You are on page 1of 19

International Journal on Engineering Performance-Based Fire Codes, Volume 6, Number 2, p.

53-71, 2004

EXTENDING THE PRINCIPLES OF IMPULSE VENTILATION IN


TUNNELS TO APPLY TO SMOKE CONTROL IN CAR PARKS

H.P. Morgan
International Fire Consultants Ltd, UK

B. Vanhove and J-C. De Smedt


N.V. International Fire Safety Engineering & Technology S.A., Belgium

(Received 23 July 2003; Accepted 24 November 2003)

ABSTRACT

In the past few years, there have been an increasing number of Impulse Systems installed in car parks, especially
in Northern Europe. Unfortunately, no design method has been described openly in the public domain. This
places Authorities Having Jurisdiction (AHJs, or Approving Authorities) in a difficult position when faced with
a proposal. The present paper is intended to develop calculation procedures which can fill this gap, as well as
pointing to aspects needing further research.

The paper describes principles and calculation methods for road tunnels, and generalises these to the different
geometry typical of open-sided car parks. These principles and calculation methods are then modified to apply
to enclosed car park storeys which have an exhaust fan or fans to finally remove smoky gases.

The fundamental characteristic of these methods is that fans (jet fans) are used to accelerate the bulk air below
the hot sub-ceiling smoke layer to a sufficient velocity to prevent the advance of the leading edge of the smoke
layer. The objective is to allow a clear-air safe approach for firefighters from one side of the fire at the cost of a
more general smoke-logging beyond the other side. Different formulae for critical bulk air velocities are
suggested for flat ceilings; for downstand beams forming channels parallel to the fan jets; and for downstand
beams at right angles to the fan jets. A method of relating this critical velocity to the number, size, and emission
velocities of the jet fans is suggested.

The desirability of matching the final exhaust to the induced bulk airflow is indicated for enclosed car park
storeys in order to avoid recirculation of smoke into the area intended to be kept clear.

Finally, the need to employ a careful scaling of key parameters in any hot smoke test intended to demonstrate
performance of the system is indicated.

1. INTRODUCTION more onerous requirements for fire-resistance


rating for the building’s structure than the former.
1.1 Background We can note that this method depends on the
natural buoyancy of smoke on windless days, and
Smoke Control in above-ground car parks is that wind forces can dominate any buoyant forces
commonly specified in prescriptive Codes (e.g. likely to be found.
Approved Document B to the Building Regulations
[1] in the UK). The approach is to specify openings While it is possible to design Smoke and Heat
in at least two walls, including two opposite sides Exhaust Ventilation Systems for car parks [e.g. 2],
of the building, having a minimum free area of a the practicality of this approach is greatly
specified percentage of the floor area. In the UK influenced by the lack of headroom beneath beams
Approved Document B [1] requires a total vent (or ceilings) commonly found in car parks.
area in the walls of at least 5% with at least 2½ %
in each of two opposite walls for the car park to be An alternative method of smoke control has been
regarded as open-sided. If the car park is not used in tunnels for many years [3]. This method
regarded as open-sided, it should have at least 2.5% adopts the principle of “Impulse” or “Jet Fan”
total vent area with at least 1¼ % on each of two ventilation.
opposite walls. The latter of the two options attracts

53
International Journal on Engineering Performance-Based Fire Codes

1.2 Impulse Ventilation in Tunnels: resistance depends on the difference in velocity


Qualitative Principles between the hot smoke and the air. If the bulk
velocity of the air in the tunnel is equal to and
A fire occurring in a tunnel, for example in a opposed to the speed at which the hot layer is able
vehicle which has come to a halt, will cause a to advance in still air, the resultant velocity of
flame and smoke plume to rise. This plume will advance of the hot smoke will be zero. In other
reach the roof, and spread outwards in both words, inducing a large enough velocity in the bulk
directions. If the fire is large enough for flame air flow will prevent the hot smoky gases from
temperature gases to reach the roof, the flames then endangering stopped vehicles on the “upstream”
spreading under the roof cause a rapid increase in side of the fire – i.e. in the direction the bulk air
heat radiation falling on the fire and on adjacent comes from. The turbulence expected at the leading
vehicles, which can lead to a rapid acceleration in edge (or “nose” if we follow Hinkley’s [4]
growth rate of the fire as it develops and spreads to nomenclature) of the hot smoke will produce a
other vehicles. great deal of mixing of smoke and air, causing the
tunnel to become smokelogged on the
The hot smoke layer beneath the roof advances at “downstream” side of the fire.
speeds of up to 5 ms-1 for flame temperature gases.
Typical vehicle speeds in a road tunnel would be Where the vehicle direction of travel is aligned
above 30 kph. This corresponds to speeds greater with the bulk air flow this smokelogging will not
than 5.5 ms-1. affect safety (vehicles will have driven clear).
There will on the other hand be safe conditions for
It follows that, in a single-bore tunnel with traffic vehicles trapped by the fire on the “upstream” side,
travelling in just one direction, vehicles in front of and clear-visibility access for firefighters
the vehicle on fire will be able to drive to safety approaching from the “upstream” side.
faster than the hot smoke will advance. Vehicles
behind the fire will be forced to stop, and will then Smoke control systems using fans to transfer
be at risk from the growing fire (see Fig. 1). In a momentum into the bulk air in the tunnel in order
tunnel where traffic moves in opposite directions in to achieve the desired velocity to prevent the
the same bore, vehicles travelling in both directions advance of hot smoke in the “clean” direction are
may become trapped by the fire. known as Impulse Ventilation Systems. The fans
used to introduce this momentum are commonly
There is an aerodynamic interaction between the known as jet fans, and the concept is often called
advancing front of the hot smoke layer and the air “Jet Fan Ventilation” as an alternative to “Impulse
in the tunnel. The smoke has to “push aside” the air Ventilation”.
in front of it, resulting in a resistance to that
advance. This process is illustrated in Fig. 2. This

Fig. 1: Impulse ventilation system in a tunnel

Fig. 2: The advance of the leading edge (or “nose”) of a buoyant layer of hot gases

54
International Journal on Engineering Performance-Based Fire Codes

1.3 Impulse Ventilation in Car Parks: special equipment and training available to fire
Qualitative Principles services. Indeed, the smoke control system need
not necessarily be activated until firefighters arrive
The principles developed for tunnels can be applied on site.
to the more complicated circumstances of a car
park. In the past few years, there have been an Impulse systems are usually designed to allow
increasing number of Impulse Systems installed in firefighters clear access with good visibility to one
car parks, especially in Northern Europe [e.g. 5]. side of the fire, at the cost of creating turbulent
Unfortunately, no design method has been mixing of smoke and air on the other side of the
described openly in the public domain. This places fire, creating extensive smoke logging. It follows
Authorities Having Jurisdiction (AHJs, or that it is usually safer if Impulse Systems are not
Approving Authorities) in a difficult position when started while people are evacuating (as they may be
faced with a proposal. The present paper is caught in the fan-induced smoke logging quicker
intended to develop calculation procedures which than with the fans off), but are instead started after
can fill this gap. a delay comparable to the firefighters attendance
time. In practice, a delay of 5 minutes from
The paper will start by detailing the design detection is often used.
methods appropriate to tunnels, and will then
generalise these to open-sided car parks. It will It may also be noted that many smoke control
then discuss the further aspects of enclosed car systems are dual purpose: they operate
parks, pointing to differences in approach continuously to dilute engine fumes etc. to safe
compared to open-sided car parks. Finally, there is levels, and change to the (usually) higher
a brief discussion of acceptance tests for Impulse ventilation rate needed for smoke control when a
Systems in car parks. fire is detected.

