be above 4.15 V DC when closed and
below 1.15 V DC when open. If not, replace controller.
Criteria Motor potentiometer open 10 - 35 %
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Airex motor Pmem CO2 O2

835 Mair closed Alarm


Description Readings for fresh air valve position is outside specified range
Cause Current too high
Trouble Possible causes:
shooting
• Damaged or blocked airex module
Trouble shooting:
1. Check fresh air module and valves for damages.
2. If valves are open, check connections according to wiring schematic.
3. Disconnect SIGNAL wire at X23 and measure voltage between GND
and disconnected SIGNAL wire. If above 4.15 V DC replace controller.
4. Mount SIGNAL wire and test Mair in manual mode, open/close.
The value measured should be above 4.15 V DC when closed and
below 1.15 V DC when open. If not, replace controller.
Criteria Motor potentiometer closed 70 - 95 %
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Airex motor Pmem CO2 O2

42
Operating and service manual, Controlled Atmosphere

836 Pmem vacuum Alarm


Description Unable to create vacuum
Cause Leakage or low performance vacuum pump
Trouble Possible causes:
shooting
• Lack of oil in the vacuum pump
• Pump not running
• Leakage involving membrane, hose and or connections
• Low performance from vacuum pump
Accompanied alarms:
• AL 403, AL 652, AL 654, AL 656 and or AL 838
Trouble shooting:
1. Check if pump is running, if not, see accompanied alarms for trouble
shooting first.
2. The vacuum pump is not running.
a) Check if the bi-metallic switch is connected according to the wire
schematic X78 (depending on model)
b) Pushing the contactor in the control cabinet, if the pump is then
activated replace controller module. If the pump is not running
when pushing the contactor, check contactor and vacuum pump.
3. The vacuum pump is running.
a) Perform “Vacuum system test” on page 11
Criteria Unable to reach 20 mBar < Pmem < 130 mBar
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Tpump Pmem CO2 O2

43
Operating and service manual, Controlled Atmosphere

837 Pmem ambient Alarm


Description Not measuring Pmem pressure 1000 mBar (-50/+50 mBar)
Cause Actual pressure measurement out of range
Trouble Possible causes:
shooting
• Pmem defective
Accompanied alarms:
• AL 211, AL 212 and or AL 213
Trouble shooting:
1. See trouble shooting for accompanied alarms.
Criteria Unable to reach Pmem. 950 mBar < Pmem < 1050 mBar
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Tpump Pmem CO2 O2

838 Mpump ON current Alarm


Description Current failure
Cause Uses less or more current than specified
Trouble Possible causes:
shooting
• Bad power connection or supply
• Jammed or damaged vacuum pump
• Low performance from vacuum pump due to lack of oil
Accompanied alarms:
• AL 654, AL 656 and or AL 836
Trouble shooting:
1. Check oil level.
2. Run pump manually and observe current.
If current outside range 0.9 - 1.3 Amp, replace vacuum pump.
Criteria Vacuum pump current is outside its limit 0.9 - 1.3 Amp
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Ilimit I1 I2 I3

44
Operating and service manual, Controlled Atmosphere

839 Mpump OFF current Alarm


Description Current in off position is too high
Cause Measured current is too high when vacuum pump is turned off
Trouble Possible causes:
shooting
• Mpump contactor K9 defective
• Defective controller module.
Accompanied alarms:
• AL 800, AL 812, AL 817, AL 821 and AL 828 may also be active
Trouble shooting:
1. If no accompanied alarms, check contactor K9. If K9 is defective,
replace.
Criteria Less than 0.5 Amp
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Step ID Ilimit I1 I2 I3

45
Operating and service manual, Controlled Atmosphere

890 PTI Tset 13 Alarm


Description PTI 13°C Set Fault
Cause Indication of insufficient performance
Trouble Possible causes:
shooting
• Doors are open.
• There may not be enough refrigerant in the unit.
• The heaters do not operate correctly.
Accompanied alarms:
• N/A.
Trouble shooting:
1) Verify that the doors are closed.
2) If start temperature was below +5°C, the heaters may be defective.
Start the heaters in manual mode and see if the current consumption
is higher than 5 A each phase.
3) The unit may be lacking refrigerant. Check if the small red balls in the
sight glass in the receiver (receiver tank) are not at the bottom when
the unit is turned off.
Search for leaks, repair and charge the unit.
Criteria Set-point +13°C was not reached within the 3 hour limit
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Test failed
Elimination Alarm may then be deleted after test completed
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Active/Inactive Tset Tact Tevap Tret

