Abb Ab R BO15-003: Rapport 1/26
Abb Ab R BO15-003: Rapport 1/26
BO15-003.xmcd
ABB AB Rapport
R BO15-003
Report Reg Sida - Page
Från - From Datum - Date
Författare - Author 1/26
PPHB/BOD 2015-02-09 Ordernr - Ref.No.
Ulf Åkesson
Utredning, teoretisk
X undersökning -Analysis,
Godkännare - Approv ed by theoretical investigation
Tom my Borg
Slutrapport
X Final report
Antal textsidor - No of text pages
LTB145D1 24
Load combinations Antal bilagor - No of supplements
2
Breaker type: LTB72,5D1 3-pole FSA
Dim ension print: 1HSBDG00001-329
Zone: 0.5 g according to IEEE 693 2005
________________________________________________________________________________
Sammanfattning - Summary
Load com binations calculation is carried out according to IEC 62155 and IEEE 693 2005.
TThe circuit breaker is equipped with porcelain insulators and ηsupport fram e.
LC1: Design pressure 100%, Mass 100%, Normal wind 30%, Static term inal load 100%
and Impact at operation 100%.
Extrem e load cases:
LC2: Design Pressure 100%, Mass 100%, Ice load 100%, Norm al wind 110%, Static terminal load 100%
and Impact at operation 100%.
LC3: Design Pressure 100%, Mass 100%, High wind 100%, Static terminal load 100%
and Impact at operation 100%.
LC4: Design Pressure 100%, Mass 100%, Short circuit load 100%, Normal wind 100%, Static term inal
load 100% and Im pact at operation 100%.
LC5: Design Pressure 100%, Mass 100%, Earthquake load 100%, Norm al wind 10%, Static terminal
load 100 % and Impact at operation 100 %.
Basic loads:
Horizontal earthquake acceleration 0.5 g Short circuit current 40 kA Norm al wind 34 m/s
Static term inal loads according to IEC Ice 20 mm High wind 46 m/s
Maximum bending moment on the post insulator occurs under short circuit condition and
maximum bending moment on the support frame occurs under earthquake condition:
Calculated Minim um Safety factor Allowed IEEE 693 2005
bending moment failing load Calculated For com bined loads
Nm Nm
M
3 3 1
Breaking chamber M5x = 3.8 ´ 10 M = 11.0 ´ 10 = 2.9 SE = 2.0
1 1 M5x 1
2732 2118-BL 1
M
2
3 3 = 2
Post insulator M4y = 10.0 ´ 10 M = 20.0 ´ 10 M4y SS = 2.0
2 2 2 2
1HSB422732-G
M
3 3 3
Support fram e M5x = 39.2 ´ 10 M = 100.0 ´ 10 = 2.6 SE = 1.5
3 3 M5x 3
1HSB425422-VP 3
Maximum foundation load occurs under earthquake condition:
Bending mom ent Transversal forces Vertical f orce
Nm Direction x N Direction y N N
3 3 3 3
Foundation M5x = 39.2 ´ 10 T5x = 12.8 ´ 10 T5y = 12.1 ´ 10 T5z = 21.3 ´ 10
3 3 3 3
Result:
The breaker is well suited to withstand above specified combined loads.
2
BO15-003.xmcd
Content:
