TEST REpoRT of transformer

Client : MEIL
Station : 400/220 kV S/s.-PODILI
Designation : TRANSFORMER
Report Date : 20THAUGUST 2018

Contact Person: Dr. Aradhana Ray


Designation : Engineering Consultant
Contact Details: Ph- +918000645964, GSM: +91-9374076950,
Email: lxassociates@gmail.com, web: www.laxmiassociates.in

1
Laxmi Associates,
Sun Enclave, Office no: 13, 14, 15
Opposite Sun city Paradise,
Manjalpur, Vadodara-390020
Email: lxassociates@gmail.com
Http: www.laxmiassociates.in

Report Title : Test Report of Breaker

Station : 400/220 kV S/s.-PODILI

Client : MEIL

Location : PODILI – ANDHRA PRADESH

Equipment Designation : TRANSFORMER

Report Submitted to : Electrical Maintenance Department

Tested on : 20/08/2018

Report Date : 10/09/2018

Tested By : DHARMENDRA

Tested by Report Reviewed by

VIJAY PAL Dr. Aradhana Ray


Testing & Commissioning Engg EngineeringConsultant

PURPOSE OF DISTRIBUTION:

This document is distributed to ISHITA ENTERPRIES-JAMKHANDI for their own


commercial and maintenance purposes. Rights to copy or distribute this document are
only granted for the stated purpose. The document may not otherwise be used or
distributed without the prior written permission of Laxmi Associates.

2
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

Contents

1.0. Background…………………………………………………… 4
2.0. Scope of work………………………………………………………... 4
3.0. Reference………………………………………………………......... 4
4.0. Instrument used……………………………………………………... 4
5.0. Details ofTest & Analysis Report…………………………………… 7
5.1.1. Tanδ And Capacitance Measurement of Winding………7
5.1.2. Insulation Resistance Measurement………………………7
5.1.3. Magnetizing Current Test……………………………………8
5.1.4. Turn Ratio Test………………………………………….....8
5.1.5. Magnetic Balance Test……………………………………....9
5.1.6. Winding Resistance Measurement……………………9
5.1.7. Vector Group Test……………………………………..10

3
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

1. Executive Summary:

As a part of preventive maintenance activities activities 400/220 kV S/s. PODILI has decided
to carry out offline testing on their Transformer.

For the stated purpose MEIL – PODILI appointed Laxmi Associates as service provider. The
detailed test results and analysis are given in this document.

2. Scope of work:

Carry out diagnostic testing on transformers and submit a detailed test report.

3. Reference:

The condition of power transformer evaluated in reference with the following standards
and publications.

IS 3156-4 (1992) is applicable to transformers for use with electrical measuring


instruments.

4. Instruments used:

Calibration
Sl. No Instrument Make Sr. No.
Date
1 CPC 100 Omicron SE639Y 05-08-2018
2 IR tester Fluke 3616028 09-01-2018
3 MultiMeter Fluke 40010307WS 08-01-2018
4 Leakage Meter Meco 14020362 26-11-2017

4
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

TesT RePORT of transformer

5
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

Contact person
Name Mr.
Phone No. 1 --
E-mail --

Transformer nameplate data


Serial number 2183208 Apparatus ID Distribution Transformer
Manufacturer Toshiba Transformer Rating 630 KVA, 33/0.415 kV
Phase 3 Vector Group Dyn11
Rated Current 11.022/876.459 A Cooling Type ONAN

Global test conditions


Weather Clear Humidity 74%
Unit location Outside Air Temp 44°C

6
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

5. Details of Test Results and Analysis:

5.1.1 Tan Delta And Capacitance Measurement Of Winding

Test Factory Factory


Capacitance Tanδ
Combination Mode Voltage Capacitance Tanδ
(nF) (%)
(kV) (nF) (%)
2 2.2312 - 0.5340 -
HV/LV UST 5 2.2311 - 0.5346 -
10 2.2312 - 0.5358 -
2 0.98771 - 0.7924 -
HV/ ground with LV
GST-g 5 0.98774 - 0.7985 -
Guard
10 0.98777 - 0.7995 -
2 3.2189 - 0.6142 -
HV/LV+Ground GST 5 3.2190 - 0.6151 -
10 3.2190 - 0.6193 -
0.1 2.2317 - 0.5348 -
UST
LV/HV 0.2 2.2318 - 0.5390 -
0.1 4.4184 - 0.7810 -
LV/HV+Ground GST-g
0.2 4.4190 - 0.7870 -
LV/ground with HV 0.1 6.6467 - 0.6320 -
GST
Guard 0.2 6.6492 - 0.6318 -