46
Operating and service manual, Controlled Atmosphere

Controller alarms (9XX)


977 Pmem sens sup LOW Warning
Description Controller Internal Voltage Reference Fault
Cause Sensor voltage supply < 4.50 V
Trouble Possible causes:
shooting
• Controller defective
Accompanied alarms:
• AL 211, AL 212, AL 213 and or AL 214
Trouble shooting:
1) See Trouble shooting for accompanied alarms
Criteria Voltage < 4.50 V DC
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Less accurate readings from measurement
Elimination Alarm will be marked as inactive in alarm list when supply voltage is correct. Alarm may
then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Low High Act 0

47
Operating and service manual, Controlled Atmosphere

978 Pmem sens sup HIGH Warning


Description Controller Internal Voltage Reference Fault
Cause Sensor voltage supply > 5.50 V
Trouble Possible causes:
shooting
• Defective power supply for main controller
• Defective Pmem pressure transmitter
• Defective main controller
Accompanied alarms:
• AL 213 and or AL 214
Trouble shooting:
1) See Trouble shooting for accompanied alarms
Criteria Voltage > 5.50 V DC
None
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Less accurate readings from measurement
Elimination Alarm will be marked as inactive in alarm list when supply voltage is correct. Alarm may
then be deleted
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5
Log data
Low High Act 0

998 Could not detect CA Warning


Description Uanble to detect CA
Cause Broken communication
Trouble Possible causes:
shooting
• COMCA cable defective (for some models)
• Heating element defective
• Contactors defective K10
• Controler module defective
Accompanied alarms:
• AL 653, AL 740 and or AL 760
Trouble shooting:
1) Check connections according to wire schematic
2) Turn unit off on
3) See Trouble shooting for AL 653
Criteria Could not detect CA module in time
Cannot run CA mode
Controller
action
Log X Alarm X Alarm light Slow flash
Consequence Can not pass CA PTI
Elimination Alarm may be deleted after test complete
Parm 1 Parm 2 Parm 3 Parm 4 Parm 5

Log data CA mode CA Idle Hpump on current sum


communi- current
cation sum

48
Operating and service manual, Controlled Atmosphere

Controller overview

Displayed overview may vary depending on model

49
Operating and service manual, Controlled Atmosphere

Tables
Vcc = 5V
Voltage [V] Pressure [Bar] Pressure [PsiA] Voltage [V] Pressure [Bar] Pressure [PsiA]
0* 0.009 0.13 2.55 0.598 8.67