1 Introduction
2 Specification of equipment
4 Load combinations
7 Foundation load
8 Foundation bolts
BO15-003.xmcd
1 Introduction
vh = 46 m /s High wind
t = 20 mm Ice thickness
2 Specification of equipment.
BO15-003.xmcd
2
mtot = 7.1 ´ 10 kgs Total dead weight
3.2 Dead weight from ice load on conductor according to IEC 62271-1
t = 20 mm Thickness of ice
QI := π× éë( Dc + t) - Dc ùû × 10
2 2 -6
× 900× t N/m Ice load
Qicez = 646.9 N Vertical load from ice on term inal of one breaker pole
5
BO15-003.xmcd
3.3 Dead weight from ice load on breaker according to IEC 62271-1
mice =
i = i
1 23.2 Ice on one breaking unit
2 24.1 Ice on one post insulator
3 33.4 Ice on pole beam
4 50.5
Ice on operating m echanism
5 67.7
Ice on one support fram e
p =
1 Breaking cham ber insulator
2 Post insulator
Di = m Inner diameter
p
0.175
0.130
(× Dop)2 + (Dip)2
( p)
π 2
Mdes := Pdes × × Ds
p 32 Do
p
Mdes = 993 Nm Equivalent bending moment on breaking chamber insulator due to design
1
pressure
Mdes = 491 Nm Equivalent bending moment on post insulator due to design pressure
2
6
BO15-003.xmcd
2
Qwx := 0.625× v × A × cc
1 1
2
Qwx := 0.625× v × A × cc
2 2
2
Qwx := 0.625× v × A × cp
3 3
2
Qwx := 0.625× v × A × cp
4 4
2
Qwx := 0.625× v × A × cp
5 5
Qwx = 262 N Load in X direction on one breaking unit due to normal wind
1
Qwx = 217 N Load in X direction on one post insulator due to normal wind
2
BO15-003.xmcd
Qwy = 267 N Load in Y direction on one breaking unit due to normal wind
1
Qwy = 217 N Load in Y direction on one post insulator due to normal wind
2
BO15-003.xmcd
1 ( 1 1)
Mwx := Qwx × h - L
1
Mwx = 173 Nm Bending mom ent in X direction on one breaking unit due to
1
normal wind
Mwx = 697 Nm Bending mom ent in X direction on one post insulator due to
2
normal wind
Mwx = 4460 Nm Bending mom ent in X direction on one support fram e due
3
to normal wind
1 ( 1 1)
Mwy := Qwy × h - L
1
Mwy = 177 Nm Bending mom ent in Y direction on one breaking unit due to
1
normal wind
Mwy = 707 Nm Bending mom ent in Y direction on one post insulator due to
2
normal wind
Mwy = 3813 Nm Bending mom ent in Y direction on one support f ram e due
3
to normal wind
9
BO15-003.xmcd
Qwhx = 479 N Load in X direction on one breaking unit due to high wind
1
Qwhy = 488 N Load in Y direction on one breaking unit due to high wind
1
BO15-003.xmcd
1 ( 1 1)
Mwhx := Qwhx × h - L
1
Mwhx = 317 Nm Bending mom ent in X direction on one breaking unit due to
1
high wind
Mwhx = 1276 Nm Bending mom ent in X direction on one post insulator due to
2
high wind
Mwhx = 8547 Nm Bending mom ent in X direction on one support fram e due
3
to high wind
1 ( 1 1)
Mwhy := Qwhy × h - L
1
Mwhy = 323.1 Nm Bending mom ent in Y direction on one breaking unit due to
1
high wind
Mwhy = 1294 Nm Bending mom ent in Y direction on one post insulator due to
2
high wind
Mwhy = 6920 Nm Bending mom ent in Y direction on one support f ram e due
3
to high wind
11
BO15-003.xmcd
v = 34 m /s Norm al wind
2
Qwno := .625× v × cc × Ac
( 1 1) 2
1
Mwno := Qwno× h - L ×
1
Mwno := Qwno× (h - L )
2 1 2
3
Mwno := Qwno× h ×
3 1 2
BO15-003.xmcd
v = 34 m /s Norm al wind
cc = 0.9 Drag factor, cyli ndrical surface
2
Qwice := .625× v × cc× Ac N Norm al wind load on iced conductor
Qwice = 202.9
( 1 1) 2
1
Mwice := Qwice× h - L ×
1
Mwice := Qwice× ( h - L )
2 1 2
3
Mwice := Qwice× h ×
3 1 2
Mwice = 67.2 Nm Bending mom ent in Y direction on one breaking unit due to
1
normal wind on conductor with ice
Mwice = 422 Nm Bending mom ent in Y direction on one post insulator due to
2
normal wind on conductor with ice
Mwice = 1369 Nm Bending mom ent in Y direction on one support f ram e due
3
to normal wind on conductor with ice
13
BO15-003.xmcd
vh = 46 m /s High wind
2
Qwhno := .625× vh × cc × Ach N High wind load on conductor
Qwhno = 309.5
( 1 1) 2
1
Mwhno := Qwhno× h - L ×
1
Mwhno := Qwhno× ( h - L )
2 1 2
3
Mwhno := Qwhno× h ×
3 1 2
Mwhno = 102 Nm Bending mom ent in Y direction on one breaking unit due to
1
high wind on conductor
Mwhno = 644 Nm Bending mom ent in Y direction on one post insulator due to
2
high wind on conductor
Mwhno = 2088 Nm Bending mom ent in Y direction on one support fram e due
3
to high wind on conductor
14
BO15-003.xmcd
The static terminal load due to weight and type of connection will be added to all load cases.
Static term inal load due to wind and ice are separately calculated in other paragraphs.
Bending mom ent along line due to static term inal load:
( 0 1) + Ftz× Lb
MFthx := Fthx× L - L
1
MFthx = 1964 Nm Bending mom ent in X direction on one breaking unit due to
1
static terminal load
MFthx = 3739 Nm Bending mom ent in X direction on one post insulator due to
2
static terminal load
3
MFthx = 10.140 ´ 10 Nm Bending mom ent in X direction on one support fram e due to
3
static terminal load
( 0 1)
MFthy := Fthy× L - L
1
MFthy := Fthy× ( L - L )
2 0 2
3
MFthy := Fthy× L ×
3 0 2
MFthy = 1025 Nm Bending mom ent in Y direction on one breaking unit due to
1
static terminal load
MFthy = 2090 Nm Bending mom ent in Y direction on one post insulator due to
2
static terminal load
MFthy = 5855 Nm Bending mom ent in Y direction on one support fram e due to
3
static terminal load
15
BO15-003.xmcd
The bending mom ent at the support frame and bottom of post insulator due to operational impact
is added to all load com binations.
Fyimp = 1000 N Horizontal force at operation
a := 1 Support factor
(
Lsc := L - L
0 1 ) + Lb×2 + Lc×2 m Interrupter length and part of conductor length
2
Isc
Fscy := 0.2 × K× × a× Lsc N Electromagnetic force on equipm ent
Lph
Fscy = 2818
(
Mscy := Fscy× hsc - L
1 1)
Mscy = 1865 Nm Bending mom ent in X direction on one breaking unit due to
1
short circuit load
Mscy = 5866 Nm Bending mom ent in X direction on one post insulator due to
2
short circuit load
16
BO15-003.xmcd
Feh := ahr × m
i i
Fev := avr × m
i i
Meh := Feh × h - L
1 1 (1 1 )
Meh := Feh × h - L
2 1 (1 2 ) + Feh2×(h2 - L2)
2
æ Feh × h × 3 ö +
4 æ Fehi × hi ö
Meh :=
3 å ç i i 2÷
è ø å ç
è 2 ø
÷ + Feh5× h5
i=1 i=3
BO15-003.xmcd
4 Load combinations
(
T1y := Qwy + Qwno × 0.3 + Fthy
1 1 )
T1y := T1y + Qwy × 0.3
2 1 2
3 æ Qwy + Qwy 3 4 ö
T1y := T1y × + ç + Qwy ÷ × 0.3 + Fyimp
3 2 2
è 2 ø
5
1 (
M1y := Mdes + Mwy + Mwno × 0.3 + MFthy
1 1 1 ) 1
2 (
M1y := Mdes + Mwy + Mwno × 0.3 + MFthy + Mimp
2 2 2 ) 2
3 (
M1y := Mwy + Mwno × 0.3 + MFthy + Mimp
3 3 ) 3
BO15-003.xmcd
3 æ Qwx + Qwx 3 4 ö
T2x := T2x × + ç + Qwx ÷ × 1.1
3 2 2
è 2 ø
5
(
T2y := Qwy + Qwice × 1.1 + Fthy
1 1 )
T2y := T2y + Qwy × 1.1
2 1 2
Qwy + Qwy
3 æ 3 4 ö
T2y := T2y × + ç + Qwy ÷ × 1.1 + Fyimp
3 2 2
è 2 5
ø
1 (
M2y := Mdes + Mwy + Mwice × 1.1 + MFthy
1 1 1 ) 1
2 (
M2y := Mdes + Mwy + Mwice × 1.1 + MFthy + Mimp
2 2 2 ) 2
3 (
M2y := Mwy + Mwice × 1.1 + MFthy + Mimp
3 3 ) 3
1 (
T2z := m + mice × 9.81 + Qicez + Ftz
1 1 )
T2z := T2z + m + mice × 9.81
2 1 ( 2 2 )
4 é ( mi + micei ) × 9.81ù
ú + ( m5 + mice5) × 9.81 + Fzimp
å
3
T2z := T2z × + ê
3 2 2
ë 2 û
i=3
19
BO15-003.xmcd
BO15-003.xmcd
BO15-003.xmcd
1 (
T5y := Qwy + Qwno × 0.1 + Fthy× 0.7 + Feh
1 ) 1
é 2 æ Qwyi × 3 ö 4 Qwy ù
ê + Qwy + Qwnoú × 0.1 + Fthy× 0.7 ...
å å
i
T5y := ç ÷ +
3 ê è 2 ø 2 5 ú
ëi = 1 i=3 û
2
é 2 æ Fehi × 3 ö 4 Feh ù
+ ê + Feh ú + Fyimp
å å
i
ç ÷+ 2
ê è 2 ø 2 5ú
ëi = 1 i= 3 û
Bending moment [X direction]:
M5x := Mdes + Mwx × 0.1 + MFthx × 0.7 + Meh
1 1 1 1 1
1 (
M5y := Mdes + Mwy + Mwno × 0.1 + MFthy × 0.7 + Meh
1 1 1 ) 1 1
2 2 (
M5y := Mdes + Mwy + Mwno × 0.1 + MFthy × 0.7 +
2 2 ) 2 (Meh2)2 + Mimp2
3 (
M5y := Mwy + Mwno × 0.1 + MFthy × 0.7 +
3 3 ) 3 (Meh3)2 + Mimp2
Vertical loads [Z direction]:
T5z := m × 9.81 + Ftz× 0.7 + Fev
1 1 1
é 2 æ mi × 3 ö 4 æ mi ö ù
ê ç ÷ + m5ú × 9.81 + Ftz× 3 × 0.7 ...
