Professional Documents
Culture Documents
June 2007
The Onyx - Dubai Structural Concept Design Report
Contents
7.0 Appendix
June 2007
The Onyx - Dubai Structural Concept Design Report
The Onyx is the key entry site into the Greens community and one of the biggest sites for
development by Zahran. The objective is to develop the site as a mixed use facility
incorporating office, hotel and retail to maximize the view of the land.
The land area subject to survey is 22, 032 sq-m [237, 363 sq-ft] with a water table
approximately 1.5m below the surface [to be confirmed by Geotechnical Engineer].
The progression of the lateral load resisting schemes from elemental beam and column
assemblages toward the notion of an equivalent vertical cantilever is fundamental to any
structural systems methodology. While the structural schemes must address the
preeminent focus on the lateral load resistance, the load carrying function of the tall
building subsystems is rarely independent. The most efficient tall building systems fully
engage vertical gravity load resisting elements in the lateral load subsystems in order to
reduce the overall structural premium for resisting lateral loads. Some degree of
independence is generally recognized between the floor framing systems and the lateral
load resisting systems, although the integration of these subassemblies into the overall
structural organization is crucial.
June 2007 `1
The Onyx - Dubai Structural Concept Design Report
The floor layout and spans of the building are such that reinforced concrete columns,
shear walls and PT flat slab with perimeter PT beams seems like an efficient structural
system for floor slabs.
The Podium and Basements are having very large Plan area; due to huge area on these
floors; there will be many construction stages if having PT slabs which will reduce
construction speed. Whereas RC band beam system is best suited in these conditions
All the six options shall be appraised for the floor system based on the importance of a
particular parameter which varies from 1 to 3, 3 being the most important, and the points
scored by a particular parameter shall be weighted with respect to their importance. The
results shall be presented in a matrix format, sample sheet attached for reference. The
matrix shall consider the following main issues:
1. Constructability
2. Structural Efficiency
3. Program
4. Cost
The structural scheme which scores maximum and gives the optimum solution shall be
adopted.
June 2007 `2
The Onyx - Dubai Structural Concept Design Report
The lateral load resisting system shall consist of reinforced concrete shear walls located
preferably in the core areas to resist the overturning due to wind and seismic loads.
The shear walls shall continue down to the lowest basement level and shall be supported
on raft. Similarly, columns are supported on raft.
The raft covering the entire footprint of tower structures shall be supported on bored piles
based on the load carrying capacity determined by geotechnical investigation contractor.
Podium structure shall most likely be supported on individual pile caps.
To obtain the maximum pile design forces at service load level, the ETABS static analysis
shall be performed for various loading combinations involving gravity, wind and seismic
loads as given in design criteria.
Three Towers with the portion of Some Podium areas are separated by the Expansion
Joints. One of the EJ will be run near Grid-8 terminating on other EJ near Grid-F from
ground floor level. However there will be no movement joints below ground floor level.
The structure below ground floor level shall be designed to accommodate shrinkage
stresses using additional reinforcement.
The basement, including the depth of the foundation, extends into the design water table.
In order to prevent the ingress of ground water, the base slab and perimeter walls shall
be designed as water retaining structures. Construction joints will include water stops
with hydrophilic tips to prevent the ingress of water. The effective construction of water
retaining concrete structures is heavily dependent on the quality of workmanship on site.
A waterproof membrane shall be installed on the underside of the base slab and the
external face of the perimeter walls to protect further the basement against the ingress of
ground water. The membrane is additionally required to protect the reinforced concrete
structure against attack from sulfates and chlorides in the ground water. Within the
specification, assurances will be required from the Contractors that the waterproofing
products are compatible with each other.
This project requires temporary shoring to be installed during the construction stage. The
shoring is proposed to be RC diaphragm wall approximately 600mm anchored at a
design height on all four sides of the plot. The design and construction of the diaphragm
wall shall be the responsibility of the shoring specialist contractor.
