Buffalo, N.Y., used the ventilation plant to entirely heat and ing was large and squat. Wright described it in his 1943 biogra-
ventilate the building (i.e., without using radiators). He sug- phy13 as a simple cliff of brick hermetically sealed (one of the
gested, with considerable foresight, that an ideal solution for first air-conditioned buildings in the country). The term air
such systems would be to have double ducts, one hot and one conditioning was practically unknown in 1906 and did not
cold. come into common use until the 1920s.
Alfred R. Wolff was the leading exponent of the design of Although the building appeared distinctly different, in terms
mechanical systems in the United States at the turn of the cen- of the mass it resembled the Chicago Quarter Blocks that
tury and the person responsible for the all-air ventilation sys- Wright was involved with when he worked in Louis Sullivans
tem at Buffalo. He designed about 100 systems between 1889 architectural offices in the 1890s. It had a basement and five
and his death in 1909.11 These tall buildings were not mechani- floors above ground, and the office space surrounded a large
cally ventilated throughout. For example, the 21-story Ameri- atrium with a glazed roof, or light court as it was called (Figure
can Surety Building in New York, completed in 1896, had a 3). This provided daylight to inner spaces on the floors above
mechanical warm air supply and extract ventilation system pro- ground, even though the building had electric lighting through-
viding four fresh air changes per hour, which only served the out. The large windows had an unusually high sill, 1.5 m (5 ft)
lower seven floors. The rationale was that lower floors suf- above the floor level, and no sun shading, in contrast to most
fered from the noise and smells of the street and that the occu- buildings of the period.
pants could not open windows for relief. The practice contin- The mechanical ventilation system provided heating and
ued into the late 1920s and 1930s. cooling by 4 to 5 changes of full fresh air per hour treated in the
The problem of office overheating was not mentioned in the basement air-handling plant. Air was exhausted from the of-
paper nor raised in the discussion. However, a comprehensive fices at floor line in winter and from the ceiling in summer,
paper on The Cooling of Closed Rooms,5 had been presented presumably to maximize the respective heating and cooling
at a meeting of ASHVE the previous year, and a few mechani- effect. Although the cooling power was not great, by compari-
cal cooling installations had already been completed. 11 son with more recent systems, one can speculate that intrinsic
features of the building would have meant that it was cool and
The Larkin Administration Building comfortable in summer. These features that contribute to cool
The first office building to break the mold was the Larkin comfort include: the generous floor to ceiling height of 4 m (13
Administration Building, designed by Frank Lloyd Wright and ft); the thermal-mass of the walls and ceilings; and the re-
completed in 1906. The brief from the client12 required a sealed cessed windows. The only area where there was likely to be a
building with mechanical ventilation. No mention was made of lack of comfort was on the west side where clerks would have
cooling, but Wright specified a refrigeration plant that distrib- been in direct sunshine on summer afternoons. Later photo-
uted cooling water at 10°C (50°F) to air-cooling coils in the graphs show that blinds were eventually installed, presumably
air-handling plants.13 to minimize overheating.
The external appearance, form and massing of the building The Larkin building was probably the first building designed
was dramatically different from architectural fashion at the time. to accommodate all the paraphernalia associated with modern
Most U.S. architects were still designing offices in the Beaux air conditioning. Service ducts running from basement to roof
Arts style with heavily ornamented facades. The Larkin build- were sited adjacent to staircases and expressed on the outside
June 1999 ASHRAE Journal 43
HISTORY
Naturally Ventilated Skyscrapers mid-1920s, air conditioning was installed of air conditioning. Classic buildings such
Although the Larkin Building was in theatres, hotels and department stores, as the Woolworth and Chrysler reached
widely reported and well received, the but rarely in offices, despite the mid-20s unprecedented heights by relying on na-
development of air conditioning in offices building boom. In fact, the skyscraper as ture to provide lighting and ventilation.
languished for the next 20 years. By the we know it evolved without the benefit The form of office buildings was still
Figure 5. Ducts were housed in a false ceiling that formed a lated air for a design of the Centrosoyus Palace in Moscow.
bulkhead that was lower than the main office ceiling. Air was The combination was called conditioned air, which Lyon
supplied from side-wall outlets at a high level and returned to the thought was an idea of genius. The Russians obviously did
fan room via transfer grilles and along corridors. The amount of not agree. They ignored the proposal and simply placed radia-
fresh air makeup could be adjusted by hand. The refrigeration tors behind the large opening windows.