A consequence of the previous two paragraphs as


2. DESIGN OBJECTIVES FOR SMOKE far as Impulse Systems are concerned, is that the jet
CONTROL IN A CAR PARK STOREY fans may need to be turned off when smoke is first
detected, and then turned back on again at the
Smoke control can serve several purposes in a car smoke control level after the pre-determined
park. interval.

It can ensure that escape routes within the car park Even though this present paper is based on
storey continue to be usable even while the fire is similarities between tunnel systems and car park
burning. This objective is therefore to protect the systems, it is worth recognising that there are many
Means of Escape (MoE). differences between the two. Some of these are
summarised in Table 1.
In practice, this objective can only be met if escape
routes are kept free of smoke to a great enough
height for people to move freely in clear air. In 3. IMPULSE VENTILATION IN
most car park designs, this objective is of minor TUNNELS
important compared to the provision of suitably
short travel distances leading to protected stairs 3.1 Principles
and/or fire exit doors.
Design calculations must first establish the largest
Smoke control can provide “smoke clearance”. fire appropriate for the circumstances. Where the
This involves clearing smoke out of the storey after design is based on a steady-state (i.e. on a “worst
the fire has been suppressed. The objective is to plausible case”) fire, this can be specified as a heat
provide good visibility to help firefighters to generation rate coupled with an effective perimeter
confirm that there are no secondary fires, and also of the fire. The mass flow rate and temperature of
to speed the reinstatement of the building to normal smoky gases reaching the roof close above the fire
activity. can then be calculated using established formulae
and the known height of the tunnel.
Between these two extremes, smoke control can
assist firefighters in finding and extinguishing the The rate of advance of the front edge, or “nose”, of
fire. In other words, it can make operational fire the smoke layer must be assessed. The outcome of
fighting faster and more effective, thus reducing this calculation is a critical velocity of advance of
damage to the building. This objective does not the hot smoke layer under the ceiling, for the
require as good a performance as for protecting specified fire in a tunnel of specified height and
occupants and their escape route, in view of the width.

55
International Journal on Engineering Performance-Based Fire Codes

Table 1: Some typical differences between tunnels and car parks (Note: Many exceptions exist)

Tunnel Car park


Aspect ratio (transverse section) Height similar to width Height << width
Aspect ratio (long section) Very long compared to width Length similar to width
Vehicle movement Unidirectional, at road speeds Multi-directional, at slow speeds
Vehicle types Mixed. Cars to trucks and buses Cars
Typical design fire Truck. > 17 MW Car. About 3 MW
Air flow pattern induced by jet Along length of tunnel in Specific to each car park.
fan direction of traffic flow Ignores traffic movement
Jet fan operation As soon as fire is detected Delay until pedestrian escape is
complete
Evacuation patterns for people If ahead of fire, drive on. If Escape on foot via building’s
behind fire, escape on foot Means of Escape (e.g. protected
away from fire stairwells)
Fire fighting approach Drive fire appliance into tunnel Enter building on foot, approach
from air inflow end, as close as fire following jet fan-induced
possible to the fire airflow

We then need to be able to calculate jet fan is considered below in the context of car park
characteristics capable of inducing a bulk airflow at Impulse Systems.
least equal but opposite to the smoke layer’s speed
of advance in the “upstream” direction. The 3.2 Jet Fan Thrust and Induced Velocities
transfer of momentum from fan jet to bulk air, in Tunnels
resulting in the creation of a pressure pushing the
air, is discussed below. 3.2.1 Thrust and induced pressure differences
The principles of Impulse or Jet fan ventilation in a
This pressure has to be sufficient to overcome the single-tube tunnel (or covered roadway) have been
pressure losses experienced by the bulk air while described in Section 3.1 above. The present
travelling through the tunnel. In general, a tunnel purpose is to develop the mathematical formulae
will have an entry and an exit opening to the needed to implement a design based on those
atmosphere. There may be bends or changes in principles. Equivalent explanations can also be
cross-section. There will be friction effects at the found elsewhere [e.g. 3,7].
walls, floor, and roof. The tunnel is in effect a
large duct, similar in most respects to an air- One or more fans will be arranged so that they emit
handling duct in a HVAC system in a building. jets along the length of the tunnel. These jets
Design information developed for ducts [6] can be should be arranged such that they minimize contact
used to assess the flow resistance (assessed in with the roof and walls of the tunnel. It is desirable
terms of pressure losses at each contribution to for the jets to have the maximum opportunity to
flow resistance such as entry losses, exit losses, interact with the air in the tunnel without friction
losses at bends, etc.) of the tunnel. The design effects slowing the jets before that interaction has
should be successful when the sum of all the occurred.
pressure losses, for induced bulk air speeds greater
than or equal to the critical “nose” velocity, is A fan can be characterized as having an emission
equal to the driving pressure induced by the jet fans. orifice of area Af m2 and an emission velocity of vf
This will ensure that the smoke will not be able to ms-1.
advance in the “upstream” direction from the fire.
The remainder of Section 3 develops these ideas The volume flow rate emitted by the fan is:
quantitatively.
V f = Af v f (1)
Wind pressure differences between the entry and
the exit to the tunnel can either assist or oppose the
flows induced by the jet fans. Daly [3] suggests For ambient temperature air of density ρ0 kgm-3,
that such effects should be taken into account. This the mass flow rate of air emitted per second is the
aspect is not developed further for tunnels in this product of volume flow rate and density, i.e.:
present paper, although the effect of wind pressures
Mf = ρ0 Vf (2)

