Professional Documents
Culture Documents
(UNIT 5)
The methods for treating the data depend to some degree on the experimental procedure. The following cases
should be distinguished:
a. Ageing procedure. a. 1 Continuous. a 2 Cyclic.
b. Evaluation of the state of the specimens. b. 1 Non-destructive measurement of property/properties. b. 1.1
Continuous monitoring. b. 1.2 Periodic measurements. b.2 Periodic application of a specified test stress ( proof
tests ). b.3 Destructive determination of a property.
STATISTICAL PROCEDURES 3.1 The statistical procedures involved comprise the following steps:
1) Determination of the times to failure.
2) Calculation of the coefficients a and b of the linear eqllation of regression Y = a + bx of the logarithm of
time to failure (y=lg 5) on the reciprocal value of the thermodynamic temperature ( x = I/@ ).
3)Drawing the thermal endurance graph.
4)Determination of the temperature index ( when applicable ).
5)Testing the equality of the variances of the logarithm of the times to failure at the different ageing
temperatures.
6)Test for linearity of the regression equation.
7)Determination of the lower unilateral 95% confidence limit on the logarithmic mean time to faiiure on the
regression line.
8)Calculation of the values of temperature 0°C corresponding to times to failure of 5 000 h and 20 000 h
according to the regression equation.
9)Check the coefficient of variation of the logarithm of time to failure according to the regression equation at 5
000 h.
10)Calculation of the lower unilateral 95% confidence limit on the temperature corresponding to a time to
failure of 5 000 h on the regression line.
Factors affecting the use of insulating materials and methods of identification
1. Resistance to ignition: the ability to resist the ignition when a fire is fired or separated by a fire.
With the increasing of insulation materials, the insulation ladder has become more and more important for its
resistance to fire resistance. People have improved and improved the resistance of insulation materials through
various means of process.
2. Insulation resistance and resistivity: the resistance is the reciprocal of the conductance, and the resistivity is
the resistance in the unit volume.The smaller the material, the higher the resistance, the inverse relationship
between the two, and for insulating materials, always hope the resistivity is as high as possible.
3. Tensile strength: it is the maximum tensile stress in the test sample.It is the most extensive and representative
of the mechanical properties of insulating materials.
4. Breakdown voltage and electrical strength: damage of insulation material under a strong electric field, loss?
The insulation performance leads to a conductive state called breakdown.The breakdown voltage is called the
breakdown voltage.The electrical strength is the distance between the voltage and the two electrodes acting as
the external voltage when the breakdown occurs under the specified conditions, which is the breakdown
voltage of the unit thickness.
5. Arc resistance: the ability of insulating materials to be affected by an arc on the surface of an insulating
material under specified conditions.When using swap high voltage low current, high voltage between two
electrodes produced by the arc moved transmission, the time needed for insulation surface of conductive layer
to determine arc resistance of insulating material.
Methods of measuring temperature of internal parts of windings/ machines & applying the correction
factor when the machine is hot
1) Resistance method
Increasing of moisture in transformer oil can form sludge due to the reason of reducing the dielectric strength
and corrosion. Acid can damage the windings of the transformer. It is too easy to reclaim the oil by removing
the precursors of sludge through the use of activated clay or activated aluminum.
The sludge test in transformer oil is very important for the transformer. Before the filtration or dehydration
sludge test is necessary for the transformer. By the help of sludge test, we can identify the impurities, acid,
semi-solid, and etc. in the transformer.
Crackle Test
The crackle test is a standard laboratory test to detect the presence of water in lubricating oil. A drop of oil is
placed on a hotplate that has been heated to approximately 400° F. The sample then bubbles, spits, crackles or
pops when moisture is present. At Insight Services when the crackle test is positive, indicating the presence of
water, a Karl Fischer titration is performed to quantify the water. If the crackle test is negative it simply means
that the level of water present in the sample is below the detection limit; it doesn’t necessarily mean the sample
is void of water.
Flashpoint test of transformer oil is a low-cost test and popular test of insulating oil. The oil sparkles after the
mixing of vapor with oxygen in the air. The vapor pressure of oil normally in flash point is 3-5 mm Hg. When a
small amount of flame is applied to the oil the mixture of vapor will burn for temporary and then it will get rid
of automatically when the point temperature has been reached. If we continue the heating process for a long
time or more than the flash point (50-70 degree Celsius) then the oil will be reached at the fire point.
