College of Engineering
APPENDIX A
Ground Floor Cooling Load Calculation
1.1 Room 1
CLTDsel @ Table B: Cooling Load Temperature Difference for sunlit walls
SE: CLTDsel = 20
LM@ Table C ∶ Correction Factor For Latitude and Month applied Walls and Roofs
Latitude ∶ 14 (May)
SE: LM = −2.77
Computation for External Wall
W
SE: Qwall = (2.5094 ) (26.3m × 6m)(19.23) = 7614.7592 W
m2 . K
𝐐𝐬 = 𝟕𝟔𝟏𝟒. 𝟕𝟓𝟗𝟐 𝐖
1.2 Room 3
CLTDsel @ Table B: Cooling Load Temperature Difference for sunlit walls
SW: CLTDsel = 25
SE: CLTDsel = 20
NE: CLTDsel = 15
LM@ Table ∶ Correction Factor For Latitude and Month applied Walls and Roofs
Latitude ∶ 14 (May)
SW: LM = −2.77
SE: LM = −2.77
NE: LM = 1.66
Computation for External Wall
W
SW: Qwall = (2.5094 ) (5.9m × 6m)(24.23) = 2152.4178 W
m2 . K
W
SE: Qwall = (2.5094 2 ) (3.7m × 6m)(19.23) = 1071.2779 W
m .K
W
NE: Qwall = (2.5094 2 ) (3.7m × 6m)(19.23) = 1398.5716 W
m .K
Qs = 2152.4178 W + 1071.2779 W + 1398.5716 W
𝐐𝐬 = 𝟒𝟔𝟐𝟐. 𝟐𝟔𝟕𝟑 𝐖
1.3 Room 4
CLTDsel @ Table B: Cooling Load Temperature Difference for sunlit walls
SE: CLTDsel = 20
LM@ Table C: Correction Factor For Latitude and Month applied Walls and Roofs
Latitude ∶ 14 (May)
SE: LM = −2.77
1.4 Room 5
CLTDsel @ Table B: Cooling Load Temperature Difference for sunlit walls
SE: CLTDsel = 20
SW: CLTDsel = 25
LM@ Table C: Correction Factor For Latitude and Month applied Walls and Roofs
Latitude ∶ 14 (May)
SE: LM = −2.77
SW: LM = −2.77
1.5 Room 6
CLTDsel @ Table B: Cooling Load Temperature Difference for sunlit walls
SE: CLTDsel = 20
SW: CLTDsel = 25
NW: CLTDsel = 21
LM@ Table C: Correction Factor For Latitude and Month applied Walls and Roofs
Latitude ∶ 14 (May)
SE: LM = −2.77
SW: LM = −2.77
NW: LM = 1.66
2. Glass Loads
Qglass = QSG + QTH
Where: QSG = (SHGF)(SC)(Aglass )(CLF)
QTH = (Uglass )(Aglass )(CLF)
Uglass wall @ Table ∶ Clear Glass U Values
Uglasswall = 2.54 for IGU Argon Insulating glass with 6mm × 12mm × 6mm,
double glass
Uglassdoor @ Table ∶ Resistance of Building Materials
Uglassdoor = 3.5 for Summer
2.1 Room 1
External Glass wall
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NE: SHGF = 530 (May @ 32° North Latitude
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Reflective
NE: SC = 0.3 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NE: CLF = 0.76
Door
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NE: SHGF = 530 (May @ 32° North Latitude
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Regular Sheet
NE: SC = 0.90 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NE: CLF = 0.76
2.2 Room 2
External Glass wall
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NE: SHGF = 530 (May @ 32° North Latitude)
NW: SHGF = 530 (May @ 32° North Latitude)
SW: SHGF = 480 (May @ 32° North Latitude)
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Reflective
NE: SC = 0.3 (no indoor shading)
NW: SC = 0.3 (no indoor shading)
SW: SC = 0.3 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NE: CLF = 0.76