56
International Journal on Engineering Performance-Based Fire Codes

The total momentum in the air emitted each second air velocity which is in turn derived from the speed
(the momentum flux) is simply the product of mass of the “nose flow” (see below).
flow rate and velocity, i.e. for a single fan
It is pointed out by Daly [3] that in practice, the
Momentum flux = Mf vf = ρ0 Vf vf (3) impressed pressure is based on the difference
between vf and vair. It follows that where greater
For a free jet – that is for a jet which does not accuracy is required, vf in equations (1) to (7)
interact with resisting solid surfaces such as walls should be replaced by (vf – vair). In the present
and roof – the total momentum is conserved despite work, this correction is ignored for simplicity, but
the entrainment of air into that jet. That is, the it can be noted that it can be introduced as a post-
mass flow rate in the jet increases as air mixes into hoc correction once the value of vair has been
the jet from the air surrounding the jet; the velocity calculated.
in the jet decreases, but the product remains
constant. 3.2.2 Pressure losses in the tunnel
To a good approximation, a tunnel can be regarded
Newton’s Second Law also applies to fluids. The
as a large duct. Provided that all significant flows
rate of change of momentum corresponds to a force.
are turbulent, that is provided that the Reynolds
This force, when exerted by a fan is usually called
Numbers are large enough, the difference in scale
a thrust. In our case, the jets will slow until they
becomes unimportant, and the resistance to airflow
become part of the bulk air movement in the tunnel.
in the tunnel can be calculated by the same
In other words, the momentum flux emitted per
methods as in a HVAC or ACMV duct. Methods of
second by the fans is transferred to the air in the
calculating resistance to flow are well known. See
tunnel. Hence, the total momentum flux in the bulk
for example Section 4 of ref. 6.
air is:
We follow ref. 6 by noting that the energy in fluids
ρ0 At vair2 = ρ0 Vf vf (4)
moving through ducts is lost in two major ways.
where At is the cross-sectional area of the tunnel at
One is by frictional interaction with the walls. This
a right angle to the direction of flow of the air.
can be expressed in D’Arcy’s equation for pressure
loss due to friction:
The increase in momentum flux in the bulk air is
experienced as a force (Newton’s Second Law)
l ρ 2
acting on that bulk air volume. It is convenient to ∆ ploss = λ v (8)
recall that a force exerted evenly on a fluid can be D 2
expressed as a pressure. It follows then that the
rise in pressure above ambient in the tunnel due to where the friction factor λ is a function of
one fan is just: Reynolds Number and the relative roughness of the
wall surfaces. For further details on how to
ρ 0 At v air
2 calculate ∆ ploss for a given value of v, via λ and D
∆p = (5)
At (the hydraulic mean diameter of the duct/tunnel),
see ref. 6 Section 4.
i.e.
The other major source of energy loss (i.e. of
pressure loss to overcome resistance to flow)
ρ 0V f v f
∆p = (6) occurs when a bend, obstacle, or other feature
At generates additional turbulence in the fluid flow.
These losses can be expressed in “Pressure Loss
where there are N fans in the same length of tunnel, Factors” ς defined by:
we have
ρ
Nρ 0V f v f ∆ ploss = ς v2 (9)
∆p = (7) 2
At
The pressure loss factor is usually determined
This is the impressed pressure difference driving empirically, and typically is a shape-dependent
the air through the tunnel, against the resistance of function rather than a scale-dependent function.
the pressure losses due to bends, surface roughness, Although it may be necessary to extrapolate
etc. These losses are described in more detail in (exercising due caution) from an air conditioning
Section 3.2.2 below, and will depend on the design duct to a similar geometry tunnel obstruction, many
values of ς factors can be found in Section 4 of

57
International Journal on Engineering Performance-Based Fire Codes

Ref. 6. One can note particularly that a tunnel will In general,


usually have an entry loss (where air is drawn in
one end) and an exit loss (where air and smoke are Vair (11)
blown out the other end); plus an additional v n, m =
A t (n , m)
pressure loss term for each geometrical feature (e.g.
bends, changes of cross-section etc.); plus the
pressure loss due to friction over its length. Note where Vair is the volume flow rate through the
that where there are significant changes in cross- tunnel; vn,m is the velocity local to the pressure-loss
section or of surface roughness, it will be necessary generating feature identified by subscript n or m,
to calculate the sum of the pressure losses due to and At(n,m) is the cross-sectional area of the tunnel
friction in each length of tunnel. at the pressure-loss generating feature identified by
subscript n or m.
None of the thermally-buoyant ceiling jet models
currently available make allowance for sloping This means that for a known geometry of tunnel,
ceilings. Sloping tunnels will affect the entrainment one can either specify Vair (as for example where a
into an inclined buoyant flow, although where the minimum dilution rate of engine fumes including
leading edge of that flow is halted close to the fire carbon monoxide must be achieved) or one can
plume such effects will be minor and can be specify v (as for example when trying to prevent a
ignored. There should be minimal effect on the thermally buoyant smoke layer travelling against
thermal plume rising above the fire. A gradient in the direction of the fan jets). Then, via equations
the tunnel will have no effect on a non-buoyant (10) and (11), the minimum fan specification can
flow. It is assumed throughout this paper that the be calculated in terms of NVf v f (or NA f v 2 ).
smoke and fire gases become so mixed with air by f
turbulence on the downstream side of the fire that This immediately shows us that there is a trade-off
they can be treated as essentially non-buoyant. It between the size of each individual fan and the
follows that changes in gradient typical of number of fans.
roadways can be ignored.
3.3 Opposing the Advance of a Thermally-
A simple entry (eg. a hole in a wall at right angles buoyant Ceiling Jet of Smoky Gases
to the duct or tunnel) will often have ς = 0.5. A
3.3.1 General
similarly simple exit will have ς = 1.0. Local
In Section 3.2, it has been shown that jet fans can
topographical features will often change these
induce a bulk flow in the air in a tunnel, determined
values [7] and tunnel designers may even have to
by many factors including the desired air volume
model the surroundings in order to arrive at
flow rate or air velocity. The designer of an
empirical values appropriate to their circumstances.
impulse smoke control system must select an
appropriate value in order to achieve his objective,
It is especially important to note that v in equation
which is to ensure that all smoke generated by a
(9) is the velocity local to that particular obstacle,
fire travels in one direction away from the fire
and changes in cross-section involve changes in
(usually in the direction of traffic movement),
local velocity. The volume flow rate (ignoring any
leaving the other side of the fire free of smoke.
heating of the air) will be the same value
This protects anyone forced to stop; and it allows
everywhere. The velocity in D’Arcy’s formula
firefighters to approach the fire in safety, in order
(equation 8) also must be altered for every change
to extinguish it. In Section 3.3 of this paper, we
in section of the tunnel.
discuss how an appropriate value of bulk air
velocity can be specified.
In general, a state of dynamic equilibrium will be
reached where
3.3.2 The design fire
Nρ o V f v f ρ0 lm ρ 0 2 The fire is likely to be in a vehicle. Usually the
= ∆p = ∑ ς n vn2 + ∑ λm vm designer will be interested in a steady-state design
At all n 2 allm dm 2
approach. This involves identifying an appropriate
(10) heat release rate and fire perimeter (or, for point-
source plume models, a fire diameter). From these
where all air is assumed to be at ambient the initial parameters can be deduced for the
temperature; the subscript n denotes separate thermally-buoyant smoke plume flowing under the
obstacles, bends, entry, exit or other shape- ceiling.
dependent features such as changes of section; and
subscript m denotes individual lengths of tunnel (or Useful sources of data on the size of vehicle fires in
duct) having the same cross-section and surface tunnels are relatively sparse. See Ingerson and
roughness. Romanov [7] for experimental data including a bus

58
International Journal on Engineering Performance-Based Fire Codes

and truck fires done as part of the EUREKA project. The average layer temperature close to the plume is
Schleich et al. [8] is a useful source for then
experimental data on car fires involving modern
cars (e.g. Fig. 3). It should be noted that the car Q (14)
design fire cited by Morgan et al. [2] of 3 MW θ=
Mc
convective heat flux and 12 metres perimeter
derives ultimately from 1960s data, but is broadly If greater accuracy is required, M, Q and θ can be
compatible with Schleich et al.’s results prior to the used to calculate the layer’s depth (see ref. 2, or
time when spread to another car is predicted [8]. Hinkley’s method [4] described below); from
which one can assess a new Y value, and
successive iteration can converge on better values
of M and θ. It is suggested that the level of
precision implied by iteration cannot usually be
justified for car park smoke ventilation in view of
the need to introduce safety margins to allow for
unquantifiable pressure losses.

3.3.3 Ceiling jets: Established flows


The design of an impulse smoke control system
first requires an assessment of the speed of advance
of the ceiling jet travelling outwards from the fire –
in the absence of an imposed airflow.

