TECHNICAL SITE SURVEY REPORT

PROJECT NAME : TOMHAWK PROJECT

SITE NAME : JLBOLING_PADANGSARAI_TB

SITE ID : 03PDN0010

CITY : PADANG

AREA : CSRO

SITE TYPE : Green Field

Silayang, Kec. Mapat Tunggul Sel., Kabupaten Pasaman, Sumatera


ADDRESS : Barat

SITE OWNER : TOWERBERSAMA GROUP

Approved By,
INDOSAT OOREDOO- PROJECT INDOSAT OOREDOO- ID INDOSAT OOREDOO

VENDOR
1. GENERAL INFORMATION

Project Name TOMHAWK PROJECT


Site Name JLBOLING_PADANGSARAI_TB City PADANG AREA CSRO
Site ID 03PDN0010 Longitude 0,4844 Latitude 1001913
Street Address Silayang, Kec. Mapat Tunggul Sel., Kabupaten Pasaman, Sumatera Barat
Site Type Green Field Site Owner Protelindo Date of Survey 26-Jul-23
Shelter Type OUTDOOR
List of Surveyor:
No. Name Company E-mail Cell Phone
1 HANDRI BEAUT +62 823-8721-0421
2 RAFI
3
List of Customer PIC:
No. Name Company E-mail Cell Phone
1 PT. Indosat
2
3
List of Proposed Equipments:
SCOPE
Cabinet Dimension Power MCB x Pcs
No. Equipment Type (SWAP/UPGRAD
Quantity (W x D x H) mm (Watt) (AC / DC)
E/NEW)

1 ZXCTN 6120H-S NEW 43.6 mm × 264 mm × 270 mm 200 2 PCS X 16A (DC)
SITE NAME TOMHAWK PROJECT CITY 03PDN0010
SITE IE JLBOLING_PADANGSARAI_TB AREA PADANG

BERITA ACARA KESEPAKATAN SURVEY EI LAPANGAN

Scope : NEW -ZXCTN 6120H-S


Project : TOMHAWK PROJECT

NO ITEM STATUS KETERANGAN

Type site TYPE SITE ROOF TOP/ GREEN FIELD/ INDOOR BUILDING GREEN FIELD
PERANGKAT ZXCTN 6120H-S-NEW
SPACE OK LOKASI Proposed New ZXCTN 6120H-S At Rack OUTDOOR
2 OTB/ODP OK LOKASI ODP READY AT POLE
3 MCB PDU A NONE PROP. MCB NEW (A)= X PCS LOAD (A) = 0
3 MCB PSU 1 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
4 MCB PSU 2 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
3 MCB PDU B NONE PROP. MCB NEW (A)= X PCS LOAD (A) = 0
5 MCB PSU 3 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
6 MCB PSU 4 NONE PROP. MCB NEW (A)= X PCS LOAD (A) =
7 PLN OK 13200VA UPGRADE KE 0
8 GENSET N/A N/A - N/A VA UPGRADE KE 0 VA
9 RECTIFIER 1 ADD MODULE OUTDOOR -DELTA-0-2 Utilisasi (%) 110%
BUT ADD BATTERY BUT 0.0
Remarks
10 RECTIFIER 2 #DIV/0! --- Utilisasi (%) #DIV/0!
BUT #DIV/0! BUT #DIV/0!
Remarks
11 RECTIFIER 3 #DIV/0! --- Utilisasi (%) #DIV/0!
BUT #DIV/0! BUT #DIV/0!
Remarks
12 RECTIFIER 4 #DIV/0! --- Utilisasi (%) #DIV/0!
BUT #DIV/0! BUT #DIV/0!
Remarks
13 MCB OK Propose USE MCB Existing 2 x 16 A

14 SINGLE/DUAL Single Koneksi Single Source Dual Feed, Main&Redundant Koneksi Ke Power System 1 -HUAWEI R4850N

15 GROUNDING OK Idle 2 Hole At Grounding Rack


16 AC SPLIT NOK SITE OUTDOOR
17 PONDASI RECT OUTDOOR OK
18 SPACE UNTUK RECT OUTDOOR OK
19 SHELTER TYPE CKD with H BEAM/CKD with CONCRETE/CONCRESITE OUTDOOR

