You are on page 1of 38

TECHNICAL SITE SURVEY REPORT

PROJECT NAME : MOCN-Phase

SITE NAME : REJASABANJARNEGARA_PL

SITE ID : 14BJN0058

CITY : Banjarnegara

AREA : Central Java

SITE TYPE : Green Field

Banjarnegara, Rejasa, Kec. Madukara, Kab. Banjarnegara, Jawa


ADDRESS : Tengah

SITE OWNER :

West Java

Approved By,
INDOSAT OOREDOO - MS EID INDOSAT OOREDOO - OPERATION INDOSAT OOREDOO - PROJECT

INDOSAT OOREDOO - PLANNING

Ahmad Arwan Asy'ari


G
E
N
E
R
A
L
IN
F
O Project Name MOCN-Phase
R Site Name REJASABANJARNEGARA_PL City Banjarnegara AREA Central Java
M Site ID 14BJN0058 Longitude -7.3875 Latitude 109.6896
A Street Address Banjarnegara, Rejasa, Kec. Madukara, Kab. Banjarnegara, Jawa Tengah
TI Site Type Green Field Site Owner Date of Survey 25-Mar-23
O Shelter Type Green Field
N List of Surveyor:
No. Name Company E-mail Cell Phone
1 M.Iqbal 082361683238
2
3
List of Customer PIC:
No. Name Company E-mail Cell Phone
1 Bastoni PT. Indosat 081533100993
2
3
List of Proposed Equipments:
SCOPE Weight
Cabinet Dimension
No. Equipment Type (SWAP/UPGRAD Power (Watt) MCB DC/AC Equipm Load
Quantity (W x D x H) mm
E/NEW) ent (kg)
W D H kg Kg/m2

1 N540X-16Z8Q2C-D 1 NEW 60 60 200 1664 63Ax4 DC 500 1,389


-
-
-
-
-
-
Site Name REJASABANJARNEGARA_PL CITY Banjarnegara
Site ID 14BJN0058 AREA Central Java

RESULT SURVEY

Scope NEW -N540X-16Z8Q2C-D - MOCN-Phase


Project MOCN-Phase

NO ITEM STATUS KETERANGAN


1 TYPE OWNER INDOSAT/TBG/CMI/DMT
2 TYPE SITE ROOF TOP/ GREEN FIELD/ INDOOR BUILDING/CO Green Field
3 PERANGKAT N540X-16Z8Q2C
4 SPACE OK LOKASI Green Field
5 OTB NOK LOKASI Green Field
6 MCB PDU A NONE PROP. MCB NEW (A)= X PCS
LOAD (A) = 0
7 MCB PSU 1 NONE PROP. MCB NEW (A)= X PCS
LOAD (A) =
8 MCB PSU 2 NONE PROP. MCB NEW (A)= X PCS
LOAD (A) =
9 MCB PDU B NONE PROP. MCB NEW (A)= X PCS
LOAD (A) = 0
10 MCB PSU 3 NONE PROP. MCB NEW (A)= X PCS
LOAD (A) =
11 MCB PSU 4 NONE PROP. MCB NEW (A)= X PCS
LOAD (A) =
12 PLN OK 7040VA UPGRADE KE 0
13 GENSET #DIV/0! - VA UPGRADE KE Manual InpVA
14 RECTIFIER 1 OK Outdoor -Huawei--4 Utilisasi (%) 18%
BUT ADD BATTERY BUT 0.0
Remarks
15 RECTIFIER 2 OK --- Utilisasi (%) 0%
BUT ADD BATTERY BUT 0.0
Remarks
16 RECTIFIER 3 OK --- Utilisasi (%) 0%
BUT ADD BATTERY BUT 0.0
Remarks
17 RECTIFIER 4 OK --- Utilisasi (%) 0%
BUT 0 BUT #DIV/0!
Remarks
18 MCB RECTIFIER OK Use MCB available 4x63A in DCPDB Shelter 2 (Single source)