Fig. 3: RHR vs Time A ceiling jet is defined in the SFPE Handbook


(Source: Prof. J.B. Schleich) Section 2-4 [14] as being the relatively rapid gas
flow in a shallow layer beneath the ceiling surface
Once a design fire appropriate to the circumstances which is driven by the buoyancy of the hot
has been selected, one can use the Large Fire combustion products. An older usage reserved the
Plume Model to estimate the mass flow rate of hot term for an under-ceiling layer flow which still
smoky gases reaching the ceiling [2]: carried some kinetic energy from the upward
moving gases in the plume above the fire.
M = C e P Y 1.5 (12)
We can identify two characteristically different
forms of flow. One (see Fig. 4) is where the smoke
where M is the mass of smoky gases rising past
flow has spread under the ceiling until the gases
height Y, Ce is a constant taking the value 0.19
have reached a sink and have been removed. In
where the fire plume rises vertically to a high
most experiments, this corresponds to a flow which
smoke layer base; or the value 0.21 where the layer
has reached the edge of the ceiling and is free to
base is close to the fire; or 0.34 where the air
spill past it. This is an established flow. The second
approaches the fire from one side and causes the
(see Fig. 5) is where thermally buoyant smoke
plume to “lean” at an angle to the vertical. P is the
layers advance beneath a ceiling by displacing the
fire perimeter and Y is the height of rise.
air in front of the “nose” of the smoke layer. This
air is effectively pushed downwards by the layer.
This development of the “Large Fire Plume Model”
The energy required to do this comes from the
was by Hansell [9] drawing on work by Zukoski et
smoke layer and so displacing this air can be
al. [10] and Quintiere et al. [11] (using “virtual
regarded as a resistance to the “nose” of the layer
point-source” axisymmetric plumes) to modify the
flow – an effect absent in a flowing established
Large Fire Plume Model developed originally by
ceiling jet.
Thomas et al. [12] and Hinkley [13].
The nature of the ceiling jet is also influenced by
As a first approximation, we can take Y to be the
the geometry of the ceiling. For the purposes of
height to the roof above the fire. Ce should take a
this paper, we can consider two simple
value appropriate to a “leaning plume”, as the
circumstances. One is where the buoyant layer (in
purpose is to induce a strong air flow in the tunnel
the absence of any induced cross-wind) flows
which will inevitably make the plume lean away
radially outward under a flat ceiling; the other is
from the vertical. Hence take
where the buoyant layer is confined and channelled
between parallel walls or downstand beams.
C e = 0.34 (13)

59
International Journal on Engineering Performance-Based Fire Codes

Fig. 4: An established smoke layer – Smoke flows above cold air

Fig. 5: An advancing smoke layer – Smoke flow displaces downwards the air
in front of the leading edge

Formulae for the velocity of advance of an the fire plume on the ceiling. If an Impulse System
established radial ceiling jet can be found in the is to be designed to prevent the advance of the
SFPE Handbook [14], having been developed by smoke in one direction, the induced airspeed in the
Alpert [15]. These are opposite direction required to achieve this will be
smaller if the smoke is allowed to travel further
1 from the point of impingement. It follows that
Q 3
(15)
v = 0.96  there can be an implied trade-off between the
h induced bulk airspeed and the distance the smoke is
allowed to travel in the unwanted direction before
for r/h ≤ 0.15, and being halted and turned back. In practical design
terms, the maximum smoke travel distance in the
1 1
0.195Q 3 h 2 unwanted direction can be related to the fire
v= (16) services’ willingness (or otherwise) to tolerate
5
r 6
some turbulently mixed smoke in the closest
approach to the burning vehicle.
for r/h > 0.15.
It can be noted that radial ceiling jets are unlikely
Equations (15) and (16) do not require prior to feature usefully in Impulse system designs for
calculation of the entrainment into the fire plume, tunnels. They may, however, feature prominently
as this is included in the correlation. in designs for car parks having extensive flat areas
of ceiling.
It can be seen from this correlation that the layer
velocity is almost inversely proportional to the Ceiling jet flows under confined or channelled
radial distance from the point of impingement of ceilings are discussed in the SFPE Handbook [14],

60
International Journal on Engineering Performance-Based Fire Codes

although no actual formulae for the layer’s velocity in a corridor or tunnel, as a part of a study of smoke
are given. Characteristic velocities for established movement in shopping malls. His work took
channelled flows were developed by Morgan and account of the nose of the ceiling flow explicitly,
Hansell [16] and are cited in Morgan et al. [2]. and so we can expect his work to be the most
They identified the effect of discharge coefficient appropriate source for the present circumstance.
on the velocity as the hot smoky gases flow Unfortunately he only developed formulae for
beneath downstand beams at right angles to the channelled flows without a downstand across the
flow direction: flow, which serves to limit the applicability of his
results.
Where the channelled flow has no downstands (i.e.
a flat ceiling between the side walls or constraints) Hinkley [4] has shown (see his equation (16),
the characteristic layer velocity is [2,16]): modified for higher temperature by setting U’=
u(T/To)1/3) that the velocity of advance of the
1 “nose” of a layer flow along a tunnel takes the form:
 gQT  3
v = 1.27  (17)
 cρ 0WT0
2
 v nose  ( h − d )( 2h − d ) 
1
3
=  (20)
Where there are downstands across the flow U ' C  h( h + d ) 
direction:
where h is the height of the tunnel or channel, d is
1 the buoyant layer depth and
 gQT  3
v = 0.76  (18)
 cρ 0WT0
2
  gQT 
1
3
U ' =  

(21)
 cρ o To W
2
In a fully channelled flow, equation (17) will apply 
over the full length of the channel or tunnel.
Equation (18), on the other hand, only applies to where W is the width of the tunnel or channel.
the flow as it passes beneath the downstand.
Hinkley developed a graphical solution method
In order to apply equations (17) or (18), it is where one first calculates:
necessary to pre-calculate the layer temperature.
This can be done using equations (12) to (14). P( gh ) 2
1
(22)
The depth of the flowing layer (in the absence of a U ′WC
counterflow of air below) is given by Morgan et al.
(equation 5.11 of ref. 2) as: (making use of equations (12) to (14) above). The
depth of the flowing layer is given by Hinkley’s
2 Fig. 4 (reproduced herein as Fig. 6). His Fig. 5
0.36  MT  3
(reproducd here as Fig. 7) gives the dimensionless
d=   (19)
C d  θ 0.5WT00.5  layer velocity v/U΄C and hence the actual velocity
of advance of the leading edge (v).
where Cd takes the value 1.0 for a flow under a flat
C is an empirical constant found by Hinkley [4] to
ceiling between beams W metres apart, and takes
be approximately 0.5 based on a Japanese
the value of 0.6 for the flow under a deep beam
experiment in a car park having a complicated
across the direction of flow.
geometry. He also speculated that C would tend to
1.0 as the advance of the nose was slowed by an
In general, because all established flow formulae
opposing bulk airflow, due to a reduction in friction
ignore the resistance to flow at the leading edge or
at the ceiling. We should recognize, however, that
“nose” of the layer, they are likely to predict a
flow resistances due to friction at a smooth ceiling
higher velocity than will actually be the case at the
are likely to be smaller than those due to
leading edge of the ceiling jet. In terms of the
displacement of air in front of the “nose” – which
design of an Impulse system, this will lead to a
would depend on the relative speed of the buoyant
higher jet fan-induced airspeed to oppose the
layer to the bulk air. Hence C is more likely to be
smoke movement, and the use of such formulae can
near the empirical value even when the “nose” has
therefore be expected to err on the side of safety in
zero net speed relative to the ceiling.
design.
We can note that he also cited Benjamin as having
3.3.4 Ceiling jets: Leading edge or “nose” flows
derived a value for C of 0.82. In practice a higher
Hinkley [4] has discussed the speed of advance of value for C will lead to a higher value for the
the leading edge of a smoke layer (i.e. a ceiling jet) critical speed of advance of the “nose” of the

