You are on page 1of 2

®

DSEGenset

DSE7110/20 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY

AUTO START & AUTO MAINS FAILURE BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
CONTROL MODULES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

The DSE7110 is an Auto Start Both modules offer electronic OPERATING TEMPERATURE
Control Module and the DSE7120 (CAN) and non-electronic (magnetic BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
is an Auto Mains (Utility) Failure pick-up/alternator sensing) engine BS EN 60068-2-2
Control Module suitable for a wide versions and offer an extensive Bb/Be Dry Heat +70 oC
variety of single, diesel or gas, gen- number of flexible inputs, outputs VIBRATION
set applications. and advanced engine protections BS EN 60068-2-6
so the system can be easily Ten sweeps in each of three
major axes
Monitoring speed, frequency, adapted to suit a wide range of 5 Hz to 8 Hz @ +/-7.5 mm,
voltage, current, oil pressure, application demands. 8 Hz to 500 Hz @ 2 gn
coolant temperature and fuel level, HUMIDITY
the modules will display warnings, Enhanced features include a 4-line BS EN 60068-2-30
shutdown and engine status icon display. Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
information on the back-lit LCD BS EN 60068-2-78
screen and illuminated LEDs. The modules can be easily Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
configured using the DSE
Configuration Suite PC software. SHOCK
Front panel editing is also available. BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

4 4 3

USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER


PORT INPUTS SENDERS STOP SUPPLY 8-35V

DEUTZ
DSE7110/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) N/C VOLT FREE N/O VOLT FREE GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT OUTPUT ALTERNATOR OUTPUTS ENGINES OR
DSE7120 ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS CURRENT VOLTS


D+
W/L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N

ISSUE 2

PENDING
®

DSEGenset

DSE7110/20 SPECIFICATION

DC SUPPLY

AUTO START & AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING


8 V to 35 V Continuous

CONTROL MODULES CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


290 mA at 12 V, 140 mA at 24 V
DSE7120
MAXIMUM STANDBY CURRENT
75 mA at 12 V, 40 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

DSE7110 MAINS (UTILITY) DSE7120 ONLY


VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E, F, G & H


2 A DC at supply voltage

GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
KEY FEATURES • Test button (DSE7120 only) information for monitoring and 3.5 Hz to 75 Hz
• Back-lit icon LCD display • Automatic load transfer maintenance periods
MAGNETIC PICK UP
• Five key menu navigation (DSE7120 only) • User-friendly set-up and button VOLTAGE RANGE
• Front panel editing • Battery voltage monitoring layout +/- 0.5 V to 70 V
• LED and LCD alarm indication • Engine pre-heat • Multiple engine parameters are
FREQUENCY RANGE
• Power Save mode • Hours counter monitored simultaneously 10,000 Hz (max)
• 4 Digital inputs • Comprehensive shutdown or • Module can be configured to
• 3 Analogue inputs (2 fixed, 1 warning on fault condition suit individual applications DIMENSIONS
OVERALL
flexible) • Fully configurable via DSE • Compatible with a wide range 240 mm x 181 mm x 42 mm
• 6 configurable outputs Configuration Suite PC software of CAN engines 9.4” x 7.1” x 1.6”
• Configurable timers and alarms • USB connectivity • Uses DSE Configuration Suite
PANEL CUT-OUT
• Alternative configuration • Remote SCADA monitoring via PC software for simplified 220 mm x 160 mm
• Event Log (5) DSE Configuration Suite PC configuration 8.7” x 6.3”
• CAN and Magnetic Pick up / software • IP65 rating (with supplied
MAXIMUM PANEL THICKNESS
Alt. sensing gasket) offers increased 8 mm
• 3 Phase generator monitoring KEY BENEFITS resistance to water ingress 0.3”
• Current monitoring and • Automatically transfers between • Licence-free software
STORAGE TEMPERATURE RANGE
protection mains (utility) and generator -40 oC to +85 oC
• 3 Phase Mains (Utility) power (DSE7120 only)
monitoring (DSE7120 only) • Hours counter provides accurate OPERATING TEMPERATURE RANGE
-30°C TO +70°C

RELATED MATERIALS
TITLE PART NO’S
DSE7110 Installation Instructions 053-080
DSE7120 Installation Instructions 053-081
DSE7100 Operator Manual 057-113
DSE7100 Configuration Suite PC Manual 057-117

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-081/10/11 (4)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

You might also like