SPACE - OK - Proposed New ZXCTN 6120H-S At Rack OUTDOOR,PLN - OK,GENSET - N/A, - OK -


Propose USE MCB Existing 2 x 16 ARECT - Single - Koneksi Single Source Dual Feed,
20 REMARKS Main&Redundant Koneksi Ke Power System 1 -HUAWEI R4850N,GROUNDING - OK - Idle 2 Hole At
Grounding Rack,AC SPLIT-NOK - SITE OUTDOOR,PONDASI RECT OUTDOOR - OK,SPACE UNTUK
RECT OUTDOOR - OK,SHELTER TYPE - SITE OUTDOOR
3. PLN & GENSET CALCULATION
SITE NAME JLBOLING_PADANGSARAI_TB CITY PADANG

SITE ID 03PDN0010 AREA CSRO

PLN UNIT KWH ATS REMARKS


TRAFO
MEREK
CAPACITY kVA
KWH
IDPEL 7677676
Phase 1 / 3 Phase 3
PLN MCB Capacity (Each Phase) Ampere 20
PLN Capacity VA 13200
R Current Load (Measured) Ampere 3.8
S Current Load (Measured) Ampere 3.4

T Current Load (Measured) Ampere 0

N Current Load (Measured) Ampere 3.6

TOTAL LOAD PLN VA 1584


R-N Voltage Volt 236
S-N Voltage Volt 236
T-N Voltage Volt 240
N - PE Voltage Volt 0.4
MCB Idle/Spare 0
GENSET UNIT GENSET 1 GENSET 2 GENSET 3 REMARKS
Brand N/A
Type (Silent / Non Silent ) N/A
YEAR OF INSTALLATION
Genset Room (Canopy / Room) N/A
kVA Capacity VA N/A
Quantity unit N/A
Condition N/A
ACPDB UNIT ACPDB 1 ACPDB 2 REMARKS
Phase 1 / 3 Phase 3
ACPDB MCB Capacity Ampere 20
R Current Load (Measured) Ampere 2.4
S Current Load (Measured) Ampere 2.7
T Current Load (Measured) Ampere 0.1
MCB Idle/Spare 6
PLN & GENSET Calculation
Existing Load VA 1584 DIAMETER CABLE
Battery Charging VA 0 FROM TRAFO TO ATS
PLN Utilization before add new Type NYFGBY
load % 12%
Genset Utilization before add new Diameter 4x25 mm²
load % #VALUE!

NEW LOAD FROM ATS TO MDP


New Equipment Location SHELTER 1 ACPDB 1
VA 200
New Air Condition ( if any changes Watt 0 Diameter 4x25 mm²
from previous Cooling capacity or
running sequence) VA 0 Type NYFGBY
Watt 0
New Rectifier
VA 0 Location SHELTER 2 ACPDB 2
Cap/Ah 0 Diameter 4x25 mm²
New Battery Qty 0 Type NYFGBY
Charging 0
Cap/Ah 0 Location
New UPS Qty 0 Diameter mm²
Charging 0 Type
Total AC Power Requirement VA 200
STATUS Location
Remain Power PLN VA 11416 Diameter mm²
Remain Power Genset VA #VALUE! Type
PLN Utilization after add new load
% 14%
Genset Utilization after add new Type
load % #VALUE!
Diameter mm²
RESULT
PLN
THRESHOLD PLN % 90%
STATUS OK/UPGRADE OK
TOTAL REQUIREMENT kVA 0
UPGRADE TO kVA
UTILIZATION AFTER UGRADE %
GENSET
THRESHOLD GENSET % 80%
STATUS OK/UPGRADE #VALUE!
UPGRADE TO kVA
UTILIZATION AFTER UGRADE %
REMARKS