61
International Journal on Engineering Performance-Based Fire Codes

smoke layer, and consequently to a larger jet fan 3.4 Suggested Design Procedure
specification, i.e. it will err on the side of safety.
a) Identify an appropriate design fire for the
It seems reasonable to adopt Benjamin’s value for circumstances.
C for design purposes where Hinkley’s method is b) Estimate separately for each length of tunnel
adopted. having the same width, ceiling height and
surface roughness, the layer temperature at
Hinkley’s analysis was for a smoke layer traveling the ceiling using Section 3.3.2.
in one direction only away from the fire. Where
smoke travels in both directions away from the fire, c) Identify the ceiling jet formula appropriate to
it is reasonable to take W as being twice the actual the circumstances for each separately
width, as the smoke flow is equivalent to a one- identifiable length of the tunnel.
direction flow in a tunnel of twice the width. d) Calculate the layer velocity for each such
length using Section 3.3.3 or 3.3.4. This will
be the minimum value of induced velocity
acceptable in that length, and can be
designated the critical velocity for that length.
e) Calculate the volume flow rate for each length.
Take the maximum value as the critical
volume flow rate. Recalculate the local
velocities corresponding to all lengths and
obstacles.
f) Calculate the total pressure losses in the
tunnel using these local velocities and Section
3.2.2.
g) Equate this total pressure loss value to the
induced pressure due to the jet fans, and
calculate the overall fan specification in terms
of NVfvf for the tunnel.

Fig. 6: Dimensionless layer depth vs 3.5 Some Practical Considerations


dimensionless flow rate, from Hinkley [4] The positioning of jet fans should be such that the
jets can transfer momentum to the air without
playing on bends or obstacles. The jets should be
able to transfer momentum to the air in the tunnel –
which implies that a jet fan can be close to an entry
blowing inwards, but should never be close to an
exit blowing out. It also seems reasonable to have
a sufficient horizontal separation along the tunnel
for momentum to be transferred before the jet
interacts with the next fan downstream. In order to
maximise the effect on the smoke layer, the ideal
jet fan jet should be angled downwards to avoid
contact with the ceiling, and should avoid contact
with the walls.

4. IMPULSE VENTILATION IN OPEN-


SIDED CAR PARKS

4.1 General
A car park storey can be thought of as a tunnel
which is very wide but (usually) with a low ceiling.
Where there are openings at opposite sides of the
Fig. 7: Dimensionless velocity vs dimensionless storey, the principles of Impulse ventilation can be
flow rate, from Hinkley [4] applied with little modification – in principle (See
Fig. 8). The most important differences between a

62
International Journal on Engineering Performance-Based Fire Codes

tunnel and a car park storey arise from the much 4.3 Opposing Thermally-Buoyant Ceiling
greater horizontal extent of the storey. Jets
4.2 Design Objectives The principles and formulae involved are the same
as in Section 3.3 above. The greater horizontal
Vehicles cannot drive as quickly in a car park as in extent of the car park compared to a tunnel, and the
a road tunnel. There is therefore essentially no lower ceiling, increases the importance of radial
opportunity to drive away from the smoke faster ceiling jets (where there is a flat ceiling), and
than it moves. It follows that Impulse systems in increases the importance of downstand beams
car parks cannot protect escape with the cars. As where they are present (discussed further in Section
explained above, they cannot protect the MoE for 4.4 below). Design of an impulse system can
occupants in view of the turbulent mixing in the follow a similar sequence to that for tunnels. An
direction of the fan jets, and so there is a need for appropriate design fire should be selected. This is
evacuation to be accomplished using travel commonly based on a single car (e.g. 4.5 MW heat
distances and protected escape stairs etc., before release rate, 12 m perimeter cited in ref. 2), with
the jet fans are switched on. the implicit or explicit assumption that the fire
service would be able to intervene before the fire
The primary role of impulse systems in this context spreads to neighbouring cars (typically this
is to provide clear access from one side of the fire assumes that the firefighters can intervene in the
for firefighters, so that they can control the fire. fire in the first 10 to 12 minutes after ignition (see
The system will then provide smoke clearance so for example Schleich et al. [8]). If attack times are
that the building can be put back into use as early likely to be longer, then perhaps consideration
as possible. should be given to fitting sprinklers, or assuming a
larger design fire.

Fig. 8: Impulse ventilation in an open car park

63
International Journal on Engineering Performance-Based Fire Codes

The selection of a suitable formula for the advance 4.4 Balancing Induced Pressure
of the ceiling jet is similar to that for a tunnel Differences Against Flow Resistances
discussed in Sections 3.3.3 and 3.3.4 above. Where
the ceiling is flat, the ceiling jet will be radial, and One can identify an entry pressure loss and an exit
equations (15) and (16) will apply. Note that the pressure loss. In general, the car park storey will
trade-off between an acceptable degree of be short compared to a typical road tunnel, and the
smokelogging close to the fire on the best line of cross sectional area of the car park will usually be
approach for the firefighters, and the critical large. This means that one could usually ignore the
velocity of bulk airflow can become a crucial factor friction losses and base calculations on the shape-
in the design. It is recommended that in all such dependent pressure losses.
circumstances there should be consultation with the
fire service before progressing the design. The method described in Section 3.4 above can
then be used to calculate NVfvf for the storey.
Where there are relatively deep downstand beams
parallel to the jet fan jet directions, either equation Where there are many uncertainties in the
(17) or Hinkley’s method (Section 3.3.4 above) calculation (see for example Section 4.5 below), it
will apply when assessing the critical velocity to can be necessary first to develop the zone model
halt the advance of the smoke layer. methods set out in this paper as an initial proposal,
and then use that proposal as a starting point for a
The depth of the channelled flow should be more detailed CFD analysis which would either
calculated (see Sections 3.3.3 and 3.3.4) to confirm validate the proposal, or which would suggest
whether or not smoke will spill into neighbouring amendments needed to make the proposal viable.
channels. If it will, then the critical velocity
becomes less accurate, although the “non-spillage” 4.5 Some Practical Design Aspects
value can still be adopted as being conservatively The greater width of a car park storey relative to its
safe in the context of calculating jet fan height, when compared with a typical tunnel,
specifications. makes it more important that the calculated number
of fans can exert a uniform pressure on the air
Where there are beams at a right angle to the jet fan across the full width of the storey. If this is not
direction, they will act as weirs, spreading the done, the air will tend to move from the region of
smoke flow laterally until smoke spills across most greater pressure towards the lower, and there will
or all of the available length of the beam. This may be a circulation pattern of air (and smoke being
be the full width of the car park. This increase in W carried with the air) with some smoke being carried
in equation (19), coupled with the smaller constant in the undesired direction past the fire into the areas
for transverse beams, can mean that the critical intended to be clear. It may be necessary to specify
velocity is much lower for transverse beams than a larger number of smaller fans to be able to
for parallel beams, leading to a smaller arrange for the spreading jets to be touching the jets
specification for the jet fans in the former case. to both sides and also the side walls by the distance
Smoke will tend to spread more widely across the from the fans where the jet velocities have reduced
jet fan’s direction with these transverse beams, to the induced air velocity.
affecting more of the car park storey.
This may mean that all N fans are used to form one
Some car parks have downstand beams in a “criss- line across the storey, although the non-uniformity
cross” pattern. These cannot be calculated by zone across a typical jet implies that it would be better to
model methods, but can be expected to perform arrange fans in two lines, with one line covering
somewhere between the parallel and the transverse the “gaps” between fans in the other line (see Fig.
beam cases. It may be necessary to use more 9).
geometry-specific methods based on
Computational Fluid Dynamics (CFD) to confirm In many car parks there are columns, enclosed
the performance of Impulse Systems with such stairwells, or other constructional features which
ceilings. will generate turbulence in the air flow, but for
which there are no known values of ζ. It is also
It should be noted that because the critical velocity, unfortunately the case that there are no ζ values in
and thus the specified value of NVfvf for the car the available literature for the pressure losses due
park storey, is different for the different ceiling to air flowing past, around, and under parked cars.
configurations, we should not expect designs Indeed, most current designs of impulse systems
shown to work acceptably for one ceiling appear to ignore the presence of parked cars
configuration to be as satisfactory for another. altogether, and design essentially for an empty car
park. There is another practical difficulty where
jets play directly onto fixed objects, or onto parked

64
International Journal on Engineering Performance-Based Fire Codes

cars, and some of the momentum in the jet is lost area we wish to be kept clear. Similar concerns
by conversion back into a force on the objects and affect Smoke and Heat Exhaust Ventilation
is therefore not available for raising the induced Systems, for which the recommendation for air
pressure acting on the bulk airflow. inflows close to smoke [2] is that the incoming jet
should not exceed 1 ms-1. Research into the
This implies that there are major sources of significance of this effect would be desirable.
pressure loss which are unquantifiable in most
cases. These can be compensated for by increasing Wind pressures on the inlet and exit openings can
the number of fans. It appears usually necessary in be much larger than the pressures induced by the
such cases to adopt a subjectively assessed safety fans. A commonly recommended approach is to
margin – e.g. by doubling the number of lines of jet use reversible jet fans, with the direction of their
fans calculated as being necessary based on the operation linked to wind direction sensors such that
known pressure loss terms. the wind-induced airflow in the car park is always
in the same direction as the fan jets.
Where downstand beams form channels, there is a
tendency for both the ceiling jet (smoke) and the Jet fans can be used additional to the calculated
fan jet to be attracted to the ceiling by the Coanda lines, to direct or “steer” flows of air and smoke
effect (i.e. where the static pressure is reduced within the car park. The purpose is to make bulk
because of the gas velocity – a demonstration of air flows more homogeneous even where the car
Bernouilli’s Equation). This may interfere with the park geometry is complicated. It would usually be
transfer of momentum from jet to air to allow air to necessary to use a CFD model to confirm the
recirculate past the fans in channels between the effectiveness of the proposal.
fans. It may be necessary to mount a fan in each
channel – although this is often not practical. More CFD modellers should note the importance of
research is needed to study this effect and to properly modelling the structure of the jets issuing
identify whether the problem exists and if so how it from jet fans. Suppliers should note the importance
can best be overcome. of making such details available to modellers.
Simply assuming that the jet from a fan is one-
If the induced velocity at the inlet opening is too dimensional risks being very misleading. CFD
high, the incoming air jet will entrain air inside the modellers should also note the critical importance
car park. This can cause a recirculation pattern of mesh size when modelling flows around beams.
which may bring smoke past the jet fans into the

Fig. 9: Staggered implementation of jet fan lines

65
International Journal on Engineering Performance-Based Fire Codes

Because the impulse system effectively guarantees exit openings in the former are natural openings;
smokelogging in the down stream direction, it is whereas the exhaust from the latter takes the form
important that the system should be fully integrated of an exhaust fan or fans (see Fig. 10 and compare
with other fire protection measures. It has already with Fig. 8). It is usual even in enclosed car parks
been noted that systems should not be initiated for some or all of the incoming air to enter the car
until a safe time after detection which will allow park through natural openings, although systems
people to have evacuated from the car park. This can also be designed with fans supplying air as well
carries an implied need for a good smoke detection as exhausting air and smoke.
system to give warning as early as possible. It also
implies that the alerting process be effective, and The fan exhaust has the effect of making the
compatible with people perhaps being inside well- system much less sensitive to wind pressures, and
soundproofed cars. This suggests the need for eye- reduces or eliminates the need for the system to be
catching flashing lights to draw attention to written designed to be bidirectional depending on wind
messages. In view of the difficulty in driving to direction.
safety, the messages should advise people to
evacuate on foot by the nearest fire exit, leaving The exhaust rate is determined by the capacity of
their cars where they are. the exhaust fans. Conservation of mass means that
the air entering the inlets has an equal mass flow
Protected evacuation stairwells which connect to rate to the exhaust. If we ignore the heating due to
the smokelogged areas of the storey risk permitting a fire, this means that the volume flow rate entering
smoke to enter the stairshaft, perhaps with the the car park storey is equal to the exhaust rate.
leakage rate increased by the local pressure rise due This also implies that the net volume flow rate
to a fan jet directed towards the stairwell door. through the car park storey has this same value –
Even though evacuation should be complete before regardless of what any jet fans are doing inside the
the jet fans start, and even though firefighters storey. In practice, this means that the bulk air
should be directed towards a clear area of the car velocity needed to halt the advance of the
park storey as a part of their approach to the fire, thermally-buoyant ceiling jet beneath the storey’s
caution suggests that doors from the car park to the accent is determined by the exhaust fans, while the
protected shaft should be fitted with smoke seals to jet fans serve to “steer” the air flows within the
minimise any such leakage. storey in order to achieve a more uniform flow and
to achieve the same effect on the ceiling jet
wherever the fire occurs across the width of the
5. IMPULSE VENTILATION IN storey.
ENCLOSED CAR PARKS
The effect of downstand beams, and of excessive
5.1 Comparison with Open-Sided Car airspeeds at air inlets, are the same as for the open-
Parks sided car park storey.