5.1.2 Insulation Resistance Measurement

APPLIED IR Value(in GΩ)


Connection
VOLTAGE 15 Sec 60 Sec 600 Sec DAI PI
HV/E 5 kV 3.28 4.38 7.49 1.335 1.710
LV/E 250 V 1.21 1.67 2.90 1.380 1.736
HV/LV 5 kV 4.20 5.80 9.40 1.380 1.620

7
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

5.1.3 Magnetization Current Test


APPLY ON HV SIDE
VOLTAGE APPLIED IN VOLTS MEASURED CURRENT (mAMPS)
TAP NO.
1U – 1V 1V – 1W 1W – 1U 1U 1V 1W
- 251.3 253.1 253.8 0.30 0.41 0.28

APPLY LV SIDE
VOLTAGE APPLIED IN VOLTS MEASURED CURRENT (mAMPS)
TAP NO.
2U – 2V 2V – 2W 2W –2U 2U 2V 2W
- 248.1 251.0 247.6 3.68 2.96 3.86

5.1.4 Voltage Ratio Test (Turn Ratio)

Voltage Ratio
TA
MEASURED RATIO % ERROR
P CALCULATED
NO. 1U–1V/ 1V–1W/ 1W–1U/ RATIO U V W
2U–2N 2V–2N 2W–2N
1 144.618 144.690 144.740 146.114 0.969 0.975 -0.941
2 141.148 141.229 141.268 141.005 -0.101 -0.159 0.186
3 137.687 137.780 137.815 137.566 -0.088 -0.155 0.181
4 134.137 134.320 134.360 134.127 -0.007 -0.144 0.174
5 130.777 130.860 130.898 130.688 -0.068 -0.132 0.161
6 127.308 127.388 127.439 127.249 -0.047 -0.109 0.149
7 123.857 123.929 123.975 123.810 -0.038 -0.096 0.134

8
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

5.1.5 Magnetic Balance Test

APPLY 415 V SUPPLY ON HV SIDE


VOLTAGE APPLIED IN VOLTS VOLTAGE MEASURED IN VOLT
TAP NO.
1U – 1V 1V – 1W 1W – 1U 2U – N 2V –N 2W – N
251.3 108.6 57.8 248.1 161.9 90.2
3 104.9 253.1 96.1 123.6 251.0 127.3
56.3 132.8 253.8 89.1 168.0 247.6

5.1.6 Measurement of Winding Resistance : (Results in mΩ)

HV Side

TAP WINDING RESISTANCE IN mΩ


NO. 1U-1V 1V-1W 1W-1U
1 13770 13736 13749
2 13434 13394 13419
3 13100 13050 13077
4 12763 13711 12740
5 12430 12368 12410
6 12090 12041 12068
7 11741 11700 11732

LV Side

TAP WINDING RESISTANCE IN mΩ


NO. 2U-N 2V-N 2W-N
1 4.220 4.160 4.180

9
Test Report of Transformer

Client MEIL Reason of the job Routine Maintenance


Tested By DHARMENDRA Location PODILI, A.P.
Approved by Dr. Aradhana Ray Tested date 20/08/2018
Apparatus ID Transformer Connection symbol Dyn11
Asset serial
number 2183209 Type of Cooling ONAN

5.1.7 Vector Group Test

Vector group- Dyn11


Measured Voltage in
Connection CONDITION
(Volts)
1U-2U terminals shorted
1U-1V 432.0
1V-1W 439.0
1W-1U 437.2
1V-2V 428.1
1V-2W 428.3
1) 1V-2V=1V-2W As all condition are verified,
Vector Group Dyn11
1W-2V 438.9
conformed.
1W-2W 431.7
2) 1W-2V>1W-2W
1V-N 429.1
2U-N 3.5
1U-1V 432
3) (1V-N)+(2U-N)=1U-1V

Please contact us in case of any further query regarding this report.


Thanking you,
For & on behalf of Laxmi Associates

Dr. Aradhana Ray


E-mail:rayaradhana@yahoo.com, Mobile No.09374076950
Laxmi Associates (Engineering consultancy & Service Provider)
Sun Enclave, Office No. 13-14-15, Near Suncity Paradise, Manjalpur, Vadodara-390 020
http://www.laxmiassociates.in/09376446909 / 09376446910

END OF REPORT