PLN OK

APABLA PLN TIDAK BISA DI TES,CEK DI INPUT ATS


4a. RECTIFIER CALCULATION
Site Name JLBOLING_PADANGSARAI_TB CITY PADANG

Site ID 03PDN0010 AREA CSRO


GENERAL
DC POWER SYSTEM UNIT Power System 1 Power System 2 Power System 3 Power System 4 Power System 5 Power System 6 REMARKS
Location: Shelter/Outdoor OUTDOOR
Brand DELTA
Type Module Rectifier 0
YEAR OF INSTALLATION
Capacity per Rectifier Module Watt 3000
Maximum Rectifier Modules Slot Pcs 6
Qty of Rectifier Module Installed Slot 2
Available Modules Slot Pcs 4
Current Max Output (Rating) Ampere 108.89
Float Voltage Volt 55.1 55.1
Boost Voltage Volt 56.0 56.0 56.0 56.0 56.0 56.0
DC Current Load (Measured) Ampere 44.2 If display can not reading please check manual
Rectifier Efficiency % 90% 90% 90% 90% 90% 90% 90%
Battery UNIT Battery 1 Battery 2 Battery 3
Brand 0

Type 0

YEAR OF INSTALLATION
Charge Coefficient % 10% 10% 10% 10% 10% 10%
Capacity Ah 100
Qty of Banks Banks 0
Total Battery Capacity Ah 0 0 0 0 0 0
DC POWER CALUCATION
Existing Load Watt 2435 0 0 0 0 0 3044 VA
Battery Charging Watt 0 0 0 0 0 0 0 VA
Proposed Equipment
ZXCTN 6120H-S Watt 200
Watt
Watt
Total Proposed Equipment Watt 200 0 0 0 0 0 250 VA
Total Load Watt 2635 0 0 0 0 0 3294.275 VA
Capacity Rectifier 80% with redudancy (n-1) Watt 2400 0 0 0 0 0
Rectifier Existing Utilization % 101% #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Rectifier Existing + New Load Utilization % 110% #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Remain Power Watt -235 0 0 0 0 0
RESULT
THRESHOLD CAPACITY RECTIFIER 100% 80% 90% 90% 90% 90% 90%
STATUS RECTIFIER OK/ADD ADD MODULE #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
TYPE MODULE 0 0 0 Dec-99 0 0
ADD MODULE Pcs -1 0 0 0 0 0
AVAILABLE SLOT Pcs 3 0 0 0 0 0
NEW CAPACITY 80% WITH REDUDANCY (N-1) Watt 5400 0 0 0 0 0
RECTIFIER ULITIZATION AFTER EXPANSION % 49% #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
BATTERY CALUCATION
Battery Backup Time Load Existing hours 0.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Battery Backup Time Load Existing + New :oad hours 0.0 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
RESULT
THRESHOLD BACKUP TIME 2 hrs 2 2 2 2 2 2
TOTAL LOAD Ampere 55 0 0 0 0 0
STATUS BATTERY ADD BATTERY #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

MEREK 0 0 0 0 0 0
TYPE BATTERY 0 0 0 0 0 0
CAPACITY Ah 100 0 0 0 0 0
ADD BATTERY Banks 2 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
BACKUP TIME AFTER ADD BATTERY hours 3.6 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
COONECTION POWER Main / Main &Redundant
Redundant
NOTE FROM CORE INRASTRUCTURE DESIGN & SOLUTION
POWER Single Koneksi Single Source Dual Feed, Main&Redundant Koneksi Ke Power System 1 -HUAWEI R4850N

MCB OK Propose USE MCB Existing 2 x 16 A


SPACE OK Proposed New ZXCTN 6120H-S At Rack OUTDOOR
GROUNDING OK Idle 2 Hole At Grounding Rack
4a. RECTIFIER CALCULATION
Site Name JLBOLING_PADANGSARAI_TB CITY PADANG