0.05* 0.021 0.30 2.6 0.610 8.84

0.1* 0.032 0.47 2.65 0.621 9.01

0.15* 0.044 0.63 2.7 0.633 9.18

0.2* 0.055 0.80 2.75 0.644 9.34

0.25* 0.067 0.97 2.8 0.656 9.51

0.3* 0.078 1.14 2.85 0.667 9.68

0.35* 0.090 1.30 2.9 0.679 9.85

0.4* 0.101 1.47 2.95 0.690 10.01

0.45* 0.113 1.64 3 0.702 10.18

0.5 0.125 1.81 3.05 0.714 10.35

0.55 0.136 1.97 3.1 0.725 10.52

0.6 0.148 2.14 3.15 0.737 10.68

0.65 0.159 2.31 3.2 0.748 10.85

0.7 0.171 2.48 3.25 0.760 11.02

0.75 0.182 2.64 3.3 0.771 11.19

0.8 0.194 2.81 3.35 0.783 11.35

0.85 0.205 2.98 3.4 0.794 11.52

0.9 0.217 3.15 3.45 0.806 11.69

0.95 0.228 3.31 3.5 0.818 11.86

1 0.240 3.48 3.55 0.829 12.02

1.05 0.252 3.65 3.6 0.841 12.19

1.1 0.263 3.82 3.65 0.852 12.36

1.15 0.275 3.98 3.7 0.864 12.53

1.2 0.286 4.15 3.75 0.875 12.69

1.25 0.298 4.32 3.8 0.887 12.86

1.3 0.309 4.49 3.85 0.898 13.03

1.35 0.321 4.65 3.9 0.910 13.20

1.4 0.332 4.82 3.95 0.921 13.36

1.45 0.344 4.99 4 0.933 13.53

1.5 0.356 5.16 4.05 0.945 13.70

1.55 0.367 5.32 4.1 0.956 13.87

1.6 0.379 5.49 4.15 0.968 14.03

1.65 0.390 5.66 4.2 0.979 14.20

1.7 0.402 5.83 4.25 0.991 14.37

1.75 0.413 5.99 4.3 1.002 14.54

1.8 0.425 6.16 4.35 1.014 14.70

1.85 0.436 6.33 4.4 1.025 14.87

1.9 0.448 6.50 4.45 1.037 15.04

1.95 0.459 6.66 4.5 1.049 15.21

2 0.471 6.83 4.55* 1.060 15.37

2.05 0.483 7.00 4.6* 1.072 15.54

2.1 0.494 7.17 4.65* 1.083 15.71

2.15 0.506 7.33 4.7* 1.095 15.88

2.2 0.517 7.50 4.75* 1.106 16.04

2.25 0.529 7.67 4.8* 1.118 16.21

2.3 0.540 7.84 4.85* 1.129 16.38

2.35 0.552 8.00 4.9* 1.141 16.55

2.4 0.563 8.17 4.95* 1.152 16.71

2.45 0.575 8.34 5* 1.164 16.88

2.5 0.587 8.51

* Range with non-reliable readings

50
Operating and service manual, Controlled Atmosphere

51
Operating and service manual, Controlled Atmosphere

52
QS1 K1
1 1 Mcpr
Brown L1 L1 2 1
POWER IN 2 Overcurrent 1 L1
3 2 FC-PWR 2 1 U
Blue or Grey L2 AWG 14 L2 4 L2 2 V
4 and Main 3 3 1
5 3 4x L3 1 3 W
4x Black L3 L3 6 AWG12 2 2
6 switch 5 Y/GR
Y/GR FC 3 1 Z M
2.5mm2 Y/GR 3 2 X
4 3 Y
Outside
X100 5

AWG 14
K8 A
1
Controller Box 1 CL1 FC-com B
F1 L1 L1 L1 2 2
Inside Controller Box 3
L1 3 CL2
TR1
2
0,4A 1 L2 L2 L2 L2 4 GND
4
L2 5 CL3
L3 L3 L3 6
L3

Inside Controller Box


Outside Controller Box
F2 INTER-
LOCK
TR2 L3 Hevap
2 0,4A 1

AWG 16
K2
X41 X40 1 CL2 Hevap5-6A Hevap5-6A
12V L1 L1 2
1 1 Hevap6-6B Hevap6-6B
COM A 3 CL1
2 L2 L2 4 Hevap1-1A Hevap1-1A
T1 B 2
3 5 CL3 Hevap2-1B Hevap2-1B
Trafo SW1 GND L3 L3 6
4 3

SPM6
POWERMEAS
MODULE
1
On/Off Hevap1-2A Hevap1-2A
2
TR3 [Red] switch Hevap2-2B Hevap2-2B
Overall wiring schematic

3 Hevap
TR4 K3 Hevap3-3A Hevap3-3A
4

AWG 14
TR5 [Red] [Red] 1 Hevap4-3B 13x Hevap4-3B
5 X50 (J5) L1 2 AWG18
[White] (GND)
6 RMM 0VAC 1 0VAC 3
Y/GR L2 4 Hevap3-4A Hevap3-4A
2
RMM 24VAC 3 24VAC 5 Hevap4-4B Hevap4-4B
TRAFO T1 L3 6
Hevap5-5A Hevap5-5A
Approx voltages Hevap6-5B Hevap6-5B
X51 (J3) X52 (J1)

53
Terminal 1-2 : 440V AC GND 1 Y/GR Y/GR Y/GR
1
Operating and service manual, Controlled Atmosphere

Terminal 3-4 : 27V AC GND


Terminal 5-6 : 24V AC 2 2
RMM-com 3 3 L3 FC-com

[Red]
[Red]
Inside Controller Box 4 4
L2
Controller Hatch
TX 5 5
RX K4
RX 6 6
TX 1 1

