Professional Documents
Culture Documents
It
is in parallel with another identical generator having isolated neutral. Each generator has
a positive sequence reactance of 20%, negative sequence reactance of 10% and zero
sequence reactance of 15%. If a line to ground short circuit occurs in the common bus-
bar, determine the fault current.
Solution: Fig 1 shows the two generators in parallel. The generator 1 has its neutral earthed
through a reactance (=5%) whereas generator 2 has ungrounded neutral. The earth fault is
assumed to occur on the red phase. Taking red phase as the reference, its phase e.m.f.
ER=11×103/√3=6351V. For a line to ground fault, the equivalent circuit will be as shown in