Site ID 03PDN0010 AREA CSRO


GENERAL
DC POWER SYSTEM UNIT Power System 7 Power System 8 Power System 9 Power System 10 Power System 11 Power System 12 REMARKS
Location: Shelter/Outdoor OUTDOOR
Brand HUAWEI
Type Module Rectifier R4850G
YEAR OF INSTALLATION
Capacity per Rectifier Module 3000 Watt
Maximum Rectifier Modules Slot 5 Pcs
Qty of Rectifier Module Installed 2 Slot
Available Modules Slot 3 Pcs
Current Max Output (Rating) 25.6 Ampere
Float Voltage Volt
Boost Voltage Volt 56.0 56.0 56.0 56.0 56.0 56.0
DC Current Load (Measured) 3.86 Ampere If display can not reading please check manual
Rectifier Efficiency % 90% 90% 90% 90% 90% 90% 90%
Battery UNIT Battery 1 Battery 2
Brand SHOTO
Type 6-FMX-100B
YEAR OF INSTALLATION
Charge Coefficient % 10% 10% 10% 10% 10% 10%
Capacity 100 Ah
Qty of Banks 1 Banks
Total Battery Capacity 200 Ah 0 0 0 0 0 0
DC POWER CALUCATION
Existing Load Watt 0 0 0 0 0 0 0 VA
Battery Charging Watt 0 0 0 0 0 0 0 VA
Proposed Equipment
Watt
Watt
Watt
Total Proposed Equipment Watt 0 0 0 0 0 0 0 VA
Total Load Watt 0 0 0 0 0 0 0 VA
Capacity Rectifier 80% with redudancy (n-1) Watt 0 0 0 0 0 0
Rectifier Existing Utilization % #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Rectifier Existing + New Load Utilization % #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Remain Power Watt 0 0 0 0 0 0
RESULT
THRESHOLD CAPACITY RECTIFIER 100% 100% 100% 100% 100% 100% 100%
STATUS RECTIFIER OK/ADD #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
TYPE MODULE Dec-99 Dec-99 Dec-99 Dec-99 0 0
ADD MODULE Pcs 0 0 0 0 0 0
AVAILABLE SLOT Pcs 0 0 0 0 0 0
NEW CAPACITY 80% WITH REDUDANCY (N-1) Watt 0 0 0 0 0 0
RECTIFIER ULITIZATION AFTER EXPANSION % #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
BATTERY CALUCATION
Battery Backup Time Load Existing hours #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Battery Backup Time Load Existing + New :oad hours #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
RESULT
THRESHOLD BACKUP TIME 2 hrs 2 2 2 2 2 2
TOTAL LOAD Ampere 0 0 0 0 0 0
STATUS BATTERY #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
MEREK 0 0 0 0 0 0
TYPE BATTERY 0 0 0 0 0 0
CAPACITY Ah 0 0 0 0 0 0
ADD BATTERY Banks #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
BACKUP TIME AFTER ADD BATTERY hours #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
NOTE FROM CORE INRASTRUCTURE DESIGN & SOLUTION
5 AIR COOLING CALCULATION
Site Name JLBOLING_PADANGSARAI_TB CITY PADANG

Site ID 03PDN0010 AREA CSRO

AC SPLIT
Location / Room / Shelter
Dimension Room Length (m)
Width (m)
Area (m²)
LAMP UNIT
MEREK
CAPACITY PK
YEAR OF INSTALLATION
TEMPERATURE INSIDE °C
QUANTITY Pcs
TOTAL LOAD PLN Watt 0 0 0 0 0
CAPACITY COOLING Watt 0 0 0 0 0 0 0
COOLING CALCULATION
EQUIPMENT Watt 0 0 0 0 0 0
LAMP Watt 0 0 0 0 0 0
AIR CONDITION EXISTING Watt - - - - - -
COOLING EXISTING UTILIZATION %
Watt 200 200
NEW LOAD
Watt 200.00 200.00 200.00 200.00
COOLING EXISTING + NEW LOAD %
UTILIZATION
RESULT
THRESHOLD COOLING % 80% 80% 80% 80% 80% 80%
STATUS COOLING OK/ADD
CAPACITY PK 0 0 0 0 0 0
REMAIN CAPACITY COOLING Watt (200.00) (200.00) (200.00) (200.00) - -
QUANTITY Unit

REMARKS
SITE OUTDOOR
6. UPS POWER CALCULATION
Site Name JLBOLING_PADANGSARAI_TB CITY PADANG

Site ID 03PDN0010 AREA CSRO

UPS UNIT UPS 1 UPS 2 UPS 3


Room
UPS Capacity kVA
N Unit
Quantity
N-1 Unit 0 0
80% kVA 0 0
UPS Avalibility (N-1) and 80%
VA 0 0
EXISTING LOAD
R Current Load (Display Ampere) Ampere
S Current Load (Display Ampere) Ampere
T Current Load (Display Ampere) Ampere
R Current Load (Display kVA) kVA
S Current Load (Display kVA) kVA
T Current Load (Display kVA) kVA
TOTAL LOAD Ampere VA 0 0
kVA VA 0 0
VA 0 0
REMAINING POWER VA 0 0

UPS Usage from 80% total capacity % #DIV/0! #DIV/0!


NEW LOAD
1 CABINET CS PROBE SOC PROJECT Watt

TOTAL LOAD VA 0
RESULT
TOTAL REQUIREMENT (EXITING + NEW) VA 0 0
REMAINING POWER VA 0 0
UPS Usage from 80% total capacity 100% #DIV/0! #DIV/0!
STATUS OK/ Need Upgrade #DIV/0! #DIV/0!
Capacity kVA 0 0
Unit #DIV/0! #DIV/0!
Utilization after Upgrade % #DIV/0! #DIV/0!
BATTERY UNIT UPS 1 UPS 2
Brand
Model
Voltage
Capacity
Qty
BACK UP TIME (existing) Hrs #DIV/0! #DIV/0!
RESULT
Treshold hrs 0.5 0.5
BACK UP TIME (Existing + New) Hrs #DIV/0! #DIV/0!
STATUS OK/ Need Upgrade #DIV/0! #DIV/0!
CAPACITY AH 0 0
Qty Bank #DIV/0! #DIV/0!
BACK UP TIME AFTER UGRADE hrs #DIV/0! #DIV/0!
REMARKS
Site Name JLBOLING_PADANGSARAI_TB City PADANG
Site ID 03PDN0010 Area CSRO

STATUS RECTIFIER Type Rect LOAD PERANGKAT


No LOKASI NAMA PERANGKAT TRN/RAN/B2B MCB REMARKS
ACTIVE/ OFF (A)
1 Proposed swap ==> replace new
2 Proposed swap ==> replace new
Site Name JLBOLING_PADANGSARAI_TB City PADANG
Site ID 03PDN0010 Area CSRO

STATUS Jumlah Koneksi LOAD PERANGKAT


No LOKASI NAMA PERANGKAT TRN/RAN/B2B MCB REMARKS
AKTIF/ OFF Perangkat Rectifier (A)
1
2
Site Name JLBOLING_PADANGSARAI_TB City PADANG
Site ID 03PDN0010 Area CSRO
SITE LAYOUT 1. FOTO DARI PAGAR
2. FOTO SITE KESELURUHAN
3. FOTO IDPEL PLN
4. FOTO KWH (MCB)
5. FOTO PENGUKURAN LOAD KWH (R,S,T,N)
6. FOTO TOWER
7. FOTO JENIS SHELTER (ELEVATED CKD/PERMANENT/WITH CONCRETE/H BEAM)
GENSET 1. FOTO RUANG GENSET
2. FOTO KONDISI GENSET
3. FOTO NAME PLATE GENSET
4. FOTO ATS
5. FOTO PENGUKURAN ATS (R,S,T,N)
ALL RECTIFIER OUTDOOR 1. FOTO RECTIFIER OUDOOR FULL,& Grounding
2. FOTO RECTFIER POSISI PINTU TERBUKA
3. FOTO RECTIFIER TYPE MODULE
4. FOTO RECTIFIER LOAD
5. FOTO BATTERY
6. FOTO DETAIL MCB
7. FOTO PONDASI OUTDOOR, IGB
8. FOTO ACPDB OUTDOOR
9. FOTO LOAD ACPDB OUTDOOR
ALL SHELTER 1. FOTO DALAM SHELTER 1 DENGAN POSISI DARI PINTU MASUK
2. FOTO DALAM SHELTER 1 DENGAN POSISI KEARAH PINTU KELUAR
3. FOTO DALAM SHELTER 1 DENGAN POSISI DINDING KIRI
4. FOTO DALAM SHELTER 1 DENGAN POSISI DINDING KANAN
5. FOTO SEMUA RECTIFIER INDOOR FULL
6. FOTO SEMUA RECTFIER INDOOR PINTU TERBUKA
7. FOTO SEMUA RECTIFIER TYPE MODULE
8. FOTO SEMUA RECTIFIER LOAD
9. FOTO SEMUA BATTERY
7. FOTO DETAIL MCB SEMUA RECTIFIER
10. FOTO SEMUA PERANGKAT & NAMA PERANGKATNYA
11. FOTO SEMUA PERANGKAT DALAM POSISI PINTU TERBUKA (FULL RACK FOTO)
12. FOTO PENGUKURAN LOAD PERANGKAT
13. FOTO DETAIL PERANGKAT YANG TERINSTALL DI RACK 19
14. FOTO ACPDB
15 FOTO PENGUKURAN LOAD MCB ACPDB
16 FOTO DCPDB
17. FOTO PENGUKURAN LOAD MCB
18.FOTO SEMUA AC SPLIT
19. FOTO TEMPERATURE DI SHELTER
20. FOTO IGB
21. FOTO VENTILATION SYSTEM - AIR INLET (POSISI DI BAWAH DALAM SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
22. FOTO VENTILATION SYSTEM - AIR OUTLET (POSISI ATAS DALAM SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
23. FOTO VENTILATION SYSTEM - AIR INLET (POSISI DI BAHAH DI LUAR SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
24. FOTO VENTILATION SYSTEM - AIR OUTLET (POSISI ATAS DI LUAR SHELTER) - SEMUA SISI DINDING SHELTER (4 SISI)
ALL RECTIFIER INDOOR 1. FOTO RECTIFIER INDOOR FULL
2. FOTO RECTFIER POSISI PINTU TERUKA
3. FOTO RECTIFIER TYPE MODULE
4. FOTO RECTIFIER LOAD
5. FOTO BATTERY
6. FOTO DETAIL MCB
ALL UPS INDOOR 1. FOTO UPS FULL
3. FOTO UPS TYPE MODULE
4. FOTO UPS LOAD
5. FOTO BATTERY
AC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG
Site ID 03PDN0010 Area CSRO

