Preventive maintenance checklist- W

FOUNDRY MAINTENANCE ELECTRICAL


FURNACE NO: FD 001 FURNACE
PANEL

Date
Activity Methods
Visually for
Over heating discoloration
Busbar joints tightness and
temperature
Visually for
discoloration
gun
Capacitor link and
temperature
capacitor & other insulators Inspect for any
gun
damage
Cleaning With Dry air Internal bus

Wipe and Clean


FSS Contact
Remarks
FURNACE
Initially 2 week
Tightness tighten and later
Shunt inspect
Inspect while
Insulation
Coil relining

Bush & Bearing Greasing

Remarks
HYDRAULIC
Setting Pressure relief valve Block pressure
Speed of lid
Flow control valve
movement
FCE cushioning Slower Speed
Verify (Tilting
Time taken time, with full
Tilt and return of furnace metal)
Remarks
Prepared By - HAREESH CHECKED BY
Approved By

Preventive maintenance checklist- W


Preventive maintenance checklist- W
FOUNDRY MAINTENANCE ELECTRICAL
FURNACE NO: FD 001 FURNACE

PANEL
Date
Activity Methods
Over heating Visually for
discoloration
Busbar joints tightness and
temperature
gun

Visually for
discoloration
Capacitor link and
temperature
gun

Inspect for any


capacitor & other insulators damage
Cleaning With Dry air Internal bus
FSS Contact Wipe and Clean
Remarks
FURNACE
Initially 2 week
Tightness tighten and later
Shunt inspect
Inspect while
Insulation
Coil relining

Bush & Bearing Greasing

Remarks
HYDRAULIC
Setting Pressure relief valve Block pressure
Speed of lid
Flow control valve movement
FCE cushioning Slower Speed
Verify (Tilting
Time taken time, with full
Tilt and return of furnace metal)
Remarks
Prepared By - HAREESH CHECKED BY
Approved By
maintenance checklist- Weekly DOC NO: VSPL_FND_PM_FCE_E01-00

ELECTRICAL REV NO.1 PAGE NO.:1


Month Year
FURNACE
PANEL

Week 1 Week 2 Week 3 Week 4

FURNACE

HYDRAULIC

maintenance checklist- Weekly DOC NO: VSPL_FND_PM_FCE_E01-00


maintenance checklist- Weekly DOC NO: VSPL_FND_PM_FCE_E01-00

ELECTRICAL REV NO.1 PAGE NO.:1


Month Year
FURNACE

PANEL

Week 1 Week 2 Week 3 Week 4

FURNACE

HYDRAULIC
Preventive maintenance checklist DOC NO: VSPL_FND_PM_FCE_E01-00

FOUNDRY MAINTENANCE ELECTRICAL REV NO.1 PAGE NO.:1


FURNACE NO: FD 001 FURNACE MONTHLY
PANEL
Activity Methods Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

DATE :
capacitor & other
Over heating insulators Cleaning

Wire Joints For Proper Connection

REMARKS
FURNACE
Shunt Tightness verify tightness

REMARKS
HYDRAULIC
Oil
For viscosity
Quality

Dirt Filters, Particles


in oil

REMARKS
WATER SYSTEM
Tank All tank
Cleaning

Pump All Pump


Greasing

De-Ionizer Replace

REMARKS

Prepared By - HAREESH CHECKED BY

APPROVED BY
Preventive Maintenance Checklist- Quarterly
FOUNDRY MAINTENANCE ELECTRICAL
FURNACE NO: FD 001 FURNACE
S.NO DESCRIPTION
PANEL
1 Apply Grease to Input Switch
DOL STARTER

1 Tighten all the MCB connections & measure input and output voltages.

Tighten all in/out connection of contactor,OLR.


2 Check contactor tips condition by press &
seeing the continuity @in/out terminals.
3 Tighten stater & motor earthing connection and record the neutral to earth Vg

DM WATER MOTOR
Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly
1

2 Tighten stater & motor earthing connection and record the neutral to earth Vg

3 Checking the motor condition


HYDRAULIC
DOL STARTER

1 Tighten all the MCB connections & measure input and output voltages.

Tighten all in/out connection of contactor,OLR.


2 Check contactor tips condition by press &
seeing the continuity @in/out terminals.
3 Tighten stater & motor earthing connection and record the neutral to earth Vg

4 Check hydraulic hose pipe and valve

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Tighten stater & motor earthing connection and record the neutral to earth Vg

3 Checking the motor condition

FURNACE
1 All bolts and Nuts to be tightend of Crucible
2 Check water cool lids condition

REMARKS

PREPARED BY : HAREESHA CHECKED BY :


ve Maintenance Checklist- Quarterly DOC NO: VSPL_FND_PM_FCE_E01-00

ELECTRICAL REV NO.1 PAGE NO.:1


Month Year
FURNACE
DESCRIPTION SPECIFICATION RESULT
PANEL

DOL STARTER

easure input and output voltages. 415 V V

ctor,OLR. OLR=4-6.5Amps OLR set


ss & cont coil=0.87Ώ Ώ
als.
ection and record the neutral to earth Vg
Less than 1 Volt AC VAC

DM WATER MOTOR
s value. Megger >500MΏ MΏ
d cover needly motor=3.9Ώ Ώ
motor Vg=415 V Vg
motor Amps=4.5 R Y B

ection and record the neutral to earth Vg


Less than 1 Volt AC VAC

HYDRAULIC
DOL STARTER

easure input and output voltages. 415 V V

ctor,OLR. OLR=4-6.5Amps OLR set


ss & cont coil=0.87Ώ Ώ
als.
ection and record the neutral to earth Vg Less than 1 Volt AC VAC