The key difference between an open-sided car park


and an enclosed car park is that the air inlet and air

Fig. 10: Impulse ventilation in an enclosed car park with exhaust fans

66
International Journal on Engineering Performance-Based Fire Codes

It is still necessary to estimate the number of jet form of a recirculation pattern throughout the
fans required for the car storey. The pressure loss storey, causing smoke to affect the areas intended
at the storey inlet is more appropriately considered to be kept clear, or it can take the form of a local
as a part of the exhaust fan’s exhaust duct design recirculation at each fan, which would have less of
calculation, and need not be considered further an adverse effect on the performance of the
herein. Similarly, the pressure losses at the exhaust impulse system. The significance of these
fans’ intakes can be considered as a part of the loss recirculation patterns cannot be assessed by zone-
calculation for the exhaust duct. model methods, but should be revealed by CFD
modelling.
The calculation of the critical ceiling jet velocity,
and hence of the critical bulk air flow rate, is the The ideal design will have the bulk airflow induced
same as detailed in Sections 3 and 4 above. The within the storey equal to the exhaust volume flow
relation between the jet fan specification NVfvf and rate, in which case there should be no opportunity
the momentum in the bulk air flow (equation (4) for adverse recirculation. One can note, however,
above) can be adopted as a first approximation to that the balance point between induced and exhaust
the jet fan specification. This jet fan specification volume flow rates may be changed by changing the
can be expressed as one or more lines of fans numbers of cars in the storey. Research into the
across the desired direction of smoke movement, as significance of this effect would be highly desirable.
discussed in Section 4 above. There will be many
unknown sources of pressure loss, especially when The importance of avoiding excessively fast jets of
there are vehicles present in the car park, and as in air entering the storey through inlets of small area
Section 4 it is desirable to design at least one more is essentially the same as discussed in Section 4
line of fans than calculations indicate. This inherent above. The adverse effect, as in Section 4, is that
uncertainty in these zone model methods makes it entrainment into the air jet inside the inlet can itself
very important that the design should be validated drive a recirculation of smoky air which can
by a thorough CFD model of the storey, and overcome the “steering” effect of the jet fans.
perhaps amended in the light of the results. Note
here that the primary role of the initial zone model- Many enclosed car parks are multi-storey, with
based design is to provide a reasonably-plausible vehicle access ramps connecting the storeys. These
basis for initial discussions, and to reduce the ramps can often result in a complicated pattern of
number, duration, and hence cost of the CFD runs air flows. This can often be used to advantage in
required. providing make-up air naturally into the fire-storey,
although success in integrating this into the overall
5.2 Some Practical Considerations design depends strongly on the actual geometry of
the building.
If the induced bulk air volume flow rate in the
storey is much smaller than the exhaust fan/s It is crucially important that the spread of smoke
volume flow rate, one expects the exhaust to through the car park be restricted; in particular it is
dominate the pattern of air movement within the important that smoke should be prevented from
storey. The effect would be to reduce the spreading through the vehicle access ramps from
effectiveness of the jet fans in creating a uniform one storey to another. The possibility of a fire in a
flow along the storey. This makes it more likely vehicle on one of the ramps must also be
that smoke can move in the undesired direction considered.
where the induced air velocity is locally less than
the critical velocity of the leading edge of the Preventing smoke spread between storeys needs to
ceiling jet. The positive aspect of this is that if the be a primary design objective of the Impulse
inlets and the exhausts are evenly distributed across Ventilation System. In many circumstances, it may
opposite walls of a rectangular-plan storey, and the prove a more convenient option to use a Smoke and
volume flow rate is greater than the critical value, Heat Exhaust Ventilation System (SHEVS) concept
the benefits of impulse ventilation can be obtained to contain buoyant smoke and prevent it moving
with no jet fans at all! Unfortunately, few enclosed into the access ramp area. The design of such a
storeys have such an ideal geometry. SHEVS is outside the scope of this present paper:
we can however note that in a large and complex
If the induced bulk air volume flow rate is greater car park, it may be appropriate to mix several
than the exhaust volume flow rate, the discrepancy different design concepts in different areas
between what is being “pushed” towards the provided that they are complementary and do not
exhaust and what is being removed by the exhaust interfere adversely with each other.
must somehow travel back past the fans to become
available at the fan inlets. This can either take the

67
International Journal on Engineering Performance-Based Fire Codes

6. ACCEPTANCE TESTS OF Ce the dimensioned entrainment constant in the


INSTALLED IMPULSE VENTILA- Large Fire Plume Model, kg m-5/2s-1
TION SYSTEMS d depth below ceiling of a thermally-buoyant
smoke layer, m
Where a full test of the installed system is required D hydraulic mean depth (i.e. effective diameter
to confirm the satisfactory operation of an impulse of a non-circular duct or tunnel), m
system, one can either do an essentially “cold” test g acceleration due to gravity, ms-2
to confirm that all items of the system perform to l length of tunnel having similar cross-section
their individual specifications (which unfortunately and smoothness, m
does not confirm the performance of the system m the subscript m denotes individual lengths of
when there is an actual fire), or one can conduct a tunnel (or duct) having the same cross-
Hot Smoke Test. The latter can either burn a car- section and surface roughness
sized fire, with the inevitable additional repair and M mass flow rate of gases, kg s-1
cleaning costs for the storey, or one can use a Mf mass flow rate of air emitted from the fan
scaled Hot Smoke Test. The use of scaling orifice, Kgs-1
relationships to create the same observed n the subscript n denotes separate obstacles,
performance as an actual full-size design fire but bends, entry, exit or other shape-dependent
without damaging the building, has been developed features such as changes of section
by Morgan and De Smedt [17]. The conclusions N number of fans predicted as the minimum
from their paper can be summarised as follows: necessary for a tunnel or car park storey
P perimeter of fire, m
a) Without adopting a fire tray pattern which Q convective heat flow in the gases due to the
corresponds to the scaling relationships in the fire, kW
gas flows, the observed smoke depths and/or r radial distance from the centre of the
distances travelled by smoke will not axisymmetric plume impinging on a flat
correspond to the design predictions. ceiling, m
T absolute temperature of smoky gases, K
b) Where fans are present, their exhaust velocities T0 absolute ambient temperature, K
need to be altered to conform to the scaling u velocity of leading edge of a “nose” flow
relationships in the gas flows, otherwise the (Hinkley), ms-1
observed smoke depths and/or distances U′ leading edge velocity corrected by Hinkley
travelled by smoke will not correspond to the to allow for higher gas temperatures, ms-1
design predictions. v gas velocity, ms-1
c) Unless scaling is taken into account when v air velocity of air in the tunnel or car park
specifying the hot smoke test fire and any fans
storey, ms-1
involved, the full design performance of a
smoke control system cannot be properly vf velocity of air emitted by a fan, ms-1
assessed. Vair volume flow rate of air in a tunnel or car
d) The exception to a) to c) above is when the park storey, m3s-1
same calculation procedure has been used for Vf volume flow rate of air emitted by a fan,
both the design condition and for the hot m3s-1
smoke test, and is fully appropriate to both W width of a flowing smoke layer, measured
conditions. In this case, a good match between normal to that flow, m
prediction and observation for the hot smoke Y height from the base of the fire to the base of
test gives confidence in the application of the the hot smoke layer, m
calculation procedure to the design condition. ∆p a pressure difference (e.g. impressed by the
momentum of a fan jet), Pa
∆ploss a pressure loss due to either friction or
NOMENCLATURE
turbulent energy losses in the air flow, Pa
Af cross-sectional area of emitting orifice of a ζ a zeta-factor: a shape-dependent factor
fan, m2 relating pressure losses to flow velocity
At cross-sectional area of a tunnel (or, by θ temperature of gases above ambient, K
analogy, of a car park storey), m2 λ friction coefficient
c specific heat of air at constant pressure, kW ρ a gas density, kgm-3
kg-1K-1 ρ0 density of ambient air, kgm-3
C an empirical constant used in Hinkley’s
method for “nose” flows
Cd a discharge coefficient