N/A

ID PELANGGAN KWH

Phase R Load (Measured) 3.8 Phase S Load (Measured) 3.4

N/A N/A

Phase T Load (Measured) 0 Phase N Load (Measured) 3.6


AC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG
Site ID 03PDN0010 Area CSRO

N/A

LOAD CURRENT ACPDB R = 2.4 LOAD CURRENT ACPDB S = 2.7

N/A NA

LOAD CURRENT ACPDB T = 0.1 LOAD CURRENT ACPDB N = 2.9

N/A

ACPDB Main MCB ACPDB


AC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG
Site ID 03PDN0010 Area CSRO

NA NA

LOAD CURRENT ACPDB R = 0 A LOAD CURRENT ACPDB S = 0 A

NA NA

LOAD CURRENT ACPDB T = 0 A LOAD CURRENT ACPDB N = 0 A

NA NA

ACPDB Main MCB ACPDB


AC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TB City PADANG

Site ID 03PDN0010 Area CSRO

N/A NA

VIEW GENSET VIEW ATS GENSET

N/A N/A

Voltage Measurement at ATS Panel R-N 236 V Voltage Measurement at ATS Panel S-N 236V

N/A N/A

Voltage Measurement at ATS Panel T-N 240 V Voltage Measurement at ATS Panel PE-N 0.4 V
EXTERIOR PHOTOS
Site Name JLBOLING_PADANGSARAI_TB
City PADANG
Site ID 03PDN0010 Area CSRO

Site View Site View

Site View Site View

Site View Site View


EXTERIOR PHOTOS
Site Name JLBOLING_PADANGSARAI_TB
City PADANG
Site ID 03PDN0010 Area CSRO

NA NA

Site View Site View

NA NA

Site View Site View

NA NA

Site View Site View


INTERIOR PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG

Site ID 03PDN0010 Area CSRO

NA NA

VIEW SHELTER VIEW SHERLTER

NA NA

VIEW SHERLTER VIEW SHERLTER

NA NA

VIEW INDOOR VIEW INDOOR


NA NA

VIEW INDOOR VIEW INDOOR

NA NA

VIEW INDOOR VIEW INDOOR

NA

TERMOGUN VIEW TRAY


INDOOR EQUIPMENT PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG

Site ID 03PDN0010 Area CSRO

NA NA

VIEW ACPDB INDOOR VIEW MCB ACPDB

NO AC AVILIABLE N/A

AC SPLIT 1 AC SPLIT 2

NA NA

MAIN GROUNDING INDOOR CABLE TRAY


DC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG

Site ID 03PDN0010 Area CSRO

NA NA

Air Inlet 1 Air Inlet 2

NA NA

Outlet Air Outlet 3

NA NA

DC FAN outlet 1 DC FAN outlet 1

NA NA

DC FAN outlet 2 DC FAN outlet 2


EXTERIOR PHOTOS
Site Name JLBOLING_PADANGSARAI_TB
City PADANG
Site ID 03PDN0010 Area CSRO