19 SINGLE/DUAL Single Power Single source dual feed, konek ke DCPDB power dari Recty indoor eltek FP2 48/3000W

20 UPS 1 #VALUE! UPS 1 - huawei - x kVA Utilisasi (%) #VALUE!


BUT UPGRADE BATT BUT -
Remarks
21 UPS 2 #VALUE! UPS 2 - Liebert nx 80 - x kVA Utilisasi (%) #VALUE!
BUT BUT -
Remarks
22 SINGLE/DUAL Dual Dual => Koneksi Dual Power UPS from UPS & , MCB => OK -
20 GROUNDING NOK Need new hole
21 AC SPLIT ADD AC SPLIT 0
22 PONDASI RECT OUTDOOR OK
23 SPACE UNTUK RECT OUTDOOR OK
24 SHELTER TYPE CKD with H BEAM/CKD with CONCRETE/CONCRECKD with Concrete
25 Floor Load Equipment (max 650 kg/m2) NOK 1388.88888888889 kg/m2 0 kg/m2 0 kg/m2

26 SUMARY RESULT SURVEY #DIV/0!


Site Name REJASABANJARNEGARA_PL CITY Banjarnegara
Site ID 14BJN0058 AREA Central Java

3. SURVEY DATA

‘- Cabinet :
* Cabinet Quantity: _3_Unit
* Subrack Quantity: 3
* Floor Height (mm): __0__mm
* Cabling mode (Up/Down): __Upward__
* Cable Tray Height: __3000__mm

A. Space :
* 3 Cabinet Expansion proposed in Ancol Data Center Room Contaiment01
* 3 New Subrack in New Cabinet

B. Power Supply :
* 3 Subrack, 2 Storage , 6 Switch and19 Server Expansion total 23779 watt
* New Cabinet will be connected to the Existing ACPDU-A & ACPDU-B
Proposed MCB 6*32A at Existing ACPDU-A
Proposed MCB 6*32A at Existing ACPDU-B
* Proposed New Power Cable 6*25 Meter and 6*15 Meter Total 240 Meter
* Power Cable 3x6mm
* Need Scun 12x4 for connecting to Legrand

C. Connection :
For connection DCGW to CN via OTB
3.1 Connection:
DCGW to CN-1 Connection (via OTB):
> Type : LC/PC - FC/PC
> Type : QSFP 100GB SM
> Length : Single Length : 25 m (from DCGW to OTB, and from OTB ot CN-2 same length)
DCGW to CN-2 Connection (via OTB):
> Type : LC/PC - FC/PC
> Type : QSFP 100GB SM
> Length : Single Length : 25 m (from DCGW to OTB, and from OTB ot CN-2 same length)
Customer provide QSFP (4x100G), SM, Cysco
3. PLN & GENSET CALCULATION
SITE NAME REJASABANJARNEGARA_PL CITY Banjarnegara

SITE ID 14BJN0058 AREA Central Java

PLN UNIT KWH ATS REMARKS


TRAFO
MEREK
CAPACITY kVA
KWH
IDPEL 522041555982
Phase 1 / 3 Phase 1
PLN MCB Capacity (Each Phase) Ampere 32
PLN Capacity VA 7040
R Current Load (Measured) Ampere 4.2
S Current Load (Measured) Ampere 0
T Current Load (Measured) Ampere 0
N Current Load (Measured) Ampere 5
TOTAL LOAD PLN VA 924
R-N Voltage Volt 215
S-N Voltage Volt 215
T-N Voltage Volt 213
N - PE Voltage Volt 0
MCB Idle/Spare 0
GENSET UNIT GENSET 1 GENSET 2 GENSET 3 REMARKS
Brand
Type (Silent / Non Silent )
YEAR OF INSTALLATION
Genset Room (Canopy / Room)
kVA Capacity VA
Quantity unit
Condition
ACPDB UNIT ACPDB 1 ACPDB 2 REMARKS
Phase 1 / 3 Phase 3
ACPDB MCB Capacity Ampere 25
R Current Load (Measured) Ampere 5
S Current Load (Measured) Ampere 4.8
T Current Load (Measured) Ampere 0.6
MCB Idle/Spare
PLN & GENSET Calculation
Existing Load VA 924 DIAMETER CABLE
Battery Charging Rectifier VA 0 FROM KWH TO ATS (Mandatory)
Battery Charging UPS Type NYFGBY
VA -
PLN Utilization before add new Diameter 4x25 mm²
load % 13%
Genset Utilization before % #DIV/0! FROM ATS TO ACPDB (Mandatory)
add new load
Location SHELTER 1 ACPDB 1
NEW LOAD
New Equipment VA 1664 Diameter 4x25 mm²

New Air Condition ( if any Type NYFGBY


changes from previous
Cooling capacity or running Watt 0
sequence)
VA 0 Length m
New Rectifier Watt 0 Location SHELTER 2 ACPDB 2
VA 0 Diameter 4x25 mm²
New Battery Cap/Ah 0 Type NYFGBY
Qty 0 Length m
Charging 0 Location SHELTER 3 ACPDB 3
New UPS Cap/Ah 0 Diameter mm²
Qty 0 Type
Charging 0 Length m
Total AC Power VA 1664 Location
Requirement
STATUS Diameter mm²
Remain Power PLN VA 4452 Type
Remain Power Genset Length
VA -2588
m
PLN Utilization after add
new load % 37%
Genset Utilization after add % #DIV/0!
new load
RESULT
PLN
THRESHOLD PLN % 80%
STATUS OK/UPGRADE OK
TOTAL REQUIREMENT VA 0
UPGRADE TO VA 0
UTILIZATION AFTER UGRADE %
GENSET
THRESHOLD GENSET % 80%
STATUS OK/UPGRADE #DIV/0!
UPGRADE TO VA 20000
UTILIZATION AFTER UGRADE %
REMARKS

PLN OK

APABLA PLN TIDAK BISA DI TES,CEK DI INPUT ATS


4a. RECTIFIER CALCULATION
Site Name REJASABANJARNEGARA_PL CITY Banjarnegara

Site ID 14BJN0058 AREA Central Java


GENERAL
DC POWER SYSTEM UNIT Power System 1 Power System 2 Power System 3 Power System 4 Power System 5 Power System 6 REMARKS
Location: Shelter/Outdoor Outdoor
Brand Huawei
Type Module Rectifier
YEAR OF INSTALLATION
Capacity per Rectifier Module Watt 3000
Maximum Rectifier Modules Slot Pcs 6
Qty of Rectifier Module Installed Slot 4
Available Modules Slot Pcs 2
Current Max Output (Rating) Ampere 217.79
Float Voltage Volt 55.1
Boost Voltage Volt 56.0 56.0 56.0 56.0 56.0 56.0
DC Current Load (Measured) Ampere If display can not reading please check manual
Rectifier Efficiency % 90% 90% 90% 90% 90% 90% 90%
Battery UNIT Battery 1 Battery 2 Battery 3
Brand
Type
YEAR OF INSTALLATION
Charge Coefficient % 10% 10% 10% 10% 10% 10%
Capacity Ah
Qty of Banks Banks
Total Battery Capacity Ah 0 0 0 0 0 0
DC POWER CALUCATION
Existing Load Watt 0 0 0 0 0 0 0
Battery Charging Watt 0 0 0 0 0 0 0
Proposed Equipment
N540X-16Z8Q2C-D Watt 1664 1664 1664
0 Watt 0 0
0 Watt 0 0
0 Watt 0 0
0 Watt 0 0
Total Proposed Equipment Watt 1664 1664 1664 0 0 0 6240
Total Load Watt 1664 1664 1664 0 0 0 6240
Capacity Rectifier with redudancy (n-1) Watt 9000 0 0 0 0 0
Rectifier Existing Utilization % 0% 0% 0% 0% 0% 0%
Rectifier Existing + New Load Utilization % 18% 0% 0% 0% 0% 0%
Remain Power Watt 7336 -1664 -1664 0 0 0
RESULT
THRESHOLD CAPACITY RECTIFIER 100% 100% 100% 100% 100% 100% 100%
STATUS RECTIFIER OK/ADD OK OK OK OK OK OK
TYPE MODULE 0 0 0 0 0 0
ADD MODULE Pcs 0 0 0 0 0 0
AVAILABLE SLOT Pcs 2 0 0 0 0 0
NEW CAPACITY WITH REDUDANCY (N-1) Watt 9000 0 0 0 0 0
RECTIFIER ULITIZATION AFTER EXPANSION % 18% 0% 0% 0% 0% 0%
BATTERY CALUCATION
Battery Backup Time Load Existing hours 0.0 0.0 0.0 0.0 0.0 0.0
Battery Backup Time Load Existing + New :oad hours 0.0 0.0 0.0 #DIV/0! #DIV/0! #DIV/0!
RESULT
THRESHOLD BACKUP TIME 2 hrs 2 2 2 2 2 2
TOTAL LOAD Ampere 35 35 35 0 0 0
STATUS BATTERY ADD BATTERY ADD BATTERY ADD BATTERY 0 0 0
MEREK 0 0 0 0 0 0
TYPE BATTERY 0 0 0 0 0 0
CAPACITY Ah 0 0 0 0 0 0
ADD BATTERY Banks 0 0 0 0 0 0
BACKUP TIME AFTER ADD BATTERY hours 0.0 0.0 0.0 0.0 0.0 0.0
CONECTION POWER Main / Main +Redundant
Redundant
NOTE FROM CORE INRASTRUCTURE DESIGN & SOLUTION
POWER Single Power Single source dual feed, konek ke DCPDB power dari Recty indoor eltek FP2 48/3000W
MCB OK Use MCB available 4x63A in DCPDB Shelter 2 (Single source)
SPACE OK
GROUNDING NOK Need new hole
4b. RECTIFIER CALCULATION
Site Name REJASABANJARNEGARA_PL CITY Banjarnegara

