Professional Documents
Culture Documents
DSEGenset
DSE4210/20
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO START AND AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
CONTROL MODULES EMC Generic Emission Standard for
the Industrial Environment
FEATURES
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE4210 Auto Start Control Monitoring engine speed, oil Through USB Communication both
Module and the DSE4220 Auto pressure, coolant temperature, modules can be easily configured TEMPERATURE
BS EN 60068-2-1
Mains (Utility) Failure Control frequency, voltage and fuel level, using the DSE Configuration Suite Ab/Ae Cold Test -30 oC
Module are suitable for a wide the modules will give PC Software or can be partially BS EN 60068-2-2
variety of single gen-set comprehensive engine and configured through the module's Bb/Be Dry Heat +70 oC
load power monitoring, the engine support for diesel, gas and and end users access to 24 hour HUMIDITY
DSE42xx range of especially petrol engines all in one variant. system help and advice. BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 oC
compact controllers provide the With a number of flexible inputs, @ 95% RH 48 Hours
user with the ultimate size to outputs and protections, the BS EN 60068-2-78
feature ratio. modules can be easily adapted to Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
suit a wide range of applications.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
7 4
DSE4210/20
7
OTHER
VOLTS VOLTS
+ +
D+
+
W/L
1ph 1 1 1ph
2ph 2ph
3ph 3ph
N N
ISSUE 1
®
DSEGenset
DSE4210/20 SPECIFICATION
DSE4220
LEDs and backlight will not be maintained
during cranking.
DSE4210
40 mA at 12 V, 45 mA at 24 V
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at DC supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at DC supply voltage
KEY BENEFITS KEY FEATURES • 3 engine maintainance alarms
AUXILIARY OUTPUTS C & D
• Ultimate size to feature ratio • User friendly fault indication by • Engine speed protection 2 A DC at supply voltage
• Automatically transfers between LED • Engine hours counter
mains (utility) and generator • Fully configurable via the fascia • Engine pre-heat AUXILIARY OUTPUTS E & F DSE4220
2 A DC at supply voltage
(DSE4220 only) or PC using USB • Engine run-time scheduler
• Hours counter via PC software communication • Battery voltage monitoring GENERATOR
• User-friendly set-up and button • Extremely efficient power save • Start on low battery voltage VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
layout for ease of use mode • Configurable remote start input 26 V to 719 V AC (Ph to Ph)
• The module can be configured • 3 phase generator sensing • 1 alternative configuration
to suit a wide range of • 3 phase mains (utility) sensing • Comprehensive warning, FREQUENCY RANGE
3.5 Hz to 75 Hz
applications (DSE4220 only) electrical trip or shutdown
• Uses DSE Configuration Suite • Compatible with 600 V AC protection upon fault condition DIMENSIONS
PC Software for simplified Ph to Ph nominal systems • Event log (15) OVERALL
140 mm x 113 mm x 43 mm
configuration • Fuel and start outputs 5.5’’ x 4.4” x 1.7”
• Licence-free PC software • 4 configurable DC outputs (2 for
• IP65 rating (with optional gasket) DSE4210) PANEL CUT-OUT
118 mm x 92 mm
offers increased resistance to • 7 configurable digital inputs 4.6’’ x 3.6”
water ingress • Configurable staged loading
outputs MAXIMUM PANEL THICKNESS
8 mm
• Alternator speed sensing 0.3”
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-156/02/13 (1) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457