June 2007 `3
The Onyx - Dubai Structural Concept Design Report
6.2.1 Concrete: Normal weight concrete having density of 2400 kg/m3 with 28-day
cube compressive strengths as follows:
1. Slabs-on-grade and grade beams = 40 MPa
2. Concrete Piles: = 50 MPa
3. Foundations and Pile Caps = 50 MPa
4. Suspended Slabs and Beams: = 50 MPa
5. Columns and RC Walls: = 40-60 MPa
6. Water Tank walls, top and base slab = 50 MPa
GRADES OF CONCRETE
Concrete Cube strength fcu
Nomin Min. Max. Max.
Grade
al Size Cementitiou Cementitio free
Per BS 7 day
of Agg. s Content us Content W/C 28 day
5328 N/mm
mm Kg/m3 Kg/m3 Ratio 2 N/mm2
C50 20 400 450 038 39 50
C40 20 400 450 0.38 36 40
C35 20 380 420 0.40 28 35
C20 20 250 300 0.65 14 20
*fcu = minimum cube compressive strength of concrete, MPa
June 2007 `4
The Onyx - Dubai Structural Concept Design Report
1.5% Max.
Water Absorption Substructure Bs 1881:
11.
(C35,C40,C50) Part 122
Superstructure 2.0% Max.
Substructure 0.15 ml/m2/sec
ISAT (10 minutes) Bs 1881:
13. 0.30 ml/m2/sec
(C35, C40, C50) Superstructure Part 208
Chloride Content/Cementitious 0.20%
15.
(C35 , C40, C50) Bs 1881:
SO3 Content/Cementitious Part 124 4%
16.
(C20, C35, C40, C50)
QUALITY CONTROL
17. Standard Deviation Strength ACI 214 4 Mpa
Notes:
a. The Engineer may permit a higher slump if super plasticizer is
added.
b. Average unit weight shall be established during plant trials.
c. Values for water permeability and RCP are at 28 days.
d. Massive Concrete shall be defined as any concrete element that
has both plan and cross sectional dimensions exceeding 1.2
meters and containing a total volume exceeding eight cubic
meters.
e. Maximum concrete core temperature due to the cement hydration
June 2007 `5
The Onyx - Dubai Structural Concept Design Report
A. Wind Loads:
June 2007 `6
The Onyx - Dubai Structural Concept Design Report
B. Seismic Loads
B. Working stress design for pile loads only based on ASCE 7 - 2002
1. 1.0(D+SDL)+1.0L
2. 1.0(D+SDL)+/-1.0W
3. 1.0(D+SDL)+/-0.7E
4. 1.0(D+SDL)+0.75L+/-0.75W
5. 1.0(D+SDL)+0.75L+/-0.54E
6. 0.6(D+SDL)+/-W
7. 0.6(D+SDL)+/-0.7E
All architectural finishes, including partitions and exterior wall elements, and also
mechanical/electrical/plumbing elements, shall be constructed to accommodate
the following anticipated structural movements/deflections.
B. Lateral Deflections
The building structure is anticipated to move laterally in the each direction
with a story drift limitations shall comply with clause 1630.10 of UBC 1997.
June 2007 `7
The Onyx - Dubai Structural Concept Design Report
A single 3-D response spectrum analysis model of the structure or three different models
for each portion separated by the expansion joint will be developed on ETABS computer
for analysis and design of the superstructure. This model shall include columns, shear
walls, beams on the perimeter of floors, with or without raft and piles represented as
springs. Floor slabs are not assumed to participate in lateral load resistance for
conservatism and simplicity in model preparation. The single model shall be extended
down to the lowest basement level below which raft and vertical member connection will
defined as fixed connection. For individual models the Towers will be defined fixed at
Ground floor. The reactions from these models will be applied on another ETABS model
which comprise of complete floor area having no expansion joint from Basement -2 to
Ground Floor.
A finite element plate analysis using SAFE for RC slabs and ADAPT for PT slabs shall be
created and analyzed for various critical load combinations to investigate strength and
serviceability behavior of the floor slabs. PT slabs shall be designed by the PT specialist
contractor who will have to comply with the design criteria for the project.
All the project design calculations and drawings shall be reviewed as per company’s
QA/QC system.
Verification of loads, forces and moments will be done by tributary area method and long
hand calculations as part of KEO’s quality checking system.
June 2007 `8
The Onyx - Dubai Structural Concept Design Report
7.0 Appendix
June 2007