You are on page 1of 2

®

DSEGenset

DSE8620 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
SYNCHRONISING AUTO MAINS FAILURE BS EN 61000-6-2
EMC Generic Immunity Standard for
CONTROL MODULE the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE8620 is an Auto Mains Comprehensive communications With all communication ports
TEMPERATURE
(Utility) Failure Control Module are also available via RS232, capable of being active at the same BS EN 60068-2-1
suitable for paralleling single RS485 & Ethernet for remote PC time, the DSE8xxx Series is ideal Ab/Ae Cold Test -30 oC
gensets (diesel or gas) with the control and monitoring, and for a wide variety of demanding BS EN 60068-2-2
load share applications. Bb/Be Dry Heat +70 oC
mains (utility) supply. Designed to integration into building
synchronise a single genset with a management systems. VIBRATION
single mains (utility) supply, the The comprehensive event log will KEY LOAD SHARE FEATURES: BS EN 60068-2-6
• Peak lopping/sharing Ten sweeps in each of three
DSE8620 will automatically control record up to 250 events to facilitate major axes
the change over from mains (utility) maintenance. • Manual voltage/frequency 5 Hz to 8 Hz @ +/-7.5 mm,
to generator supply or run the adjustment 8 Hz to 500 Hz @ 2 gn

generator in synchronisation with An extensive number of fixed and • R.O.C.O.F. and vector shift HUMIDITY
the mains (utility) to provide flexible monitoring and protection protection BS EN 60068-2-30
• Generator load demand Db Damp Heat Cyclic 20/55 oC
no-break, peak lopping and peak features are included. Easy @ 95% RH 48 Hours
shaving power solutions. alteration of the sequences, timers • Mains (Utility) de-coupling BS EN 60068-2-78
• Mains (Utility) de-coupling Cab Damp Heat Static 40 oC
and alarms can be made using the @ 93% RH 48 Hours
The module can indicate DSE PC Configuration Suite test mode
operational status and fault Software. Selected configuration is • Direct governor & AVR control. SHOCK
• Volts and frequency matching. BS EN 60068-2-27
conditions on the LCD screen also available via the module’s front Three shocks in each of three major axes
(multiple languages available), by panel. • kW & kV Ar load sharing 15 gn in 11 mS
illuminated LED, audible sounder DEGREES OF PROTECTION
and SMS messaging. PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST FOR SINGLE


GEN-SET PARALLELING WITH MAINS (UTILITY)
DSE2130 MODEM MODBUS PC
DSE2131
DSE2133
DSE2152 11 6 4
DSE2157
DSE2548 232 485

DSENET RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V

ETHERNET
+

DEUTZ
DSE8620 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) SENSING N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
FLEXIBLE WITH CAN MAGNETIC PICK-UP
VOLTS CURRENT CURRENT VOLTS
D+
W/L +

1ph 1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISSUE 1
®

DSEGenset

DSE8620 SPECIFICATION

DC SUPPLY
SYNCHRONISING AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous

CONTROL MODULE CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
FEATURES supply was at least 10 V before dropout
and
supply recovers to 5 V. This is achieved
without the need for internal batteries

MAXIMUM OPERATING CURRENT


460 mA at 12 V, 245 mA at 24 V

MAXIMUM STANDBY CURRENT


375 mA at 12 V, 200 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
KEY FEATURES • Advanced SMS control and fault KEY BENEFITS
• Mains (utility) failure detection messaging (additional GSM • Compatible with DSE8003 AUXILIARY OUTPUTS E,F,G,H,I & J
• Comprehensive synchronising & modem required) • 132 x 64 pixel ratio display for 2 A DC at supply voltage
loadsharing capabilities • Easy access diagnostic pages clarity GENERATOR & MAINS
• Built-in governor and AVR control including modem diagnostic • Real-time clock provides accurate VOLTAGE RANGE
• Base load (kW export) pages event logging 15 V to 333 V AC (L-N)

functionality • Data logging and trending • Ethernet communication, provides FREQUENCY RANGE
• Positive & negative kVAr export • CAN, MPU and Frequency speed builit in advanced remote 3.5 Hz to 75 Hz
control sensing monitoring.
MAGNETIC PICK-UP
• Peak lopping & shaving • Tier 4 CAN engine support • Can be integrated into building VOLTAGE RANGE
functionality • “Protections disabled” feature management systems (BMS) and +/- 0.5 V to 70 V
• Mains (utility) power (kW, kV Ar, • Front panel editing with PIN programmable logic control (PLC) FREQUENCY RANGE
kV A & pf) monitoring protection • Increased input and output 10,000 Hz (max)
• Mains (utility) de-coupling • Fully configurable using DSE expansion capability via DSENet®
BUILT-IN GOVERNOR CONTROL
protection Configuration Suite PC software • Licence-free PC software MINIMUM LOAD IMPEDANCE
• Generator power (kW, kV Ar, kV A via USB • IP65 rating (with supplied gasket) 1000Ω
& pf) monitoring • 4 Line back-lit LCD text display offers increased resistance to water Fully isolated

• Overload (kW & kV Ar) protection • LED and LCD alarm indication ingress GAIN VOLTAGE
• Reverse power (kW & kV Ar) • Configurable display languages • Advanced Internal PLC editor allows 0 V to 10 V DC
Fully isolated
protection • USB connectivity user configurable functions to meet
• Mains (utility) kW export protection • Customisable status screens specific application requirements. OFFSET VOLTAGE
• Unbalanced load protection • Five key menu navigation +/- 10 V DC
Fully isolated
• Independent earth fault • 3 Configurable maintenance EXPANSION DEVICES
protection alarms • DSE124 CAN/MSC Extender BUILT-IN AVR CONTROL
• Advanced integral PLC editor • Multiple date and time run • DSE2130 Input Expansion Module MINIMUM LOAD IMPEDANCE
• DSE2131 Ratio-metric Input Expansion 1000Ω
• 11 Configurable inputs scheduler Fully isolated
Module
• 8 Configurable outputs • Manual fuel pump control • DSE2133 RTD & Thermo-couple GAIN VOLTAGE
• Configurable flexible sensor inputs • Fuel usage monitor and low fuel Expansion Module 0 V to 10 V DC
• DSENet® expansion compatibility level protection • DSE2152 Ratio-metric Output Fully isolated
• User configurable RS232, RS485 • Charge alternator failure Expansion Module
OFFSET VOLTAGE
and Ethernet communications protection • DSE2157 Output Expansion Module +/- 10 V DC
• Remote SCADA monitoring via • Load switching (load shedding • DSE2548 LED Expansion Module Fully isolated
various DSE software and dummy load control) DIMENSIONS
applications • Configurable event log (250) OVERALL
• MODBUS RTU & TCP support • Backed up real time clock 240 mm x 181 mm x 42 mm
9.4” x 6.8” x 1.6”
• User configurable MODBUS
pages PANEL CUTOUT
220 mm x 160 mm
8.7” x 6.3”
RELATED MATERIALS
TITLE PART NO’S MAXIMUM PANEL THICKNESS
8 mm
DSE8620 Installation Instructions 053-129 0.3”
DSE8620 Operator Manual 057-142
DSE8600 PC Configuration Suite Manual 057-119 OPERATING TEMPERATURE RANGE
-30 oC to +70 oC

STORAGE TEMPERATURE RANGE


DEEP SEA ELECTRONICS INC USA -40 oC to +85 oC
3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com
055-099/05/11 (5) US
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457