MOTOR
s value. Megger >500MΏ MΏ
d cover needly motor=6.6Ώ Ώ
motor Vg=415 V Vg
motor Amps=3.5 R Y B
Megger >500MΏ MΏ
motor=6.6Ώ Ώ
motor Vg=415 V Vg
motor Amps=3.5 R Y B

ection and record the neutral to earth Vg


Less than 1 Volt AC VAC

FURNACE
ucible 415 V V

CHECKED BY : APPROVED BY :
Preventive Maintenance Checklist- Quarterly
FOUNDRY MAINTENANCE ELECTRICAL
FURNACE NO: FD 001 FURNACE
S.NO DESCRIPTION
WATER SYSTEM
DOL STARTER (A1)
1 Tighten all the MCB connections & measure input and output voltages.

Tighten all in/out connection of contactor,OLR.


2 Check contactor tips condition by press &
seeing the continuity @in/out terminals.

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Tighten stater & motor earthing connection and record the neutral to earth Vg

3 Checking the motor condition


DOL STARTER (A2)
1 Tighten all the MCB connections & measure input and output voltages.

Tighten all in/out connection of contactor,OLR.


2 Check contactor tips condition by press &
seeing the continuity @in/out terminals.

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Tighten stater & motor earthing connection and record the neutral to earth Vg

3 Checking the motor condition

DOL STARTER (B1)


Tighten all in/out connection of contactor,OLR.
1 Check contactor tips condition by press &
seeing the continuity @in/out terminals.

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Tighten stater & motor earthing connection and record the neutral to earth Vg
3 Checking the motor condition
DOL STARTER (B2)
1 Tighten all the MCB connections & measure input and output voltages.
Tighten all in/out connection of contactor,OLR.
2 Check contactor tips condition by press &
seeing the continuity @in/out terminals.

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Tighten stater & motor earthing connection and record the neutral to earth Vg
3 Checking the motor condition
4 Clean heat exchanger - 2 Nos
OVERHEAD TANK
DOL STARTER

Tighten all in/out connection of contactor,OLR.


1 Check contactor tips condition by press &
seeing the continuity @in/out terminals.

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Checking the motor condition


COOLING TOWER MOTOR
DOL STARTER
1 Tighten all the MCB connections & measure input and output voltages.

Tighten all in/out connection of contactor,OLR.


2 Check contactor tips condition by press &
seeing the continuity @in/out terminals.

MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly

2 Tighten stater & motor earthing connection and record the neutral to earth Vg

3 Checking the motor condition


REMARKS
PREPARED BY : HAREESHA CHECKED BY :
ntive Maintenance Checklist- Quarterly DOC NO: VSPL_FND_PM_FCEWP_E01-00

ELECTRICAL REV NO.1 PAGE NO.:1


FURNACE Month Year
DESCRIPTION SPECIFICATION RESULT
WATER SYSTEM
DOL STARTER (A1)
re input and output voltages. 415 V V

,OLR. OLR=9-15 Amps OLR set


cont coil=0.63Ώ Ώ

MOTOR
ue. Megger >500MΏ MΏ
ver needly motor=2.4Ώ Ώ
motor Vg=415 V Vg
motor Amps=8 R Y B

on and record the neutral to earth Vg


Less than 1 Volt AC VAC

DOL STARTER (A2)


re input and output voltages. 415 V V

,OLR. OLR=9-15 Amps OLR set


cont coil=0.63Ώ Ώ

MOTOR
ue. Megger >500MΏ MΏ
ver needly motor=2.4Ώ Ώ
motor Vg=415 V Vg
motor Amps=8 R Y B

on and record the neutral to earth Vg


Less than 1 Volt AC VAC

DOL STARTER (B1)


,OLR. OLR=9-15 Amps OLR set
cont coil=0.63Ώ Ώ

MOTOR
ue. Megger >500MΏ MΏ
ver needly motor=2.4Ώ Ώ
motor Vg=415 V Vg
motor Amps=7.8 R Y B

on and record the neutral to earth Vg Less than 1 Volt AC VAC

DOL STARTER (B2)


re input and output voltages. 415 V V
,OLR. OLR=9-15 Amps OLR set
cont coil=0.63Ώ Ώ

MOTOR
ue. Megger >500MΏ MΏ
ver needly motor=2.4Ώ Ώ
motor Vg=415 V Vg
motor Amps=7.8 R Y B

on and record the neutral to earth Vg Less than 1 Volt AC VAC

OVERHEAD TANK
DOL STARTER

,OLR. OLR=2.5-4 Amps OLR set


cont coil=0.87Ώ Ώ

MOTOR
ue. Megger >500MΏ MΏ
ver needly motor=17.6Ώ Ώ
motor Vg=415 V Vg
motor Amps=1.7 R Y B

COOLING TOWER MOTOR


DOL STARTER
re input and output voltages. 415 V V

,OLR. OLR=2-3.3 Amps OLR set


cont coil=0.85Ώ Ώ

MOTOR
ue. Megger >500MΏ MΏ
ver needly motor=25.8Ώ Ώ
motor Vg=415 V Vg
motor Amps=2.5 R Y B

on and record the neutral to earth Vg


Less than 1 Volt AC VAC

KED BY : APPROVED BY: