DSEGenset

DSE4510/20 ENVIRONMENTAL TESTING STANDARDS

AUTO START AND AUTO MAINS FAILURE ELECTRO-MAGNETIC COMPATIBILITY

CONTROL MODULES BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
FEATURES EMC Generic Emission Standard for
the Industrial Environment

ELECTRICAL SAFETY
The DSE4510 Auto Start Control Electronic J1939 (CAN) and non- BS EN 60950

Module and the DSE4520 Auto electronic (alternator sensing) * AVAILABLE VARIANTS Safety of Information Technology Equipment,
including Electrical Business Equipment
Mains (Utility) Failure Control engine support for diesel, gas and 4510-03 Auto start with real time clock
TEMPERATURE
Module are suitable for a wide petrol engines all in one variant. BS EN 60068-2-1
4510-04 Auto start with real time clock &
variety of single gen-set With a number of flexible inputs, heated display Ab/Ae Cold Test -30 oC
applications. outputs and protections, the BS EN 60068-2-2
4520-03 Auto Mains Failure with real time Bb/Be Dry Heat +70 oC
module can be easily adapted to
clock
Whilst maintaining functions suit a wide range of applications. VIBRATION
BS EN 60068-2-6
included within higher end 4520-04 Auto Mains Failure with real time
Ten sweeps in each of three
controllers, such as generator or Through USB Communication both clock & heated display major axes
load power monitoring, the modules can be easily configured 5 Hz to 8 Hz at +/-7.5 mm,
8 Hz to 500 Hz at 2 GN
DSE45xx range of especially using the DSE Configuration Suite
compact controllers provide the PC Software or can be fully HUMIDITY
BS EN 60068-2-30
user with the ultimate size to configured through the module's Db Damp Heat Cyclic 20/55 oC
feature ratio. front panel editor. at 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 oC
Monitoring engine speed, oil All DSE products are supported by at 93% RH 48 Hours
pressure, coolant temperature, the DSE global technical support
SHOCK
frequency, voltage, current, power team which gives our customers BS EN 60068-2-27
and fuel level, the modules will give and end users access to 24 hour Three shocks in each of three major axes
comprehensive engine and system help and advice. 15 GN in 11 mS

alternator protection. This will be DEGREES OF PROTECTION


indicated on the largest back-lit PROVIDED BY ENCLOSURES
BS EN 60529
LCD icon display in its class via an IP65 - Front of module when installed into the
array of warning, electrical trip and control panel with the optional sealing gasket.
shutdown alarms.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

4 4 3

USB CONFIGURABLE DC OUTPUT ANALOGUE SENDERS DC POWER


PORT INPUTS (2 for DSE4510) SUPPLY

DEUTZ
DSE4510/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) DC OUTPUT GENERATOR / DC OUTPUT GENERATOR CHARGE FUEL AND START ELECTRONIC
SENSING 4520 1 OF 4 LOAD CURRENT 4510 1 OF 2 SENSING ALTERNATOR OUTPUTS ENGINE CAN
(DSE4520) 4520 1 OF 4 (Flexible with CAN)

VOLTS VOLTS
D+ +
+ + W/L

1ph 1 1ph 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N

ISSUE 1
®

DSEGenset

DSE4510/20 SPECIFICATION

DC SUPPLY
AUTO START AND AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CONTROL MODULES CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

DSE4520 MAXIMUM OPERATING CURRENT


85 mA at 12 V, 96 mA at 24 V

MAXIMUM STANDBY CURRENT


51 mA at 12 V, 47 mA at 24 V

MAXIMUM SLEEP CURRENT


DSE4510 35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT


<10 uA at 12 V, <10 uA at 24 V

MAINS (UTILITY) DSE4520 ONLY


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage

OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
KEY BENEFITS KEY FEATURES • 4 configurable DC outputs (2 for
AUXILIARY OUTPUTS C & D
• Ultimate size to feature ratio • Largest back-lit icon display in DSE4510) 2 A DC at supply voltage
• Automatically transfers between its class • 3 configurable analogue/digital
mains (utility) and generator • Heated display option inputs AUXILIARY OUTPUTS E & F DSE4520
2 A DC at supply voltage
(DSE4520 only) • Real time clock provides • 4 configurable digital inputs
• Hours counter provides accurate accurate event logging • Configurable staged loading GENERATOR
information for monitoring and • Fully configurable via the fascia outputs VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
maintenance periods or PC using USB • CAN and alternator speed 26 V to 719 V AC (Ph to Ph)
• User-friendly set-up and button communication sensing in one variant
layout for ease of use • Extremely efficient power save • 3 engine maintainance alarms FREQUENCY RANGE
3.5 Hz to 75 Hz
• Multiple parameters are mode • Engine speed protection
monitored simultaneously • 3 phase generator sensing • Engine hours counter DIMENSIONS
• The module can be configured • 3 phase mains (utility) sensing • Engine pre-heat OVERALL
140 mm x 113 mm x 43 mm
to suit a wide range of (DSE4520 only) • Engine run-time scheduler 5.5’’ x 4.4” x 1.7”
applications • Compatible with 600 V ph - ph • Engine idle control for starting &
• Compatible with a wide range nominal systems stopping PANEL CUT-OUT
118 mm x 92 mm
of CAN engines, including tier 4 • Generator/load power • Battery voltage monitoring 4.6’’ x 3.6”
engine support monitoring (kW, kV A, kV Ar, pf) • Start on low battery voltage
• Licence-free PC software • Generator overload protection • Configurable remote start input MAXIMUM PANEL THICKNESS
8 mm
• IP65 rating (with optional (kW) • 1 alternative configuration 0.3”
gasket) offers increased • Generator/load current • Comprehensive warning,
resistance to water ingress monitoring and protection electrical trip or shutdown STORAGE TEMPERATURE RANGE
-40°C to +85°C
• Fuel and start outputs protection upon fault condition
(configurable when using CAN) • LCD alarm indication OPERATING TEMPERATURE RANGE
• Event log (50) -30°C to +70°C
-40°C to +70°C (for heated display variant)

OPTIONAL PARTS
RELATED MATERIALS PART PART NUMBER
TITLE PART NO’S IP65 Gasket 020-282
DSE4510/20 Installation Instructions 053-157
DSE4510/20 Operator Manual 057-171
DSE4510/20 Configuration Suite PC Manual 057-172

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-132/09/12 (5)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

You might also like