NA NA

Site View Site View

NA NA

Site View Site View

NA NA

Site View Site View


INTERIOR PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity KALIMANTAN TENGAH

Site ID 16PTK088 Area KRO

NA NA

VIEW INDOOR VIEW INDOOR

NA NA

VIEW INDOOR VIEW INDOOR

NA NA

VIEW INDOOR VIEW INDOOR

NA NA

VIEW TRAY TERMOGUN


INDOOR EQUIPMENT PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG

Site ID 03PDN0010 Area CSRO

NA NA

VIEW ACPDB INDOOR VIEW MCB ACPDB

NA NA

AC SPLIT 1 AC SPLIT 2 DAN 3

NA NA

MAIN GROUNDING INDOOR CABLE TRAY


DC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG

Site ID 03PDN0010 Area CSRO

NA NA

Air Inlet 1 Air Inlet 2

NA NA

Air Outlet 1&2 Air Outlet 3

NA NA

DC FAN outlet 1 DC FAN outlet 1

NA NA

DC FAN outlet 2 DC FAN outlet 2


EXISTING EQUIPMENT PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG

Site ID 03PDN0010 Area CSRO

NEW ME NEW ME

VIEW FULL RACK PERANGKAT VIEW DCPDB RACK PERANGKAT

NEW ME NEW ME

VIEW SOURE A ( 0.50A) VIEW SOURCE B ( 0.11A)

NEW ME NEW ME

HUAWEI ATN910C HUAWEI ATN910C


DC POWER PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity KALIMANTAN TENGAH

Site ID 18SPT001 Area CSRO


JLBOLING_PADANGSARAI_TB

RECTIFIER 1 (OUTDOOR) MODULE RECTIFIER 1

LOAD CURRENT 44.2 A BATTERY BANK (NA)

NA NA

RECTIFIER 2 (OUTDOOR ) MODULE RECTIFIER 2

NA NA

LOAD CURRENT 0.1 A BATTERY (1)


NA NA

RECTIFIER 3 (SHELTER 3) MODULE RECTIFIER

NA NA

LOAD CURRENT 93 A BATTERY BANK

RECTIFIER 3 (SHELTER 3) MODULE RECTIFIER

LOAD CURRENT 60 A LOAD CURRENT A


OTB PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG
Site ID 03PDN0010 Area CSRO

N/A N/A

VIEW OTB/ODP OTB/ODP

OTB/ODP INDOSAT ODP INDOSAT


OTB PHOTOS
Site Name JLBOLING_PADANGSARAI_TB City PADANG
Site ID 03PDN0010 Area CSRO

N/A N/A

EXISTING HUAWEI 1 EXISTING HUAWEI 2

N/A N/A

LOAD EXISTING HUAWEI 1 ( A ) LOAD EXISTING HUAWEI ( )

N/A N/A

LOAD EXISTING HUAWEI 1 ( A ) LOAD EXISTING HUAWEI 2 ( A )

N/A N/A

LOAD EXISTING HUAWEI 1 ( ) LOAD EXISTING HUAWEI 2 ( A)

N/A N/A

LOAD EXISTING HUAWEI 1 (A) LOAD EXISTING HUAWEI 2 ( A)

N/A N/A

EXISTING DCPDB LOAD EXISTING DCPDB


OTB PHOTOS
Site Name JLBOLING_PADANGSARAI_TBCity PADANG
Site ID 03PDN0010 Area CSRO

PROP. ZXCTN 6120H-S PROP. MCB ZXCTN 6120H-S (USE EXISTING MCB
2 X 16 A)

N/A

PROP. ZXCTN 6120H-S PROP. MCB ZXCTN 6120H-S (USE EXISTING


(GROUNDING) MCB 2 X 16A )