Site ID 14BJN0058 AREA Central Java


GENERAL
DC POWER SYSTEM UNIT Power System 7 Power System 8 Power System 9 Power System 10 Power System 11 Power System 12 REMARKS
Location: Shelter/Outdoor
Brand
Type Module Rectifier
YEAR OF INSTALLATION
Capacity per Rectifier Module Watt
Maximum Rectifier Modules Slot Pcs
Qty of Rectifier Module Installed Slot
Available Modules Slot Pcs
Current Max Output (Rating) Ampere
Float Voltage Volt
Boost Voltage Volt 56.0 56.0 56.0 56.0 56.0 56.0
DC Current Load (Measured) Ampere If display can not reading please check manual
Rectifier Efficiency % 90% 90% 90% 90% 90% 90% 90%
Battery UNIT Battery 1 Battery 2 Battery 3
Brand
Type
YEAR OF INSTALLATION
Charge Coefficient % 10% 10% 10% 10% 10% 10%
Capacity Ah
Qty of Banks Banks
Total Battery Capacity Ah 0 0 0 0 0 0
DC POWER CALUCATION
Existing Load Watt 0 0 0 0 0 0 0
Battery Charging Watt 0 0 0 0 0 0 0
Proposed Equipment
N540X-16Z8Q2C-D Watt 1664 1664 1664
0 Watt 0 0
0 Watt 0 0
0 Watt 0 0
0 Watt 0 0
Total Proposed Equipment Watt 1664 1664 1664 0 0 0 6240
Total Load Watt 1664 1664 1664 0 0 0 6240
Capacity Rectifier with redudancy (n-1) Watt 0 0 0 0 0 0
Rectifier Existing Utilization % 0% 0% 0% 0% 0% 0%
Rectifier Existing + New Load Utilization % 0% 0% 0% 0% 0% 0%
Remain Power Watt -1664 -1664 -1664 0 0 0
RESULT
THRESHOLD CAPACITY RECTIFIER 100% 100% 100% 100% 100% 100% 100%
STATUS RECTIFIER OK/ADD OK OK OK OK OK OK
TYPE MODULE 0 0 0 0 0 0
ADD MODULE Pcs 0 0 0 0 0 0
AVAILABLE SLOT Pcs 0 0 0 0 0 0
NEW CAPACITY WITH REDUDANCY (N-1) Watt 0 0 0 0 0 0
RECTIFIER ULITIZATION AFTER EXPANSION % 0% 0% 0% 0% 0% 0%
BATTERY CALUCATION
Battery Backup Time Load Existing hours 0.0 0.0 0.0 0.0 0.0 0.0
Battery Backup Time Load Existing + New :oad hours 0.0 0.0 0.0 #DIV/0! #DIV/0! #DIV/0!
RESULT
THRESHOLD BACKUP TIME 2 hrs 2 2 2 2 2 2
TOTAL LOAD Ampere 35 35 35 0 0 0
STATUS BATTERY ADD BATTERY ADD BATTERY ADD BATTERY 0 0 0
MEREK 0 0 0 0 0 0
TYPE BATTERY 0 0 0 0 0 0
CAPACITY Ah 0 0 0 0 0 0
ADD BATTERY Banks 0 0 0 0 0 0
BACKUP TIME AFTER ADD BATTERY hours 0.0 0.0 0.0 0.0 0.0 0.0
CONECTION POWER Main / Main +Redundant
Redundant
NOTE FROM CORE INRASTRUCTURE DESIGN & SOLUTION
POWER
MCB
SPACE
GROUNDING
4c. RECTIFIER CALCULATION
Site Name REJASABANJARNEGARA_PL CITY Banjarnegara

Site ID 14BJN0058 AREA Central Java


GENERAL
DC POWER SYSTEM UNIT Power System 13 Power System 14 Power System 15 Power System 16 Power System 17 Power System 18 REMARKS
Location: Shelter/Outdoor
Brand
Type Module Rectifier
YEAR OF INSTALLATION
Capacity per Rectifier Module Watt
Maximum Rectifier Modules Slot Pcs
Qty of Rectifier Module Installed Slot
Available Modules Slot Pcs
Current Max Output (Rating) Ampere
Float Voltage Volt
Boost Voltage Volt 56.0 56.0 56.0 56.0 56.0 56.0
DC Current Load (Measured) Ampere If display can not reading please check manual
Rectifier Efficiency % 90% 90% 90% 90% 90% 90% 90%
Battery UNIT Battery 1 Battery 2 Battery 3
Brand
Type
YEAR OF INSTALLATION
Charge Coefficient % 10% 10% 10% 10% 10% 10%
Capacity Ah
Qty of Banks Banks
Total Battery Capacity Ah 0 0 0 0 0 0
DC POWER CALUCATION
Existing Load Watt 0 0 0 0 0 0 0
Battery Charging Watt 0 0 0 0 0 0 0
Proposed Equipment
N540X-16Z8Q2C-D Watt 1664 1664 1664
0 Watt 0 0
0 Watt 0 0
0 Watt 0 0
0 Watt 0 0
Total Proposed Equipment Watt 1664 1664 1664 0 0 0 6240
Total Load Watt 1664 1664 1664 0 0 0 6240
Capacity Rectifier with redudancy (n-1) Watt 0 0 0 0 0 0
Rectifier Existing Utilization % 0% 0% 0% 0% 0% 0%
Rectifier Existing + New Load Utilization % 0% 0% 0% 0% 0% 0%
Remain Power Watt -1664 -1664 -1664 0 0 0
RESULT
THRESHOLD CAPACITY RECTIFIER 100% 100% 100% 100% 100% 100% 100%
STATUS RECTIFIER OK/ADD OK OK OK OK OK OK
TYPE MODULE 0 0 0 0 0 0
ADD MODULE Pcs 0 0 0 0 0 0
AVAILABLE SLOT Pcs 0 0 0 0 0 0
NEW CAPACITY WITH REDUDANCY (N-1) Watt 0 0 0 0 0 0
RECTIFIER ULITIZATION AFTER EXPANSION % 0% 0% 0% 0% 0% 0%
BATTERY CALUCATION
Battery Backup Time Load Existing hours 0.0 0.0 0.0 0.0 0.0 0.0
Battery Backup Time Load Existing + New :oad hours 0.0 0.0 0.0 #DIV/0! #DIV/0! #DIV/0!
RESULT
THRESHOLD BACKUP TIME 2 hrs 2 2 2 2 2 2
TOTAL LOAD Ampere 35 35 35 0 0 0
STATUS BATTERY ADD BATTERY ADD BATTERY ADD BATTERY 0 0 0
MEREK 0 0 0 0 0 0
TYPE BATTERY 0 0 0 0 0 0
CAPACITY Ah 0 0 0 0 0 0
ADD BATTERY Banks 0 0 0 0 0 0
BACKUP TIME AFTER ADD BATTERY hours 0.0 0.0 0.0 0.0 0.0 0.0
CONECTION POWER Main / Main +Redundant
Redundant
NOTE FROM CORE INRASTRUCTURE DESIGN & SOLUTION
POWER
MCB
SPACE
GROUNDING
5 AIR COOLING CALCULATION
Site Name REJASABANJARNEGARA_PL CITY Banjarnegara

Site ID 14BJN0058 AREA Central Java

Location / Room / Shelter Shelter 1 Shelter 2


Type (AC Split / In Row / In Room)
Dimension Room Length (m)
Width (m)
Area (m²)
LAMP UNIT
MEREK
CAPACITY PK
YEAR OF INSTALLATION
TEMPERATURE INSIDE °C
QUANTITY Pcs
POWER COOLING Watt 0 0 0 0 0 0
CAPACITY COOLING Watt 0 0 0 0 0 0 0 0
COOLING CALCULATION
EQUIPMENT Watt 0 0 0 0 0 0 0 0
LAMP Watt 0 0 0 0 0 0 0 0
AIR CONDITION EXISTING Watt - - - - - - - -
COOLING EXISTING UTILIZATION %
Watt 1664 1664
NEW LOAD
Watt 1,664.00 1,664.00
COOLING EXISTING + NEW LOAD %
UTILIZATION
RESULT
THRESHOLD COOLING % 80% 80% 80% 80% 80% 80% 80% 80%
STATUS COOLING OK/ADD ADD AC SPLIT ADD AC SPLIT
CAPACITY PK 0 0 0 0 0 0 0 0
REMAIN CAPACITY COOLING Watt (1,664.00) (1,664.00) - - - - - -
QUANTITY Unit

REMARKS
6. UPS POWER CALCULATION
Site Name REJASABANJARNEGARA_PL CITY Banjarnegara

Site ID 14BJN0058 AREA Central Java

UPS UNIT UPS 1 UPS 2 UPS 3 UPS 4 UPS 5 UPS 6 UPS 7 UPS 8
Room / Location R. power R. power R. power R. power R. power R. power R. power R. power
UPS Brand huawei Liebert nx 80 huawei Liebert nx 81 huawei Liebert nx 82 huawei Liebert nx 83
UPS Capacity kVA
N Unit
Quantity
N-1 Unit 0 0 0 0 0 0 0 0
80% kVA #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
UPS Avalibility (N-1)
VA #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
EXISTING LOAD
R Current Load (Display Ampere) Ampere 86.9 84.7 82.5 80.3 78.1 75.9 73.7 71.5
S Current Load (Display Ampere) Ampere 102.3 83 63.7 44.4 25.1 5.8 -13.5 -32.8
T Current Load (Display Ampere) Ampere 99.5 89.5 79.5 69.5 59.5 49.5 39.5 29.5
R Current Load (Display kVA) kVA 20.1 19.5 18.9 18.3 17.7 17.1 16.5 15.9
S Current Load (Display kVA) kVA 23.6 19.3 15 10.7 6.4 2.1 -2.2 -6.5
T Current Load (Display kVA) kVA 22.8 20.6 18.4 16.2 14 11.8 9.6 7.4
TOTAL LOAD Ampere VA 79392.5 70730 62067.5 53405 44742.5 36080 27417.5 18755
kVA VA 66500 59400 52300 45200 38100 31000 23900 16800
VA 66500 59400 52300 45200 38100 31000 23900 16800
REMAINING POWER VA #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!

UPS Usage from 80% total capacity % #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
NEW LOAD

N540X-16Z8Q2C-D Watt 275 275 275


275 275 275 275 275
0 Watt 1100 1100 1100 1100 1100 1100 1100 1100
0 Watt 1100 1100 1100 1100 1100 1100 1100 1100
0 Watt 1100 1100 1100 1100 1100 1100 1100 1100
0 Watt 1100 1100 1100 1100 1100 1100 1100 1100
0 Watt 1100 1100 1100 1100 1100 1100 1100 1100
TOTAL LOAD VA 4468.75 4468.75 4468.75 4468.75 4468.75 4468.75 4468.75 4468.75
RESULT
TOTAL REQUIREMENT (EXITING + NEW) VA 70075 62975 55875 48775 41675 34575 27475 20375
REMAINING POWER VA #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
UPS Usage total capacity 100% #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
STATUS OK/ Need Upgrade #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
Capacity kVA 0 0 0 0 0 0 0 0
Unit #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
Utilization after Upgrade % #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE!
BATTERY UNIT UPS 1 UPS 2 UPS 3 UPS 4 UPS 5 UPS 6 UPS 7 UPS 8
Brand
Model Lithium / VLRA
Voltage 2V / 12V 56 56 56 56 56 56 56 56
Capacity Ah
Qty Bank
BACK UP TIME (existing) Hrs - - - - - - - -
Charging 10% - - - - - - - - -
RESULT
Treshold hrs 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
BACK UP TIME (Existing + New) Hrs - - - - - - - -
STATUS OK/ Need Upgrade UPGRADE BATUPGRADE BATT UPGRADE BATT UPGRADE BATT UPGRADE BATT UPGRADE BATT UPGRADE BATT UPGRADE BATT
CAPACITY AH 0 0 0 0 0 0 0 0
Qty Bank 0 1 0 1 0 1 0 1
BACK UP TIME AFTER UGRADE hrs - - - - - - - -
REMARKS
POWER (Dual / Single) Dual Koneksi Dual Power UPS from UPS &
MCB OK
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

STATUS RECTIFIER Type Rect LOAD PERANGKAT


No LOKASI NAMA PERANGKAT TRN/RAN/B2B MCB REMARKS
ACTIVE/ OFF (A)
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

STATUS Jumlah Koneksi LOAD PERANGKAT


No LOKASI NAMA PERANGKAT TRN/RAN/B2B MCB REMARKS
AKTIF/ OFF Perangkat Rectifier (A)
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java
SITE LAYOUT 1. FOTO DARI PAGAR
2. FOTO SITE KESELURUHAN
3. FOTO IDPEL PLN
4. FOTO KWH (MCB)
5. FOTO PENGUKURAN LOAD KWH (R,S,T,N)
6. FOTO TOWER
7. FOTO JENIS SHELTER (ELEVATED CKD/PERMANENT/WITH CONCRETE/H BEAM)
GENSET 1. FOTO RUANG GENSET
2. FOTO KONDISI GENSET
3. FOTO NAME PLATE GENSET
4. FOTO ATS
5. FOTO PENGUKURAN ATS (R,S,T,N)
ALL RECTIFIER OUTDOOR 1. FOTO RECTIFIER OUDOOR FULL,& Grounding
2. FOTO RECTFIER POSISI PINTU TERBUKA
3. FOTO RECTIFIER TYPE MODULE
4. FOTO RECTIFIER LOAD
5. FOTO BATTERY
6. FOTO DETAIL MCB
7. FOTO PONDASI OUTDOOR, IGB
8. FOTO ACPDB OUTDOOR
9. FOTO LOAD ACPDB OUTDOOR
ALL SHELTER 1. FOTO DALAM SHELTER 1 DENGAN POSISI DARI PINTU MASUK
2. FOTO DALAM SHELTER 1 DENGAN POSISI KEARAH PINTU KELUAR
3. FOTO DALAM SHELTER 1 DENGAN POSISI DINDING KIRI
4. FOTO DALAM SHELTER 1 DENGAN POSISI DINDING KANAN
5. FOTO SEMUA RECTIFIER INDOOR FULL
6. FOTO SEMUA RECTFIER INDOOR PINTU TERBUKA
7. FOTO SEMUA RECTIFIER TYPE MODULE
8. FOTO SEMUA RECTIFIER LOAD
9. FOTO SEMUA BATTERY
7. FOTO DETAIL MCB SEMUA RECTIFIER
10. FOTO SEMUA PERANGKAT & NAMA PERANGKATNYA
11. FOTO SEMUA PERANGKAT DALAM POSISI PINTU TERBUKA (FULL RACK FOTO)
12. FOTO PENGUKURAN LOAD PERANGKAT
13. FOTO DETAIL PERANGKAT YANG TERINSTALL DI RACK 19
14. FOTO ACPDB
15 FOTO PENGUKURAN LOAD MCB ACPDB
16 FOTO DCPDB
17. FOTO PENGUKURAN LOAD MCB
18.FOTO SEMUA AC SPLIT
19. FOTO TEMPERATURE DI SHELTER
20. FOTO IGB
21. FOTO VENTILATION SYSTEM - AIR INLET (POSISI DI BAWAH DALAM SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
22. FOTO VENTILATION SYSTEM - AIR OUTLET (POSISI ATAS DALAM SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
23. FOTO VENTILATION SYSTEM - AIR INLET (POSISI DI BAHAH DI LUAR SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
24. FOTO VENTILATION SYSTEM - AIR OUTLET (POSISI ATAS DI LUAR SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
ALL RECTIFIER INDOOR 1. FOTO RECTIFIER INDOOR FULL
2. FOTO RECTFIER POSISI PINTU TERUKA
3. FOTO RECTIFIER TYPE MODULE
4. FOTO RECTIFIER LOAD
5. FOTO BATTERY
6. FOTO DETAIL MCB
ALL UPS INDOOR 1. FOTO UPS FULL
3. FOTO UPS TYPE MODULE
4. FOTO UPS LOAD
5. FOTO BATTERY
AC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

