Professional Documents
Culture Documents
DSEGenset
ELECTRICAL SAFETY
BS EN 60950
The DSE8760 is an easy-to-use The module can indicate Selected configuration is also Safety of Information Technology Equipment,
single or multi-mains controller with operational status and fault available via the module’s display including Electrical Business Equipment
automatic transfer switch capability. conditions on the LCD screen panel. TEMPERATURE
Designed to synchronise single or (multiple languages available), by BS EN 60068-2-1
With all communication ports Ab/Ae Cold Test -30 oC
multiple DSE8x10s and DSE8680s illuminated LED, audible sounder BS EN 60068-2-2
with single or multiple mains (utility) and SMS messaging. capable of being active at the same Bb/Be Dry Heat +70 oC
supplies, the DSE8760 will time, the DSE8xxx Series is ideal
for a wide variety of demanding VIBRATION
automatically control the change Comprehensive communications BS EN 60068-2-6
over from mains (utility) to generator are also available via RS232, load share applications. Ten sweeps in each of three major axes
5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz at
supply or run generators in RS485 & Ethernet for remote PC KEY LOAD SHARE FEATURES 2 GN
synchronisation with the mains control and monitoring, and (WITH DSE8x10) :
HUMIDITY
(utility) to provide no-break, peak integration into building • Peak lopping/shaving
BS EN 60068-2-30
lopping and peak shaving power management systems. • Sequential set start Db Damp Heat Cyclic 20/55 oC at 95% RH 48
solutions. The comprehensive event log will • Manual voltage/frequency Hours
adjustment BS EN 60068-2-78
record up to 250 events to facilitate Cab Damp Heat Static 40 oC at 93% RH 48
• R.O.C.O.F. and vector shift
The modules are designed to work maintenance. Hours
protection
with independent front display • Generator load demand SHOCK
screens which are connected via a An extensive number of fixed and • Automatic hours run balancing BS EN 60068-2-27
data link up to a maximum flexible monitoring and protection • Mains (Utility) de-coupling Three shocks in each of three major axes
distance of 1 km. These must be features are included. Easy • Mains (Utility) de-coupling 15 GN in 11 mS
ordered as a separate item. adjustment of the sequences, test mode DEGREES OF PROTECTION
timers and alarms can be made • Bus failure detection PROVIDED BY ENCLOSURES
• Volts and frequency matching. BS EN 60529
using the DSE PC Configuration IP65 - Front of module when installed into the
• kW & kV Ar load sharing
Suite Software. control panel with the supplied sealing gasket.
+
ETHERNET
DSE8760 MSC
7
5510 7510 8xxx
OTHER
ISSUE 2
®
DSEGenset
DSE8760 SPECIFICATION
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
DSE8721
Colour Remote Display Module
FREQUENCY RANGE
3.5 Hz to 75 Hz
BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
DSE8716
Standard Remote Display Module
OUTPUTS
OUTPUTS C & D
KEY FEATURES • Multiple display languages • Can be integrated into building 8 A at 250 V AC (Volt free)
• Can be set as a DSE8710 or • Five key menu navigation management systems (BMS) and
DSE8760 • Front panel editing with PIN programmable logic control (PLC) AUXILIARY OUTPUTS E,F,G,H, I & J
2 A DC at supply voltage
• Independent display screen protection • Increased input and output
options • Customisable status screens expansion capability via DSENet® DIMENSIONS
• Mains (utility) failure detection • Configurable inputs (11) • Licence-free PC software OVERALL
240 mm x 181 mm x 42 mm
• Mains (utility) power monitoring • Configurable outputs (8) • IP65 rating (with supplied gasket) 9.4” x 7.1” x 1.6”
(kW, kV Ar, kV A and pf) • Configurable timers and alarms offers increased resistance to water
• Comprehensive synchronising • Multiple entry scheduler ingress OPERATING TEMPERATURE RANGE
-30 oC to +70 oC
and loadsharing capabilities • Configurable event log (250) • Advanced Internal PLC editor allows -22 oF to +158 oF
• Peak lopping & shaving • Easy access diagnostic pages user configurable functions to meet
functionality • LED and LCD alarm indication specific application requirements. STORAGE TEMPERATURE RANGE
-40 oC to +85 oC
• Mains (utility) kW export • USB connectivity -40 oF to +185 oF
protection • Backed up real time clock EXPANSION DEVICES
• Mains (utility) de-coupling • Fully configurable via DSE • DSE124 CAN/MSC Extender
protection Configuration Suite PC Software • DSE2130 Input Expansion Module
• Advanced integral PLC editor • DSE2131 Ratiometric Input
• User configurable RS232, KEY BENEFITS Expansion Module
RS485 & Ethernet • A single flexible solution for • DSE2133 RTD & Thermocouple
communications multiple applications Expansion Module
• MODBUS RTU & TCP support • Compatible with DSE5510, • DSE2152 Analogue Output
• User configurable MODBUS DSE7510 & DSE8x10 series of Expansion Module
pages modules • DSE2157 Output Expansion
• Advanced SMS control and fault • Real-time clock provides Module
messaging (additional GSM accurate event logging • DSE2548 LED Expansion Module
modem required) • Ethernet communication provided
• DSENet expansion compatible builit in advanced remote
• Data logging and trending monitoring.
RELATED MATERIALS
TITLE PART NO’S
DSE8721 Colour Remote Display Module Data Sheet 055-073
DSE871x Mono Remote Display Module Data Sheet 055-084
DSE8700 Installation Instructions 053-073
DSE8760 Operator Manual 057-125
DSE8700 PC Configuration Suite Manual 057-127
DSE8710 Data Sheet 055-184
DSE8680 Data Sheet 055-091
DSE8810 Data Sheet 055-116
DSE8860 Data Sheet 055-139