You are on page 1of 2

®

DSEGenset

DSE8610 ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITY


SYNCHRONISING AUTO START LOAD SHARE BS EN 61000-6-2
EMC Generic Immunity Standard for the

CONTROL MODULE Industrial Environment


BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment

FEATURES ELECTRICAL SAFETY


BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

TEMPERATURE
BS EN 60068
Ab/Ae Cold Test -30oC
The DSE8610 is an easy to use The event log will record 250 events KEY LOAD SHARE FEATURES: BS EN 60068-2-2
Synchronising Auto Start Control to facilitate easy maintenance. An • Peak lopping/sharing (with Bb/Be Dry Heat +70oC
Module suitable for use in a extensive number of fixed and DSExx60)
VIBRATION
multi-generator loadshare system, flexible monitoring, metering and • Sequential set start BS EN 60068-2-6
designed to synchronise up to 32 protection features are included • Manual voltage/frequency Ten sweeps in each of three major axes
generators including electronic and as well as comprehensive adjustment 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
non-electronic engines. communication and system • R.O.C.O.F. and vector shift HUMIDITY
expansion options. protection BS EN 60068-2-30
The DSE8610 monitors the • Generator load demand Db Damp Heat Cyclic 20/55oC @ 95% RH
48 Hours
generator and indicates operational Using the DSE PC Configuration • Automatic hours run balancing BS EN 60068-2-78
status and fault conditions, Suite Software allows easy • Mains (Utility) de-coupling Cab Damp Heat Static 40oC @ 93% RH
automatically starting or stopping alteration of the operational • Mains (Utility) de-coupling 48 Hours

the engine on load demand or fault sequences, timers and alarms. With test mode SHOCK
condition. all communication ports capable of • Dead bus sensing BS EN 60068-2-27
being active at the same time, the • Bus failure detection Three shocks in each of three major axes
15gn in 11mS
System alarms are annunciated on DSE8610 is ideal for a wide variety • Direct governor and AVR control
the LCD screen (multiple language of demanding load share • Volts and frequency matching DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
options available), illuminated LED applications. • kW and kV Ar load sharing BS EN 60529
and audible sounder. • Dead bus synchronising IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY


OF LOAD SHARE APPLICATIONS
DSE2130 MODEM MODBUS PC
DSE2131
DSE2133
DSE2152 11 6 4
DSE2157
DSE2548 232 485

DSENET® RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
+
ETHERNET

DEUTZ
DSE8610 MSC
ISUZU
PERKINS
CATERPILLAR
MTU
7 55xx ­75xx ­8xxx VOLVO
OTHER
CUMMINS
SCANIA

BUS VOLT FREE GENERATOR SENSING FUEL & START CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
CURRENT VOLTS
D­+
+ W/L

1ph 2 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N

ISSUE 3
®

DSEGenset

DSE8610 SPECIFICATION

DC SUPPLY
SYNCHRONISING AUTO START LOAD SHARE CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CONTROL MODULE CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
FEATURES supply was at least 10 V before dropout
and
supply recovers to 5 V. This is achieved
without the need for internal batteries

MAXIMUM OPERATING CURRENT


460 mA at 12 V, 245 mA at 24 V

MAXIMUM STANDBY CURRENT


375 mA at 12 V, 200 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G,H,I & J


2 A DC at supply voltage

GENERATOR & BUS


KEY FEATURES • CAN, MPU and Frequency speed KEY BENEFITS VOLTAGE RANGE
• Comprehensive synchronising & sensing • Compatible in load share systems 15 V to 333 V AC (L-N)
loadsharing capabilities • Tier 4 CAN engine support containing DSE5500, DSE7500 FREQUENCY RANGE
• Built-in governor and AVR control • “Protections disabled” feature and DSE8600 series. Contact DSE 3.5 Hz to 75 Hz
• Base load (kW export) • Front panel editing with PIN for further details
MAGNETIC PICK-UP
functionality protection • 132 x 64 pixel ratio display for VOLTAGE RANGE
• Positive & negative kVAr export • Fully configurable using DSE clarity +/- 0.5 V to 70 V
control Configuration Suite PC software • Real-time clock provides accurate
FREQUENCY RANGE
• Mains (utility) de-coupling via USB event logging 10,000 Hz (max)
protection • 4 Line back-lit LCD text display • Ethernet communication, provides
• Generator power (kW, kV Ar, kV A • LED and LCD alarm indication builit in advanced remote BUILT-IN GOVERNOR CONTROL
MINIMUM LOAD IMPEDANCE
& pf) monitoring • Configurable display languages monitoring. 1000Ω
• Overload (kW & kV Ar) protection • USB connectivity • Can be integrated into building Fully isolated
• Reverse power (kW & kV Ar) • Customisable status screens management systems (BMS) and GAIN VOLTAGE
protection • Five key menu navigation programmable logic control (PLC) 0 V to 10 V DC
• Unbalanced load protection • 3 Configurable maintenance • Increased input and output Fully isolated

• Independent earth fault protection alarms expansion capability via DSENet® OFFSET VOLTAGE
• Advanced integral PLC editor • Multiple date and time run • Licence-free PC software +/- 10 V DC
Fully isolated
• 11 Configurable inputs scheduler • IP65 rating (with supplied gasket)
• 8 Configurable outputs • Manual fuel pump control offers increased resistance to water BUILT-IN AVR CONTROL
• Configurable flexible sensor inputs • Fuel usage monitor and low fuel ingress MINIMUM LOAD IMPEDANCE
1000Ω
• DSENet® expansion compatibility level protection • Advanced Internal PLC editor allows Fully isolated
• User configurable RS232, RS485 • Charge alternator failure user configurable functions to meet
GAIN VOLTAGE
and Ethernet communications protection specific application requirements. 0 V to 10 V DC
• Remote SCADA monitoring via • Load switching (load shedding Fully isolated
various DSE software applications and dummy load control) EXPANSION DEVICES
• DSE124 CAN/MSC Extender OFFSET VOLTAGE
• MODBUS RTU & TCP support • Configurable event log (250) +/- 10 V DC
• User configurable MODBUS • Backed up real time clock • DSE2130 Input Expansion Module Fully isolated
• DSE2131 Ratio-metric Input Expansion
pages
Module DIMENSIONS
• Advanced SMS control and fault • DSE2133 RTD & Thermo-couple OVERALL
messaging (additional GSM Expansion Module 240 mm x 181 mm x 42 mm
9.4” x 6.8” x 1.6”
modem required) • DSE2152 Ratio-metric Output
• Easy access diagnostic pages Expansion Module PANEL CUTOUT
including modem diagnostic pages • DSE2157 Output Expansion Module 220 mm x 160 mm
8.7” x 6.3”
• Data logging and trending • DSE2548 LED Expansion Module
MAXIMUM PANEL THICKNESS
RELATED MATERIALS 8 mm
0.3”
TITLE PART NO’S
DSE8610 Installation Instructions 053-069 OPERATING TEMPERATURE RANGE
DSE8610 Operator Manual 057-115 -30 oC to +70 oC
DSE8600 PC Configuration Suite Manual 057-119
DSE8660 Date Sheet 055-086 STORAGE TEMPERATURE RANGE
-40 oC to +85 oC

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-083/03/12 (9) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

You might also like