NW: CLF = 0.82
SW: CLF = 0.83
Door
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NE: SHGF = 530 (May @ 32° North Latitude)
NW: SHGF = 530 (May @ 32° North Latitude)
2.3 Room 3
External Glass wall
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NW: SHG = 530 (May @ 32° North Latitude)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NW: CLF = 0.82
Door
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NW: SHGF = 530 (May @ 32° North Latitude)
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Regular Sheet
NW: SC = 0.90 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NW: CLF = 0.82
2.4 Room 4
External Glass wall
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NW: SHGF = 530 (May @ 32° North Latitude)
SW: SHGF = 480 (May @ 32° North Latitude)
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Reflective
NW: SC = 0.3 (no indoor shading)
SW: SC = 0.3 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NW: CLF = 0.82
SW: CLF = 0.83
Door
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NW: SHGF = 530 (May @ 32° North Latitude)
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Regular Sheet
NW: SC = 0.90 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NW: CLF = 0.82
2.5 Room 5
External Glass wall
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NW: SHGF = 530 (May @ 32° North Latitude)
SW: SHGF = 480 (May @ 32° North Latitude)
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Reflective
NW: SC = 0.265 (Venetian blinds, medium)
SW: SC = 0.265 (Venetian blinds, medium)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NW: CLF = 0.82
SW: CLF = 0.83
2.6 Room 6
Door
SHGF @ Table D: Maximum Solar Heat Gain factor for sunlit glass
NW: SHGF = 530 (May @ 32° North Latitude)
SW: SHGF = 480 (May @ 32° North Latitude)
SC @ Table E: Shading Coefficient
Type ofGlass: Double Glass, Regular sheet
NW: SC = 0.9 (no indoor shading)
SW: SC = 0.9 (no indoor shading)
CLF @ Table F: Cooling Load Factors for glass with interior shading, North Latitude
NW: CLF = 0.82
SW: CLF = 0.83
Computation for Solar Heat Gain
NW: QSG = (530)(0.9)[(2)(2)(2.6m × 1m)](0.82) = 4067.856 W
SW: QSG = (480)(0.9)(2)(2)(2.6m × 1m)(0.83) = 3729.024 W
QSG = 4067.856 W + 3729.024 W = 7796.88 W
25 − 24 Psat − 2.982
=
26 − 24 3.360 − 2.982
Psat = 3.171 kPa
0.622Pv
ωi =
Patm − Pv
0.622(3.171 kPa)(0.55)
ωi =
101.325 kPa − (3.171 kPa)(0.55)
𝛚𝐢 − 𝟎. 𝟎𝟏𝟎𝟖𝟗 𝐤𝐠/𝐤𝐠
27 − 26 Psat − 3.360
=
28 − 26 3.778 − 3.360
Psat = 3.569 kPa
0.622Pv
ωo =
Patm − Pv
0.622(3.569 kPa)(0.60)
ωo =
101.325 kPa − (3.569 kPa)(0.60)
𝛚𝐨 = 𝟎. 𝟎𝟏𝟑𝟒𝟑 𝐤𝐠/𝐤𝐠
1. Room 1
Infiltration due to outside air
Qinf = [a + b(vwind ) + c(t o − t i )] × volume
Qinf = [0.150 + 0.010(2.5 m/s) + 0.007(34 − 25)] = 0.238
V = [(22.5 × 26.3) + (3.2 × 15) − (3.1 × 6.4) − (3.2 × 4.1)] × (6m) = 3640.74 m3
Qinf = 0.238(3640.74 m3 )
𝐐𝐢𝐧𝐟 = 𝟖𝟔𝟔. 𝟒𝟗𝟔𝟏 𝐋/𝐬
2. Room 2
Infiltration due to outside air
