Replaceable

Integrated Dry Remote Expandable


Panel Mount Surge EtherNet/IP USB AVR
I/O Contacts On/Off Battery
Protection
1609-B • • • • •
1609-D • • • • • • • •
1609 - D 600 N
Batteries not included:
1609-B units require two batteries.
Bulletin Product Family VA (Volt-Amperes) Voltage
1609 D= Deluxe (Full featured) 600= 600 VA 1609-D units require three batteries.
N = 120VAC
B= Basic 1000 = 1000 VA Input/Output Standard battery is 1609-SBAT.
1500 = 1500 VA Hi-Temp Battery is 1609-HBAT.
Input Protection
V nom. 120V 380 Joules (Total Performance Rated With
Surge
10*1000ms Pulse)
600N 600VA (390 W) >110-130% Shutdown after 10 Seconds
Overload
Capacity 1000N 1000VA (650 W) >130% Shutdown immediately
Output Short On Line Premises branch circuit over-current protection
1500N 1500VA (980 W)
Output Short On Battery Shutdown
Voltage Range, default 90~145V
Thermal Protection UPS inside temperature 60 degree C
Voltage Range, widest, on line 90~145V
Current nom. 5.5A Bypass N/A
Regulatory
Capacity Frequency 50/60Hz±3Hz
Safety UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1
None (Load power factor is EMC FCC & CE (Class A)
PFC reflected in the input line
current) Markings UL, cUL, FCC, CE

Output
Battery Pack
Run Time ≧5 Minutes (at 25 degree C, full R load)
V nom. 120V
Type Sealed Lead Acid Battery
600N 600VA (390 W) 0-40°C:
Rated B.B. BP5-12
Capacity 1000N 1000VA (650 W) 12V/5.5Ah
Capacity 0-50°C:
1500N 1500VA (980 W) B.B. HRL5.5-12
Charger Current limited, constant voltage float charger
On Line
Recharge Time Less than 8 hours to 90% capacity after
Output Range, default 108~132V discharged with full load
Lifetime 2~3 years @ 25 degree C ambient
Output Voltage Range, widest 108~132V
Environmental
Transfer Point Accuracy ±3%
Operating Temperature – 0°C~40°C (32°F~104°F)
On Battery Standard Battery 0°C~50°C (32°F~122°F)
V nom. 120V (Sine Wave)
Operating Temperature – 0°C~50°C (32°F~122°F)
Hi Temperature Battery
Frequency 50/60Hz ±0.5Hz (Factory Storage Temperature - 15...45°C (5°F...113°F)
Default: 60Hz ±0.5Hz) Altitude Operating 0 ... 6600 feet (0 to 2000 meters)
THD ≦10% (Full Linear Load) Humidity
Operating/Storage 5~95 % RH
(Non-condensing)
Short Circuit Protection On Line, Full
load: 217 BTU per hour
Crest Factor 2.2:1
Heat On Line, Full 296 BTU per hour
Efficiency Output load, Charging:
On Battery 75% (Typical with resistive load) On Battery: Full
1331 BTU per hour
Load:
86% (Typical with resistive load Audible
On Line 50 dBA at front side one meter
excluding AVR mode) Noise

Allen-Bradley, LISTEN. THINK. SOLVE. and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Allen-Bradley 1609-D1000N
Publication 1609-PP005A-EN-P – February 2013 Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Bulletin 1609
Next Generation Industrial UPS

Features and Benefits Batteries not included:


The 1609 family of Industrial 1609-B units require two batteries.
Uninterruptible Power Supplies is 1609-D units require three batteries.
designed for industrial applications – Standard battery is 1609-SBAT.
with features required for remote control Hi-Temp Battery is 1609-HBAT.
and operation inside of industrial
control panels.

DIN-rail/panel/floor mount
• Flexibility to meet most installation
scenarios, included control panels
typically used in production
environments.
Hard-wired input and output
• Electrical codes typically do not allow
plug-in connections within a control
panel.
Integrated remote on/off and
Dry I/O contacts
• Meet code requirements to allow Faster Recovery From Power Failures
proper shutdown of the UPS when An industrial uninterruptable power supply (UPS) can enable your
control panel is open and closed and production production process to recover quickly from a line power
provide for remote monitoring and
interruption, saving you lost production time and work in process.
control of UPS.
Sometimes users think that because there isn’t a battery large enough
USB communications to keep the process itself going, a UPS won’t make any difference. What
• Provides remote monitoring and a UPS can do effectively, is to keep the control system, networks and
configuration through included sensors powered, so when power returns, the control system knows where
software everything is and can start up without having to completely reset and clear
True sine wave AC output the work in process.
• Compatible with the widest range of The 1609 is uniquely designed for the industrial market to provide back-up
equipment.
AC power to the control cabinet. The 1609 will provide back-up power to
Expandable battery capacity bridge dips, sags, or brief losses of power. If necessary, the 1609 will facilitate
• Additional batteries can be added a safe shut-down of your industrial PC, PLC, data logging HMI, or any other
to the UPS to extend run-time or critical device in the control scheme. Without a 1609 in place, the customer
accommodate additional equipment. is faced with nuisance power dips, ex¬tended down-time, and potential
(1609-D Only) machine damage; all of which can result in signifi¬cant and costly challenges
EtherNet/IP communications
The newer technologies of industrial controls are much more sensitive to
• Allows the ability to communicate power fluctuations, the need for clean consistent reliable power continues
with and integrate to Rockwell
to grow as industrial automation and process control continues to migrate
Automation Integrated Architecture.
more towards more sensitive electronic controls and extensive networking.
(Optional, for 1609-D Only)
Industrial UPS products are about increasing system reliability and
minimizing down time due to power disruptions and product failures in the
control system.