Professional Documents
Culture Documents
DSEGenset
ELECTRO-MAGNETIC COMPATIBILITY
The DSE7410 is an Auto Start The DSE7400 Series modules are TEMPERATURE
Control Module and the DSE7420 compatible with electronic (CAN) BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
is an Auto Mains (Utility) Failure and non-electronic (magnetic pick- BS EN 60068-2-2
Control Module suitable for a wide up/alternator sensing) engines and Bb/Be Dry Heat +70 oC
variety of single, diesel or gas, offer a comprehensive number of VIBRATION
gen-set applications. flexible inputs, outputs and BS EN 60068-2-6
extensive engine protections so the Ten sweeps in each of three
major axes
A sophisticated module monitoring system can be easily adapted to 5 Hz to 8 Hz @ +/-7.5 mm,
an extensive number of engine meet the most demanding industry 8 Hz to 500 Hz @ 2 gn
parameters, the DSE74xx will paralleling requirements. HUMIDITY
annunciate warnings, shutdown BS EN 60068-2-30
and engine status information on The modules can be easily Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
the back-lit LCD screen, illuminated configured using the DSE BS EN 60068-2-78
LED, remote PC, audible alarm and Configuration Suite Software. Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
via SMS text alerts. The module Selected front panel editing is also
includes RS232, RS485 & Ethernet available. SHOCK
ports as well as dedicated BS EN 60068-2-27
Three shocks in each of three major axes
terminals for system expansion. 15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DSENET RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
ETHERNET
+
DEUTZ
DSE7410/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) SENSING (DSE7420) N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
BUS SENSING (DSE7410) OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
FLEXIBLE WITH CAN MAGNETIC PICK-UP
VOLTS CURRENT VOLTS
D+
W/L +
ISSUE 1
®
DSEGenset
DSE7410/20 SPECIFICATION
DC SUPPLY
AUTO START & AUTO MAINS FAILURE MODULES CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
FEATURES and supply recovers to 5 V. This is achieved
without the need for internal batteries
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)
KEY FEATURES • Five key menu navigation • Advanced SMS messaging
• Configurable inputs (11) • Front panel editing with PIN (additional external modem FREQUENCY RANGE
3.5 Hz to 75 Hz
• Configurable outputs (8) protection required)
• Voltage measurement • 3 configurable maintenance • Start & stop capability via SMS MAINS (UTILITY) (DSE7420)
• Mains (utility) failure detection alarms messaging VOLTAGE RANGE
15 V to 333 V AC (L-N)
• Dedicated load test button • CAN and magnetic pick-up/Alt. • Additional display screens to
• kW overload alarms sensing help with modem diagnostics FREQUENCY RANGE
• Comprehensive electrical • Fuel usage monitor and low fuel • DSENet® expansion 3.5 Hz to 75 Hz
protection alarms • Integral PLC editor
BUS (DSE7410)
• RS232, RS485 & Ethernet • Charge alternator failure alarm VOLTAGE RANGE
remote communications • Manual speed control (on KEY BENEFITS 15 V to 333 V AC (L-N)
• Modbus RTU/TCP compatible CAN engines) • RS232, RS485 & Ethernet can
FREQUENCY RANGE
• PLC functionality • Manual fuel pump control be used at the same time 3.5 Hz to 75 Hz
• Multi event exercise timer • “Protections disabled” feature • DSENet® connection for
MAGNETIC PICK UP
• Back-lit LCD 4-line text display • Reverse power protection system expansion
VOLTAGE RANGE
• Multiple display languages • Power monitoring (kW h, kV Ar, • PLC functionality +/- 0.5 V to 70 V
• Automatic start/Manual start kV A h, kV Ar h) • Five step dummy load support
FREQUENCY RANGE
• Audible alarm • Load switching (load shedding • Five step load shedding support
10,000 Hz (max)
• Fixed and flexible LED indicators and dummy load outputs) • High number of inputs and
• Event log (250) • Automatic load transfer (DSE7420) outputs DIMENSIONS
OVERALL
• Engine protection • Unbalanced load protection • Worldwide language support
240 mm x 172 mm x 57 mm
• Fault condition notification to • Independent earth fault trip • Direct USB connection to PC 9.4” x 6.8” x 2.2”
a designated PC • Fully configurable via DSE • Ethernet monitoring
PANEL CUTOUT
• Front panel mounting Configuration Suite PC software • USB host
220 mm x 160 mm
• Protected front panel • Configurable display languages • Data logging & trending 8.7” x 6.3”
programming • Remote SCADA monitoring via
MAXIMUM PANEL THICKNESS
• Configurable alarms and timers DSE Configuration Suite PC
8 mm
• Configurable start and stop timers software 0.3”
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-108/01/12 (1)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457