TRANSFORMER OIL FILTRATION
Insulation fluids are used in many types of high voltage equipment: capacitors, cables, switches, transformers etc. The
fluids usually perform two main functions, i.e. electrical insulation and cooling. Some extra functions are arc
extinguishing in switchgear and protection of the internal solid insulation from moisture in the environment.
It is difficult to imagine modern processes of transmission and distribution of electric energy without power
transformers. This equipment should be protected from possible breakdowns by protecting its hard insulation and
cooling. This function is assigned to mineral oils.
Wiping off dirt with a clean, dry, lint-free cloth or soft brush is usually satisfactory if the apparatus is small,
the surfaces to be cleaned are accessible, and only dry dirt is to be removed.
Don't use waste rags when cleaning electrical equipment because lint will adhere to the insulation, acting as
a further dirt-collecting agent, which can cause tracking. Cloth rags should be clean and free of oil, grease,
and metallic deposits.
Use care to avoid damage to delicate parts. Rags can easily catch on edges other and sharp objects, which
could damage small plastic or moving parts.
Accumulated dirt, oil, or grease might require a solvent to be removed. A rag barely moistened (not wet) with
a nonflammable solvent can be used for wiping. Solvents used for cleaning of electrical equipment should
be selected carefully to ensure compatibility with materials being cleaned.
Do not use any liquid cleaners, including spray cleaners, unless specified by the equipment
manufacturer, because of the risk of residues causing damage, interfering with electrical or mechanical
functions, or compromising the integrity of insulation surfaces.
Allow sufficient time for drying after cleaning equipment with a liquid solvent or water!
Observe all material data sheets prior to using chemical cleaners. Wear the required personal protective
equipment (PPE) such as goggles, gloves, aprons, and respirators when working with potentially hazardous
solvents.
Vacuum Cleaning
Loose dust, dirt, and particles can be removed using a vacuum-type cleaner with non-metallic
attachments and hoses.
Blowing equipment out with compressed air is likely to spread contamination and damage insulation.
Equipment enclosures and substation room filters should be cleaned at regular intervals and replaced if they are
damaged or clogged.
Loose hardware and debris should be removed from the enclosures. New or unusual wear or loss of parts
occurring after the cleaning can be detected during subsequent maintenance.
If the sweeping of a substation room is required, use a sweeping compound to limit the amount of dirt and
dust becoming airborne.
When mopping, keep the mop bucket as far as practical from the switchgear to prevent damage from spillage.
Where dirt cannot be removed by wiping or vacuuming, compressed air blowing might be necessary.
CAUTION: Cleaning with compressed air can create a hazard to personnel and cause equipment to
fail or malfunction. If compressed air is used, protection should be provided against injury to workers'
faces and eyes from flying debris and to their lungs from dust inhalation.
The use of compressed air should comply with OSHA regulations in 29 CFR 1910.242(b), "Hand and
Portable Powered Tools and Other Hand Held Equipment," including limiting air pressure for such cleaning to
less than a gauge pressure of 208.85 kPa (30 psi) and the provision of effective chip guarding and appropriate
personal protective equipment.
Use care when working with compressed air to avoid contaminants from become airborne, which can
contaminate insulation surfaces, cause injury to personnel, or affect the mechanical operation of nearby
equipment.
Compressed air should be dry and directed in a manner to avoid further blockage of ventilation ducts and
recesses in insulations.
Protection might also be needed against contamination of other nearby equipment if the insulation is
cleaned in place with compressed air. Removed the apparatus to a suitable location for cleaning, or other
exposed equipment should be covered before cleaning starts to keep the debris out.
Electrical equipment might require cleaning by nonconductive sandblasting. Shot blasting should not be used.
Abrasive blasting operations should comply with OSHA regulations in 29 CFR 1910.94(a), "Occupational
Health and Environmental Control — Ventilation." Use personal protective equipment to protect the face
and eyes from abrasives and flying debris, and the lungs from dust inhalation.
Asbestos Exposure
Asbestos is a toxic substance subject to government regulations. Special considerations should be taken
when cleaning aged equipment that may contain asbestos, especially when using compressed air
methods.Knowledge of government regulations is required in handling asbestos and other such materials.