Qinf = [a + b(vwind ) + c(t o − t i )] × volume
Qinf = [0.150 + 0.010(2.5 m/s) + 0.007(34 − 25)] = 0.238
V = [(18 × 26.3) − (3.2 × 4.1)] × (6m) = 2761.68 m3
Qinf = 0.238(2761.68 m3 )
𝐐𝐢𝐧𝐟 = 𝟔𝟓𝟕. 𝟐𝟕𝟗𝟖 𝐋/𝐬
3. Room 3
Infiltration due to outside air
Qinf = [a + b(vwind ) + c(t o − t i )] × volume
Qinf = [0.150 + 0.010(2.5 m/s) + 0.007(34 − 25)] = 0.238
V = [(14.3 × 15.1) − (5.9 × 3.7) − (3.2 × 4.1)] × (6m) = 1085.88 m3
Qinf = 0.238(1085.88 m3 )
𝐐𝐢𝐧𝐟 = 𝟐𝟓𝟖. 𝟒𝟑𝟗𝟖 𝐋/𝐬
4. Room 4
Infiltration due to outside air
Qinf = [a + b(vwind ) + c(t o − t i )] × volume
Qinf = [0.150 + 0.010(2.5 m/s) + 0.007(34 − 25)] = 0.238
V = [(8.4 × 17.5)] × (6m) = 882 m3
Qinf = 0.238(882 m3 )
𝐐𝐢𝐧𝐟 = 𝟐𝟎𝟗. 𝟗𝟏𝟔 𝐋/𝐬
5. Room 5
Infiltration due to outside air
Qinf = [a + b(vwind ) + c(t o − t i )] × volume
Qinf = [0.150 + 0.010(2.5 m/s) + 0.007(34 − 25)] = 0.238
V = [(198.83 m2 )] × (6m) = 1192.98 m3
Qinf = 0.238(1192.98 m3 )
𝐐𝐢𝐧𝐟 = 𝟐𝟖𝟑. 𝟗𝟐𝟗𝟐 𝐋/𝐬
Qs = 3148.2070 + 489.4273 W
𝐐𝐬 = 𝟑𝟔𝟑𝟕. 𝟔𝟑𝟒𝟑 𝐖
QL = 7359.2582 + 1513.5697 W
𝐐𝐋 = 𝟖𝟖𝟕𝟐. 𝟖𝟐𝟕𝟗 𝐖
6. Room 6
Infiltration due to outside air
Qinf = [a + b(vwind ) + c(t o − t i )] × volume
Qinf = [0.150 + 0.010(2.5 m/s) + 0.007(34 − 25)] = 0.238
V = [(526.95 m2 )] × (6m) = 3161.7 m3
Qinf = 0.238(3161.7 m3 )
𝐐𝐢𝐧𝐟 = 𝟕𝟎𝟖. 𝟐𝟐𝟎𝟖 𝐋/𝐬
5. Room 5 (Office)
@ Table H: Outdoor Air Ventilation
Retail/Office
7
Qvent = [(198.83)] ( ) (2.5)
100
𝐐𝐯𝐞𝐧𝐭 = 𝟑𝟒. 𝟕𝟗𝟓𝟑 𝐋/𝐬
6. Room 6 (Lobby)
@ Table H: Outdoor Air Ventilation
Lobby
30
Qvent = (526.95) ( ) (2.5)
100
𝐐𝐯𝐞𝐧𝐭 = 𝟑𝟗𝟓. 𝟐𝟏𝟐𝟓 𝐋/𝐬
2. Occupant Load
QS = (Gain per person)(sensible heat gain)(no. of people)(CLF)
Ql = (Gain per person)(latent heat gain)(no. of people)(CLF)
@ Table N: Sensible Heat Cooling Factors for People
Hours after each entry into space: 2 hours
Total Hours in space: 12 hours
CLF = 0.64 (For Sensible)
CLF = 1(For Latent)
@ Table H: Outdoor Air Ventilation (estimated occupancy per 100 square floor area)
18 person
For food service center =
100 m2
3. Partition Load
Qs = (U)(A)(∆T)
Where:
W
U = overall heat transfer coefficient of partition, m2 .K
W
Uinternalwall = 2.5094 m2 .K
W
Udoor = 0.64 (2.1812 by 1.8939 Single swing door, wood)
m2 .K
3.1 Room 1
Partition @ Internal Wall (South West)
W
Qs1 = (2.5094 )(19.3 m × 6m)(27 − 25)
m2 . K
Qs1 = 581.1770 W
W
Qs2 = (2.5094 )(3.2 m × 6m)(27 − 25)
m2 . K
Qs2 = 96.3606 W
Partition @ Internal Wall (North West)
W
Qs = (2.5094 )(4.6m × 6m)(27 − 25)
m2 . K
Qs = 138.5189 W
Comfort Room
Partition @ Internal Wall
W
Qs = (2.5094 )[(3.2 m × 6m) + (4.1 m × 6m) − (2. .2 × 0.8)](30 − 25)
m2 . K
Qs = 527.4759 W
3.2 Room 2
Partition @ Internal Wall (South East)
W
Qs = (2.5094 )(7.2 m × 6m)(27 − 25)
m2 . K
Qs = 216.8122 W
Partition @ Internal Wall (South West)
W
Qs = (2.5094 )(11.2m × 6m)(27 − 25)
m2 . K
Qs = 337.2634 W
Comfort Room
Partition @ Internal Wall
W
Qs = (2.5094 )[(3.2 m × 6m) + (4.1 m × 6m) − (2. .2 × 0.8)](30 − 25)
m2 . K
Qs = 527.4759 W
3.3 Room 3
Partition @ Internal Wall (North East)
W