ID PELANGGAN KWH

Phase R Load (Measured) A Phase S Load (Measured) A

Phase T Load (Measured) A Phase N Load (Measured) A


AC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

LOAD CURRENT ACPDB R = A LOAD CURRENT ACPDB S = A

LOAD CURRENT ACPDB T = A LOAD CURRENT ACPDB N = A

ACPDB Main MCB ACPDB


AC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

LOAD CURRENT ACPDB R = A LOAD CURRENT ACPDB S = A

LOAD CURRENT ACPDB T = A LOAD CURRENT ACPDB N = A

ACPDB Main MCB ACPDB


AC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

VIEW GENSET VIEW ATS GENSET

Voltage Measurement at ATS Panel R-N V Voltage Measurement at ATS Panel S-N V

N/A

Voltage Measurement at ATS Panel T-N V Voltage Measurement at ATS Panel PE-N V
EXTERIOR PHOTOS
Site Name REJASABANJARNEGARA_PLCity Banjarnegara
Site ID 14BJN0058 Area Central Java

Site View Site View

Site View Site View

Site View Site View


EXTERIOR PHOTOS
Site Name REJASABANJARNEGARA_PLCity Banjarnegara
Site ID 14BJN0058 Area Central Java

Site View Site View

Site View Site View

Site View Site View


INTERIOR PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

VIEW SHELTER VIEW SHERLTER

VIEW SHERLTER VIEW SHERLTER

VIEW INDOOR VIEW INDOOR


VIEW INDOOR VIEW INDOOR

VIEW INDOOR VIEW INDOOR

TERMOGUN VIEW TRAY


INDOOR EQUIPMENT PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

VIEW ACPDB INDOOR VIEW MCB ACPDB

AC SPLIT 1 AC SPLIT 2,3 DAN 4

MAIN GROUNDING INDOOR CABLE TRAY


DC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

NA NA

Air Inlet 1 Air Inlet 2

NA NA

Outlet Air Outlet 3

NA NA

DC FAN outlet 1 DC FAN outlet 1

NA NA
DC FAN outlet 2 DC FAN outlet 2
EXTERIOR PHOTOS
Site Name REJASABANJARNEGARA_PLCity Banjarnegara
Site ID 14BJN0058 Area Central Java

Site View Site View

Site View Site View

Site View Site View


INTERIOR PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

VIEW INDOOR VIEW INDOOR

VIEW INDOOR VIEW INDOOR

VIEW INDOOR VIEW INDOOR


VIEW TRAY TERMOGUN
INDOOR EQUIPMENT PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

VIEW ACPDB INDOOR VIEW MCB ACPDB

AC SPLIT 1 AC SPLIT 2 DAN 3

MAIN GROUNDING INDOOR CABLE TRAY


DC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java

NA NA

Air Inlet 1 Air Inlet 2

NA NA

Air Outlet 1&2 Air Outlet 3

NA NA

DC FAN outlet 1 DC FAN outlet 1

NA NA
DC FAN outlet 2 DC FAN outlet 2
EXISTING EQUIPMENT PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area

VIEW FULL RACK PERANGKAT VIEW DCPDB RACK PERANGKAT

VIEW SOURE A (A) VIEW SOURCE B (A)

CISCO CISCO
DC POWER PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara

Site ID 14BJN0058 Area Central Java


REJASABANJARNEGARA_PL

RECTIFIER 1 (SHELTER 1) MODULE RECTIFIER 1

LOAD CURRENT A BATTERY BANK

NA NA

RECTIFIER 2 (SHELTER 2) MODULE RECTIFIER 2

NA NA
LOAD CURRENT A BATTERY BANK
NA NA

RECTIFIER 3 (SHELTER 3) MODULE RECTIFIER

NA NA

LOAD CURRENT A BATTERY BANK

RECTIFIER 3 (SHELTER 3) MODULE RECTIFIER

LOAD CURRENT A LOAD CURRENT A


OTB PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

VIEW OTB OTB

OTB INDOSAT OTB INDOSAT


OTB PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

EXISTING NOKIA 1 EXISTING NOKIA 2

LOAD EXISTING NOKIA 1 (A) LOAD EXISTING NOKIA 2 (A)

LOAD EXISTING NOKIA 1 (A) LOAD EXISTING NOKIA 2 (A)

LOAD EXISTING NOKIA 1 (A) LOAD EXISTING NOKIA 2 (A)

LOAD EXISTING NOKIA 1 (A) LOAD EXISTING NOKIA 2 (A)

EXISTING DCPDB LOAD EXISTING DCPDB


OTB PHOTOS
Site Name REJASABANJARNEGARA_PL City Banjarnegara
Site ID 14BJN0058 Area Central Java

PROP. N540X-16Z8Q2C-D PROPOSED MCB

ANOTHER PROP. MCB RECT ELTEK


ANOTHER PROP. PERANGKAT
SHELTER 2

You might also like