TR4
TR3S
L1 CL1 2
7 7

RMM - York
Powerline
modem
X80 ON 3 2
/ON 5 CL2 4 Mcond
GND
GND 4 5 3
B CL3 6 1 1
/B 3 COM RMM-com 1 2 2
A
Inside Controller Box
Outside Controller Box

SUP6
USER
PANEL
A 2 COM INTER- 1 2 3 3
12V 12V LOCK 3
1
TR3S 4 4 4
KEYPAD K5B 5 Mcond 5 5 M
TR4 6 6 6
27 3 9x
28 7
AWG 16

10 37 5 8 AWG18 7 7
38 Y/GR 8 8
Y/GR
KEYPAD X26 X27 K5
Mevap2 - 8 Tpump 1 4
4 GND GND 4 CL1 2
Mevap2 - 7 Tpump
Controller Hatch 3 SIGNAL SIGNAL 3 3 5
Mevap1 - 8 Mcond - 8 CL2 4
Inside Controller Box 2 GND GND 2
Mevap1 - 7 1 SIGNAL 1 Mcond - 7 5 6
SIGNAL CL3 6
Outside Controller Box
X24 X25 Mcond - 7
Tret Mcond - 8 Mevap 1
Tret 10 GND GND 10 Tevap
Tevap 1 1
2 9 SIGNAL SIGNAL 9 1 2 2
B B 2
Cargo 1 Tcargo 8 GND GND 8 Tsuc K6 2 3 3
A A 1 Tsuc 3
7 SIGNAL SIGNAL 7 1 1
2 2 CL1 2 4 4 4
B B Tusda3 6 GND GND 6 Tamb 5 Mevap1 5 5 M
USDA3 1 1 Tamb 3 2
A A 5 SIGNAL SIGNAL 5 CL2 4 6 6 6
2 7 9x
2 Tusda2 4 GND GND 4 Tsup2 5 3
B B 1 Tsup2 CL3 6 8 AWG18 7 7
USDA2 1 3 SIGNAL SIGNAL 3 Y/GR 8 8
A A 2
Tusda1 2 GND GND 2 Tsup1 INTER- 1 Y/GR
2 1 Tsup1
B B 1 SIGNAL SIGNAL 1 LOCK
USDA1 1
A A K7B
Inside Controller Box

X22 X23 Mevap 2


Outside Controller Box

GND 1 27 3
6 GND GND 6 28
Pdis SIG 2 MotorPos 1 1
AWG 16

Pdis P 5 SIGNAL SIGNAL 5 37 5 1 2 2


5V 3 38 2 3 3
4 +5V +5V 4
GND GND 3
3 GND GND 3
Psuc SIG SIG AirEx K7 4 4 4
Psuc P 2 SIGNAL SIGNAL 2 Air AirEx 5 Mevap2 5 5 M
5V 5V 1 4 6 6 6
1 +5V +5V 1 CL1 2
7 9x
AirMotor 3 5 8 AWG18 7 7
X20 X21 CL2 4
MotorPos 5 Y/GR 8 8
2 /PWR GND 2 5 6
M 4 CL3 6 Y/GR
1 PWR GND 1
Mevap2 - 7
X18 X19 Mevap2 - 8
6 GND GND GND Vhg
6 Mevap1 - 7
1 V Vhg
5 PWR PWR 5 Mevap1 - 8
A2 GND Vexp
K8 - 4 GND GND 4
A1 [Blue] K8 1 V Vexp K9
CCW 3 PWR PWR 3
A2 GND Veco 1 1
K7 - 2 GND GND 2 CL1 2
A1 [Blue] K7 1 V Veco
Mevap Hi 1 PWR PWR 1 3 2 Mpump
K-GND K-GND CL2 4
X16 X17 7 7
5 3
Inside Controller Box
Outside Controller Box

A2 K-GND K-GND A2 CL3 6 1 8 8


K3 - 6 GND GND 6 K6 -
A1 [Blue] K3 K6 [Blue] A1 2
Hevap 5 PWR PWR 5 Mevap Lo 3 1 1
A2 A2 4 2 2 M
K2 - 4 GND GND 4 K5 -
A1 [Blue] K2 K5 [Blue] A1 5 Mpump 3 3
CW 3 PWR PWR 3 Mcond Hi K10
A2 A2 4 4
Inside Controller Box