68
International Journal on Engineering Performance-Based Fire Codes

REFERENCES design”, Fire Safety Journal, Vol. 12, No. 1, pp. 9-


35 (1987).
1. The Building Regulations 2000, Fire safety, 17. H.P. Morgan and J-C. De Smedt, “Hot smoke tests:
Approved Document B, Department of the Testing the design performance of smoke and heat
Environment, Transport and Regions, London, ventilation systems and of impulse systems”,
(2002). FireAsia 2003 “A safe city in motion”, Hong Kong,
26-28 February (2003).
2. H.P. Morgan, B.K. Ghosh, G. Garrad, R.
Pamlitschka, J-C. De Smedt and L.R. Schoonbaert,
“Design methodologies for smoke and heat exhaust
ventilation”, BR 368, CRC, London (1999). WORKED EXAMPLE
3. B.B. Daly, Woods practical guide to fan
engineering, Chapter 13 Ventilation of tunnels and In this example, we look at a simple rectangular car
mines, 6th edition, Woods of Colchester, Colchester, park storey with a flat ceiling. The dimensions are
UK (1992). not intended to represent a fully realistic design,
but are solely intended to illustrate the principles.
4. P.L Hinkley, “The flow of hot gases along an
enclosed shopping mall - A tentative theory”, Fire
Research Note 807, FRS (Now part of BRE, The car park storey is 50 m wide, 75 m long and
Garston, UK) (1970). has a height of 3.20 m. Both of the shorter sides
are open for the full height, through the full width.
5. R. van Beek and G. Dons, “No smoking”, Fire This implies a typical entry coefficient of 0.5, and a
Prevention and Fire Engineers Journal, Vol. 63, pp.
typical exit coefficient of 1.0 by analogy with duct
29-31 (2003).
flows.
6. CIBSE Guide C, Reference data, Section 4 - Flow
of fluids in pipes and ducts, The Chartered Institute The objective is to design an impulse ventilation
of Building Services Engineers, London (2001). system for this car park storey. The design fire has
7. H Ingason and L Romanov, “Use of mobile fans in a convective heat flux of 6 MW and a perimeter of
tunnels”, SP Swedish National Testing and 12 m. This represents a very severe single car fire.
Research Institute, SP Report 2002:06 (2002). For a real case, the design fire has to be chosen
8. J.B. Schleich, L.G. Cajot and D. Joyeux, “Natural very carefully in correspondence to the given
fires in closed car parks”, Eurofire 99, Brussels, circumstances. While dimensioning the jet fan
(1999). installation, we shall assume that this installation
must stop the spread of smoke within 15 m on the
9. G.O. Hansell, “Heat and mass transfer process
“upstream” side of the design fire. The car park
affecting smoke control in atrium buildings”, PhD
Thesis, South Bank University, London (1993). has a flat ceiling which implies a radial spread of
the ceiling jet.
10. E.E. Zukoski, T. Kubota and B. Cetegan,
“Entrainment in fire plumes”, Fire Safety Journal, In the calculation, the following procedure is
Vol. 3, pp. 107 (1981).
applied:
11. J.G. Quintiere, W.J. Rinkinen and W.W. Jones,
“The effects of room openings on fire plume Stage 1: Calculation of r/h
entrainment”, Combustion Science and
Technology, Vol. 26, No. 5-6, pp. 193-201 (1981). r is the radial distance from the centre of the
12. P.H. Thomas, P.L. Hinkley, C.R. Theobald and axisymmetric plume impinging on a flat ceiling,
D.L. Simms, “Investigation into the flow of hot and h is the height of the car parking.
gases in roof venting”, Fire Research Technical
Paper No. 7, London, The Stationary Office (1963). It can be seen from equations (15) and (16) that we
13. P.L. Hinkley, “Rates of production of hot gases in need to identify whether
roof venting experiments”, Fire Safety Journal,
Vol. 10, pp. 57-65 (1986). r
≥ 0.15
14. D.D. Evans, SFPE Handbook of Fire Protection h
Engineering, 2nd edition, Section 2, Chapter 4 -
Ceiling jet flows, The National Fire Protection For the present example,
Association, USA (1995).
15. R.L. Alpert, “Calculation of response time of r = 15 m
ceiling-mounted fire detectors”, Fire Technology, h = 3.20 m
Vol. 8, pp. 181-195 (1972).
From which we obtain:
16. H.P. Morgan and G.O. Hansell, “Atrium buildings:
Calculating smoke flows in atria for smoke control
r/h = 4.7 > 0.15

69
International Journal on Engineering Performance-Based Fire Codes

Example figure: “Chequerboard pattern” jet fans in an open-sided car park

Stage 2: Calculation of the velocity of the ceiling Stage 4: Calculation of the critical volume flow
jet in the car park storey vceiling jet (ms-1) rate through the storey (and the velocity at the
openings)
Because r/h > 0.15 => we must use equation (16):
The critical volume flow rate is just the product of
1 1 the calculated critical velocity (Stage 2 above) and
0.195Q 3 h 2
the cross-sectional area (Stage 3 above).
ν cj = 5
r 6

i.e. Vair = vceiling jet At


For the present example,
For this example,
Q = 6 MW
h = 3.20 m Vair = 0.66 x 160 = 105.6 m3s-1
r = 15 m
Stage 5: Specification of the characteristics of
From which we obtain: the jet fans

vceiling jet = 0.66 ms-1 In practice, the designer must choose between
available fan types and sizes. For this example,
Stage 3: Calculation of the cross-sectional area assume that fans are available with the following
of the car park storey At (m²) characteristics (Note: It should not be assumed that
actually available fans will have these
This means the cross-section at a right angle to the characteristic parameters):
direction of the induced bulk air flow:
Vf is the volume flow rate of air emitted by a fan =
At = bh 1.4 m³s-1, and vf is the velocity of air emitted by a
fan = 14 ms-1.
For the present example,
Stage 6: Calculation of the number of jet fans N
b = 50 m
h = 3.20 m We need to implement equation (10). The local
velocity in the inlet opening is equal to that within
From which we obtain: the storey, because the opening is full height. The
same is true of the exhaust opening. Therefore the
At = 160 m² local velocity at the “obstacle” represented by each
opening is:

70
International Journal on Engineering Performance-Based Fire Codes

Vn = 0.66 ms-1

Provided we can ignore the friction losses, equation


(10) then reduces to:

Nρ o V f v f ρ0 ρ0
= ς inlet v n2,inlet + ζ exhaust v n2,exhaust
At 2 2

i.e.

N1.2 ×1.4 ×14 1 .2 1 .2


= 1.0 × × 0.66 2 + 0.5 × × 0.66 2
160 2 2

i.e. N = 2.7

In practice, one would need to use three jet fans, or


find a different model with more suitable
parameters. In general, increasing the total fan
impulse will increase the safety margins within the
storey.

Further design factors

We can conclude that a total of three jet fans will


create a bulk air movement sufficient to achieve
our objective of stopping the advance of the ceiling
jet of smoky gases by a distance of 15 m upstream
of the central axis of the fire plume. These fans
however, need to be arranged abreast to prevent
smoky gases recirculating around the sides of the
jets. Pressure losses due to friction (and the
presence of cars) are not known and have not been
taken into account. There is also the problem that
each fan’s jet is faster in the centre than at the
edges of the jet, so that a fire between fan jets,
closer than the distance needed for full transfer of
momentum to the bulk air, may travel further than
intended before being stopped. This can be
overcome by putting in an extra row of jet fans,
positioned to cover the gaps between the first line.
See the figure in this example which illustrates the
“chequerboard” pattern that results.

If in reality this extra row is more than needed to


overcome the pressure losses, we note that it
increases the bulk air flow and is thus a
conservative amendment to the design.

________________________
Reproduced by permission of International Fire Consultants Ltd. (IFC) and of N.V. International Fire Safety Engineering
and Technology S.A. (IFSET).

71

You might also like