T5z :=
3 ê å ç
è 2 ø
÷+ å è2 ø ú 2
ëi = 1 i=3 û
2
é 2 æ Fevi × 3 ö 4 Fev ù
ê + Fev ú + Fzimp
å å
i
+ ç ÷ +
2
ê è 2 ø 2 5ú
ëi = 1 i=3 û
22
BO15-003.xmcd
BO15-003.xmcd
3
M = 11.0 ´ 10 Nm Minim um value of breaking cham ber insulator and top of post insulator
1
3
M = 20.0 ´ 10 Nm Post insulator 1HSB422732-G
2
3
M = 100.0 ´ 10 Nm Support fram e 1HSB425422-VP
3
Norm al Ice High Short- Earth- Norm al Ice High Short Earth
wind wind circuit quake wind wind circuit quake
M M M M M
k k k k k
= = = = = SN := SI := SH := SS := SE :=
k= M1x M2x M3x M4x M5x k k k k k
k k k k k
1 3.7 3.5 3.4 5.1 2.9 2.1 1.2 1.2 2.0 2.0
2 4.5 4.0 3.6 6.5 2.2 2.1 1.2 1.2 2.0 2.0
3 8.7 6.6 5.4 10.5 2.6 1.5 1.2 1.2 1.5 1.5
Norm al Ice High Short- Earth- Norm al Ice High Short- Earth
wind wind circuit quake wind wind circuit quake
M M M M M
k k k k k
= = = = = SN := SI := SH := SS := SE :=
k= M1y M2y M3y M4y M5y k k k k k
k k k k k
1 5.3 4.8 4.5 3.1 3.4 2.1 1.2 1.2 2.0 2.0
2 4.5 3.8 3.3 2.0 2.5 2.1 1.2 1.2 2.0 2.0
3 11.3 7.7 6.1 10.7 2.8 1.5 1.2 1.2 1.5 1.5
24
BO15-003.xmcd
3 3 3 3 3
LC2 T2z = 23.2 ´ 10 T2x = 3.7 ´ 10 T2y = 4.1 ´ 10 M2x = 15.0 ´ 10 M2y = 13.1 ´ 10
3 3 3 3 3
3 3 3 3 3
LC3 T3z = 20.5 ´ 10 T3x = 5.0 ´ 10 T3y = 5.2 ´ 10 M3x = 18.7 ´ 10 M3y = 16.4 ´ 10
3 3 3 3 3
3 3 3 3 3
LC4 T4z = 19.7 ´ 10 T4x = 2.6 ´ 10 T4y = 7.5 ´ 10 M4x = 9.5 ´ 10 M4y = 9.4 ´ 10
3 3 3 3 3
3 3 3 3 3
LC5 T5z = 21.3 ´ 10 T5x = 12.8 ´ 10 T5y = 12.1 ´ 10 M5x = 39.2 ´ 10 M5y = 36.3 ´ 10
3 3 3 3 3
8 Foundation bolts.
Maximum load on support frame foundation bolts:
Tz := Tx := Ty := Mx := My :=
i i i i i
Axial loads [N] Axial stress [N/m m 2] Shear stress X [N/mm 2] Shear stress Y [N/m m 2]
Faz :=
Tz
i
+
(
max Mx , My
i i ) σz :=
Faz
i
τx :=
Tx
i
τy :=
Ty
i
i 4 2× db i 352.490 i π 2 i π 2
× 21.185 × 21.185
4 4
Faz = σz = τx = τy =
i i i i
19.5·103 55.2 6.8 7.5
24.6·103 69.8 10.6 11.5
28.5·103 80.8 14.1 14.8
16.8·103 47.8 7.5 21.3
54.3·103 N 154.2 N/m m 2 36.4 N/m m 2 34.2 N/m m 2
Equivalent stress:
σe :=
i (σzi)2 + 3×éë(τxi)2 + (τyi )2ùû
match( max( σe) , σe) = ( 5 ) Load case that yields the highest load on foundation bolts
For size M24 foundation bolts a material with yield point larger than se shall be used.
25
BO15-003.xmcd
26
BO15-003.xmcd