2 GND GND 2 9x
Outside Controller Box

K1 - K4 - 1 4 7 5 5
FC A1 [Blue] K1 K4 [Blue] A1 Mcond Lo CL1 2 8 AWG18 H
1 PWR PWR 1
3 5
Inside Controller Box

Y/GR
Outside Controller Box

CL2 4
X14 X15 Y/GR
Shp-1 5
2 GND SIGNAL 2 CL3 6
1 SIGNAL SIGNAL 1 Shp-2 Hpump
Mpump - 7
Mpump - 8
X12 X13
High pressure
switch
(Normally closed)
X10 X11
ON
/ON /ON
GND GND GND GND K10 -
COMCA B
/B /B
B COM Mheat X78 X79
A2 K-GND
A A 4 GND GND 4
A A A1 [Blue] K10
12V 12V 3 PWR PWR 3
12V 12V A2
COMCA 2 GND GND 2
A1 [Blue] K9 PWR
X8 X9 1 PWR 1
GND 3 K9 -
GND GND 3 GND Mpump
FC-com B TX RMM-com X76 X77
2 /B TXD 2 Mpump - 8 3 GND GND 3 GND
A 1 A RXD 1 RX Mpump - 7 Pmem
FC-com 2 SIGNAL SIGNAL 2 SIG P Pmem
5V
X6 X7 1 n.c. +5V 1
GND 3 COMCA
GND GND 3 GND
E LM Front TX TX LM Cargo X74 X75
RS232 2 TXD TXD 2 GND
Retriever D RX 1 RX 4 GND GND 4
C GND RXD RXD 1 B
plug in LM Cargo 3 /B /B 3 B
B TX A A
container A RX X4 X5 2 A A 2
4 GND Inside Controller Box 12V 1 12V 12V 1 COMRH
3 DDP Outside Controller Box
Outside Controller Box X72 X73
2 DDM RH
Inside Controller Box 2 GND GND 2 GND
1 VBUS 4 4
SEN- 3
4 4
3
1 12V 12V 1 12V
X2 X3 3 3
RS232 E BT1 SOR 2 2 2 2 X71
[Black] 1 1
Retriever D 2 GND GND 2 1 1 TR3S
C GND [Red] 1 AC-IN
plug inside LM Front 1 RX-TX 12V 1 TR4
B TX 2 AC-IN
Ctrl Box A RX + CO2
X1
SSC6-CA
SUB CONTROLLER CA

TR3S
1 AC-IN 12V NiMH SEN- 4 4 4 4 X70
3 3 [Y/GR]
TR4 Rechargeable 3 3 GND
2 AC-IN SOR 2 2
battery 2 2
1 1 1 1
SMC6
MAIN CONTROLLER

X0
[Y/GR] GND
O2 5 5
SEN- 4 4 2 GND SCC6-CA 8851560201
4 4 4 4
3 3 3 3 4 B
SOR 2 2 RH RH 3 3 COMRH
2 2 3 A Overall Wiring Schematic
1 1 1 1 2 2
1
1 1 12V
Outside Controller Box Lodam electronics a/s
Inside Controller Box P/N: 5251561800 Rev: 1.20
QS1 K1
1 1 Mcpr
Brown L1 L1 2 1
POWER IN 2 Overcurrent1 L1
3 2 FC-PWR 2 1 U
Blue or Grey L2 AWG 14 L2 4 L2 2 V
4 and Main 3 3 1
5 3 4x L3 1 3 W
4x Black L3 L3 6 AWG12 2 2
6 switch 5 Y/GR
Y/GR FC 3 1 Z M
2.5mm2 Y/GR 3 2 X
4 3 Y
Outside
X100 5

AWG 14
K8 A
1
Controller Box 1 CL1 FC-com B
F1 L1 L1 L1 2 2
Inside Controller Box 3
L1 3 CL2
TR1
2
0,4A 1
L2 L2 L2 L2 4 GND
4
L2 5 CL3
L3 L3 L3 6
L3