Qs1 = (2.5094 )(9.6m × 6m)(27 − 25)
m2 . K
Qs1 = 289.0829 W
Partition @ Internal Wall (South East)
W
Qs2 = (2.5094 )(6.4m × 6m)(27 − 25)
m2 . K
Qs = 192.7219 W
W
Qs2 = (2.5094 )(5.1m × 6m)(30 − 25)
m2 . K
Qs2 = 383.9382 W
Comfort Room
Partition @ Internal Wall
W
Qs = (2.5094 )[(3.2 m × 6m) + (4.1 m × 6m) − (2. .2 × 0.8)](30 − 25)
m2 . K
Qs = 527.4759 W
3.4 Room 5
Partition @ Internal Wall (North East)
W
Qs1 = (2.5094 )(7m × 6m)(27 − 25)
m2 . K
Qs1 = 210.7896 W
W
Qs2 = (2.5094 )(0.8m × 6m)(27 − 25)
m2 . K
Qs1 = 24.0902 W
W
Qs3 = (2.5094 )[(4.7 + .5)(6) − (2.2 × 0.8)](30 − 25)
m2 . K
Qs3 = 369.3837 W
3.5 Room 6
Partition @ Internal Wall (North East)
W
Qs = (2.5094 )[(6 + 5.2)(6) − (3)(2.2 × 0.8)](30 − 27)
m2 . K
Qs = 466.1461 W
Partition @ Internal Wall (North West)
W
Qs = (2.5094 )(6.8 × 6)(30 − 27)
m2 . K
Qs = 511.9176 W
Partition @ Internal Wall (South East)
W
Qs = (2.5094 )(6.8 × 6)(30 − 27)
m2 . K
Qs = 511.9176 W
Elevator
Partition @ Internal Wall (North West)
W
Qs = (3.125 )[(2.2 × 0.9)(3)](30 − 27)
m2 . K
Qs = 55.6875 W
Partition @ Internal Wall (South East)
W
Qs = (3.125 )[(2.2 × 0.9)(3)](30 − 27)
m2 . K
Qs = 55.6875 W
4. Miscellaneous/Equipment Load
Qs = (no. of equipment)(q sensible )
q sensible = (Qinput )(Fu )(FR )
Where q sensible
@ TABLE O. Recommended Rates of Heat Gain from Typical Commercial
Cooking Appliances
@ TABLE P. Recommended Heat Gain from Typical Computer Equipment
@ TABLE Q. Recommended Heat Gain from Miscellaneous Office Equipment
@ TABLE R. Recommended Heat Gain from Typical Laser Printers and Copiers
4.1 Room 1 (Restaurant/Food Preparation)
EQUIPMENT LOAD
Equipment Quantity Sensible (W) Total (W)
Oven (roasting) 1 800 800
Fryer (deep fat)w/ hood 2 350 700
Griddle w/ hood 1 1350 1350
Food Warmer (shelf type) 1 2330 2330
Toaster 1 800 800
Coffee Brewer 1 1100 1100
Microwave 1 2630 2630
Ice Machine 1 1880 1880
Food Processor 1 520 520
Mixers (small) 2 15 30
Blender 2 310 620
Soup Cooker 1 45 450
Refrigerator (large) 1 310 310
Dish washer 1 56 560
Computer 2 65 130
Cash Registers 2 48 96
QS 14306
𝑸𝒔 = 𝟏𝟒𝟑𝟎𝟔 𝑾
EQUIPMENT LOAD
Equipment Quantity Sensible (W) Total (W)
Fryer 3 350 1050
Griddle 2 1350 2700
Food Warmer 1 2330 2330
Ice Machine 1 1880 1880
Refrigerator (large) 1 310 310
Dough Roller (small) 2 460 920
Oven (pizza) 2 410 820
𝑸𝒔 = 𝟏𝟏𝟏𝟔𝟐 𝑾
EQUIPMENT LOAD
Equipment Quantity Sensible (W) Total (W)
Food Warmer 1 2330 2330
Display Case (refrigerated) 2 640 1280
Microwave Oven 1 600 600
Vending Machine (Cold Food/Beverage) 3 575 1725
Vending Machine (snack) 4 240 960
Computer 2 65 130
Cash Registers 5 48 240
Qs 7265
𝑸𝒔 = 𝟕𝟐𝟔𝟓 𝑾
EQUIPMENT LOAD
Equipment Quantity Sensible (W) Total (W)
Computer 15 65 975
Printers (large office) 1 125 125
Copier 1 300 300
Water Cooler 2 350 700
𝑸𝒔 = 𝟐𝟑𝟎𝟎 𝑾
EQUIPMENT LOAD
Equipment Quantity Qs (W) Total (w)
Security Monitor 2 70 140
Computer 1 65 65
Cash Register 2 48 96
Vending Machine (Cold Beverage 1 575 575
Total 876
𝑸𝒔 = 𝟖𝟕𝟔 𝑾