Results Summary Log

Motor ID Time Temp Resist Megohm DA/PI DC Surge


OT 2471 INGRESO 14/08/2019 20:15:18 -- -- PASS PASS PASS --

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 14/08/2019 20:23:00

Nameplate Information Motor ID OT 2471 INGRESO


Location HUDBAY Building OT 2471 INGRESO
Model Manufacturer
Serial Number HP/KW 0
Volts-Rating 460 Volts-Operating 0
Amps-Rating Amps-Operating 0
Insulation Enclosure
RPM 0 Service Factor 0
Frame Freq-Hz 0
LR Code LR Amps 0
NEMA Design Max Amb °C 0
NEMA nom eff 0 Duty Cycle
Manuf's Type Manuf Dt Cd
Description MOTOR

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 14/08/2019 20:23:00

Nameplate Information Motor ID OT 2471 INGRESO


Location HUDBAY Building OT 2471 INGRESO
Model Manufacturer
Serial Number HP/KW 0
Volts-Rating 460 Volts-Operating 0
Amps-Rating Amps-Operating 0
Insulation Enclosure
RPM 0 Service Factor 0
Frame Freq-Hz 0
LR Code LR Amps 0
NEMA Design Max Amb °C 0
NEMA nom eff 0 Duty Cycle
Manuf's Type Manuf Dt Cd
Description MOTOR

Application Information Test Date/Time 14/08/2019 20:15:18


Test ID Default Repair/Job #
Tested By Tested For
Room # MCC
Location HUDBAY Building OT 2471 INGRESO
Use % Load
Vert/Horiz Starter
Starts/24Hrs Rewind Dt
Install Dt Basic Dt
Volts 1 0,0 Amps 1 0,0
Volts 2 0,0 Amps 2 0,0
Volts 3 0,0 Amps 3 0,0
Tester Type D12R Tester SN 0
Tester ID PP30 SN 0
Cal Date Next Cal Date

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 14/08/2019 20:23:00

Nameplate Information Motor ID OT 2471 INGRESO


Location HUDBAY Building OT 2471 INGRESO
Model Manufacturer
Serial Number HP/KW 0
Volts-Rating 460 Volts-Operating 0
Amps-Rating Amps-Operating 0
Insulation Enclosure
RPM 0 Service Factor 0
Frame Freq-Hz 0
LR Code LR Amps 0
NEMA Design Max Amb °C 0
NEMA nom eff 0 Duty Cycle
Manuf's Type Manuf Dt Cd
Description MOTOR

Results Summary Test Date/Time 14/08/2019 20:15:18


Test ID: Default Repair/Job #
Tested By Tested For
Room # MCC
Location HUDBAY Building OT 2471 INGRESO
Temp Status No Test Performed PI Status PASS
Temp Volts (V) 500
Resist Status No Test Performed DA Ratio 3,1
L1-L2 (Ohms) 0 PI Ratio 2,6
L2-L3 (Ohms) 0 HiPot PASS
L3-L1 (Ohms) 0 Volts (V) 500
Max Delta R % 0,000% Current(µA) 0,01
Coil 1 (Ohms) 0 Resist (Mohm) 48557
Coil 2 (Ohms) 0 Surge Status No Test Performed
Coil 3 (Ohms) 0 Peak Volt(V) L1 0
Megohm Status PASS Peak Volt(V) L2 0
Volts (V) 510 Peak Volt(V) L3 0
Current(µA) 0,04 Max P-P EAR% 0,0%,0,0%,0,0%,
Resist (Mohm) 13170 EAR 1-2,2-3,3-1 --,--,--
Tester Info: ; 0; Cal Dates: -

Report Generated by Baker Instrument Company, An SKF Group Company - MTA


Print Date: 14/08/2019 20:23:00

DA/PI Motor ID OT 2471 INGRESO


Test Date/Time 14/08/2019 20:15:18 Voltage (V) 500
DA Ratio 3,1 PI Ratio 2,6
PI Status PASS

Time (Min) Current(µA) Megohms


0:15 0,09 5955
0:30 0,06 9060
0:45 0,04 11288
1:00 0,04 13170
1:30 0,03 19843
2:00 0,02 25918
2:30 0,02 29022
3:00 0,02 28222
4:00 0,01 38846
5:00 0,01 45357
6:00 0,01 42583
7:00 0,01 >50000
8:00 0,01 >50000
9:00 0,01 >50000
10:00 0,01 33866

Tester Info: ; 0; Cal


Dates: -

Report Generated by Baker Instrument Company, An SKF Group Company - MTA