Inside Controller Box


Outside Controller Box
INTER-
F2
LOCK
TR2 0,4A L3 Hevap
2 1

AWG 16
K2
X41 X40 1 CL2 Hevap5-6A Hevap5-6A
12V L1 L1 2
1 1 Hevap6-6B Hevap6-6B
A 3 CL1
COM 2 L2 L2 4 Hevap1-1A Hevap1-1A
T1 B 2
3 5 CL3 Hevap2-1B Hevap2-1B
Trafo SW1 GND L3 L3 6
4 3

SPM6
POWERMEAS
MODULE
1
On/Off Hevap1-2A Hevap1-2A
2
TR3 [Red] switch Hevap2-2B Hevap Hevap2-2B
3
TR4 K3 Hevap3-3A Hevap3-3A

AWG 14
4
TR5 [Red] [Red] 1 Hevap4-3B 13x Hevap4-3B
5 X50 (J5) L1 2 AWG18
[White]
6 RMM 0VAC 1 0VAC (GND) 3
Y/GR L2 4 Hevap3-4A Hevap3-4A
2
RMM 24VAC 3 5 Hevap4-4B Hevap4-4B
24VAC L3 6
TRAFO T1 Hevap5-5A Hevap5-5A
Approx voltages Hevap6-5B Hevap6-5B
Terminal 1-2 : 440V AC X51 (J3) X52 (J1)
GND Y/GR Y/GR Y/GR
Terminal 3-4 : 27V AC 1 GND 1
Terminal 5-6 : 24V AC 2 2
L3 FC-com
3 3

[Red]
[Red]
Inside Controller Box 4 4
TX L2
Controller Hatch 5 RX 5 K4
RX
6 TX 6 1 1

TR4
TR3S
L1 CL1 2

RMM-com
RMM - York
Powerline
modem
X80 7 7
ON 3 2
/ON 5 CL2 4 Mcond
GND Optional
GND 4 5 3
B CL3 6 1 1
/B 3 COM RMM-com 1 2 2
A
Inside Controller Box
Outside Controller Box

SUP6
USER
PANEL
A 2 COM INTER- 1 2 3 3
12V 12V LOCK 3
1
TR3S 4 4 4
KEYPAD K5B 5 Mcond 5 5 M
TR4 6 6 6
27 3 9x
28 7
AWG 16

10 37 5 8 AWG18 7 7
38 Y/GR 8 8
Y/GR
KEYPAD X26 X27 K5
Mevap2 - 8 Tpump 1 4
4 GND GND 4 CL1 2
Mevap2 - 7 Tpump
Controller Hatch 3 SIGNAL SIGNAL 3 3 5
Mevap1 - 8 Mcond - 8 CL2 4
Inside Controller Box 2 GND GND 2
Mevap1 - 7 Mcond - 7 5 6
1 SIGNAL SIGNAL 1 CL3 6
Outside Controller Box
X24 X25 Mcond - 7
Tret Mcond - 8 Mevap 1
Tret 10 GND GND 10 Tevap
Tevap 1 1
2 9 SIGNAL SIGNAL 9 1 2 2
B B 2
Cargo 1 Tcargo 8 GND GND 8 Tsuc K6 2 3 3
A A 1 Tsuc 3
7 SIGNAL SIGNAL 7 1 1
2 2 CL1 2 4 4 4
B B Tusda3 6 GND GND 6 Tamb 5 Mevap1 5 5 M
USDA3 1 1 Tamb 3 2
A A 5 SIGNAL SIGNAL 5 CL2 4 6 6 6
2 7 9x
2 Tusda2 4 GND GND 4 Tsup2 5 3
B B 1 Tsup2 CL3 6 8 AWG18 7 7
USDA2 1 3 SIGNAL SIGNAL 3 Y/GR 8 8
A A 2
Tusda1 2 GND GND 2 Tsup1 INTER- 1 Y/GR
2 1 Tsup1
B B 1 SIGNAL SIGNAL 1 LOCK
USDA1 1
A A K7B
Inside Controller Box

X22 X23
Outside Controller Box

GND GND 27 3
Mevap 2
6 GND GND 6 28
Pdis SIG SIG Pmem 1 1
AWG 16

Pdis P 5 SIGNAL SIGNAL 5 P Pmem 37 5 1 2 2


5V 5V 38 2 3 3
4 +5V +5V 4
GND GND 3
3 GND GND 3
Psuc SIG SIG AirEx K7 4 4 4
Psuc P 2 SIGNAL SIGNAL 2 Air AirEx 5 Mevap2 5 5 M
5V 5V 1 4 6 6 6
1 +5V +5V 1 CL1 2
7 9x
AirMotor 3 5 8 AWG18 7 7
X20 X21 CL2 4
MotorPos 2 Y/GR 8 8
2 /PWR GND 2 5 6
M 1 CL3 6 Y/GR
1 PWR GND 1
Mevap2 - 7
X18 X19 Mevap2 - 8
GND Vhg
6 GND 6 Mevap1 - 7
1 V Vhg
5 PWR 5 Mevap1 - 8
A2 GND Vexp
K8 - 4 GND GND 4
A1 [Blue] K8 1 V Vexp K9
CCW 3 PWR PWR 3
A2 GND Veco 1 1
K7 - 2 GND GND 2 CL1 2
A1 [Blue] K7 1 V Veco
Mevap Hi 1 PWR PWR 1 3 2 Mpump
K-GND K-GND CL2 4
X16 X17 7 7
5 3
Inside Controller Box
Outside Controller Box

A2 K-GND K-GND A2 CL3 6 1 8 8


K3 - 6 GND GND 6 K6 -
A1 [Blue] K3 K6 [Blue] A1 2
Hevap 5 PWR PWR 5 Mevap Lo 3 1 1
A2 A2 4 2 2 M
K2 - 4 GND GND 4 K5 -
A1 [Blue] K2 K5 [Blue] A1 5 Mpump 3 3
CW 3 PWR PWR 3 Mcond Hi K10
A2 A2 4 4
Inside Controller Box

9x
Outside Controller Box

K1 - 2 GND GND 2 K4 - 1 4 7 5 5
FC A1 [Blue] K1 K4 [Blue] A1 Mcond Lo CL1 2 8 AWG18 H
1 PWR PWR 1
3 5
Inside Controller Box

Y/GR
Outside Controller Box

CL2 4
X14 X15 Y/GR
Mpump - 8 Shp-1 5
2 GND SIGNAL 2 CL3 6
Mpump - 7 Shp-2 Hpump
1 SIGNAL SIGNAL 1 Mpump - 7
K-GND K-GND Mpump - 8
X12 X13
A2 K-GND High pressure
K9 - 2 GND GND 2
Mpump A1 [Blue] K9 K10 [Blue] switch
1 PWR PWR 1
(Normally closed)

A2
X10 X11 K10 -
ON A1 Mheat
5 /ON /ON 5
2 GND
4 GND GND 4
RH 4 B COM
3 /B /B 3
54

3 A
2 A A 2
1 12V
1 12V 12V 1
Operating and service manual, Controlled Atmosphere

X8 X9
GND GND
3 GND GND 3
FC-com B TX RMM-com
2 /B TXD 2
A RX
Overall wiring schematic (alternate)

1 A RXD 1
FC-com
X6 X7
GND GND
3 GND GND 3
E LM Front TX TX LM Cargo Inside Controller Box
RS232 2 TXD TXD 2
RX RX Outside Controller Box
Retriever D GND
1 RXD RXD 1
plug in
C TX LM Cargo RH
B RX
container A X4 X5 4 4 4 4 SEN-
4 GND 3 3 3 3
3 DDP 2 2 2 2 SOR
Outside Controller Box 1 1 1 1
2 DDM
Inside Controller Box 1 VBUS

RS232 E X2 X3 BT1 CO2


[Black]
Retriever D 2 GND GND 2 4 4
C GND [Red] 4 4 SEN-
LM Front

1 RX-TX 12V 1 3 3 3 3
plug inside B TX 2 2 SOR
Ctrl Box A RX + 1 2 2 1
X1 1 1
TR3S 12V NiMH
1 AC-IN
TR4 Rechargeable
2 AC-IN
battery O2
RH
SMC6.1
MAIN CONTROLLER

X0
[Y/GR] 4 SCC6-CA 8851560202
GND 4 4 4 3
SEN-
RH 3 3 3 2
2 2 2 SOR Overall Wiring Schematic
1 1 1 1
Outside Controller Box Lodam electronics a/s
Inside Controller Box
P/N: 5251561801 Rev: 2.0

You might also like