unit had a cooling capacity of 300 tons (1,100 kW), which when The opportunity to use the concept came with the Cite de Ref-
related to the area of 20,000 m2 (220,000 ft2), seems quite mini- uge, a Salvation Army shelter in Paris. Le Corbusier conceived
mal. The maximum rate of cooling would have been about 54 the idea to hermetically seal the south face of the building from
W/m2 (17 Btu/h·ft2). Taking into account the outdoor design con- floor to ceiling and wall to wall with 1,000 m2 (11,000 ft2) of
dition of 36°C db (96.8°F) and 23°C wb. (73.4°F), the design of glass. His view was that the glass could be hermetically sealed as
the ductwork and the poor air distribution, it is unlikely that the warm and cleaned air circulated abundantly inside. He was
occupants of the offices in the southwest corner enjoyed the ben- giving the poor souls the free and ineffable joy of full light
efits of a fully air-conditioned environment. Perhaps the ability and the sun.
to open windows was a significant factor. The building opened late and over budget on Dec. 7, 1933, in
one of the coldest periods in memory. The temperature inside on
Air Conditioning and the International Style that cold, sunny day was perfect. Unfortunately, the same could
Although the office workers in the Milam Building might not not be said during summer. Although the designers had intended
have received the full benefits of air conditioning, they were con- to provide their version of air conditioning, the budget did not
siderably better off than the people in the Salvation Army Hostel provide for the cooling plant, and the neutralizing wall had been
designed by Le Corbusier and Jeanneret at about the same time. omitted.18 Sealed windows did not comply with regulations and
Le Corbusier had been collaborating with Gustave Lyon, who ultimately, much to Le Corbusiers displeasure, the windows were
was developing air conditioning in Europe independent of the changed to opening. It appears that this experience changed Le
experiments in the U.S.17 Lyon had completed the air condi- Corbusiers ideas about glazing. His subsequent buildings fea-
tioning for a 3,000-seat auditorium with his system called lair tured shading (which was eventually fitted to the hostel), and he
ponctuel, which loosely translates as regulated air. is credited with inventing the brise-soleil.
Le Corbusier claimed to have invented a technique for can-
celing the cooling effects of the large glazed surfaces charac- The PSFS Building
teristic of the new architecture, subsequently called the Inter- The 32-story PSFS Building in Philadelphia, completed in
national Style. Le Corbusiers idea was to circulate air at a 1932, broke new ground in its architectural style and the con-
constant temperature of 18°C (64.4°F) between the panes of cept of air conditioning. The appearance was considered mod-
double glazed windows. He called the technique le mur ern and distinctly different from any other in the U.S. The de-
neutralisant (neutralizing wall) and coupled it with Lyons regu- sign reflected the International Style19 with such features as an
48 ASHRAE Journal June 1999
(Circle No. 28 on Reader Service Card)
absence of external ornamentation, cubic shapes and a rela-
tively large area of metal framed, ribbon windows (Figure 6).
The PSFS building shared these characteristics with Le
Corbusiers Salvation Army Hostel and buildings by other lead-
ing architects of the time such as Gropius and Loos. But unlike
their buildings, it was fully air conditioned.
It is difficult to understand why this building was air condi-
tioned when other major buildings of the period were not. For
example, the Empire State Building in New York City had only
been completed a year earlier, and the RCA Building, the cen-
terpiece of Rockefeller Center, had just started construction.
Neither were air conditioned. The manager of the PSFS Build-
ing, writing in 1937,20 claimed the reason was the prospect of
increased rental income. However, the difference might have
been that the PSFS was built for a prosperous savings fund
society that had the funds available. It was a period of severe
recession in the U.S., and property developers had still not iden-
tified any financial gain from air conditioning.
The design of the engineering systems at the PSFS Building
included several innovations that pioneered the approach to ser-
vicing tall buildings. One of the more significant was the intro- Figure 5a: Floor plan for the Milam Building (1929).16
duction of an intermediate level mechanical plant room floor on
impact indoor air quality distribution to the breathing level within the ventilated space. Measurement
procedures and criteria for assessing the suitability of the test space for
and thermal comfort in measurements of air-change effectiveness are included. The method involves
1-800-527-4723
ASHRAE Customer Service
Mail to: 1791 Tullie Circle NE; Atlanta, GA 30329
For credit card orders: Call 1-800-5-ASHRAE (U.S./Canada)
or 404-636-8400 (worldwide); Fax: 404-321-5478
E-mail: orders@ashrae.org; www.ashrae.org
the 21st floor, in addition to the plant at considered in applying technologies to CTIAC systems.
roof level and in the basement. The con-
cept reduced the space required for the ver-
THIS BOOK PROVIDES the user with an understanding
tical ducts by distributing them up and
down from the roof, basement and inter-
mediate plant floor. This division of the of the benefits and limitations and assists in the successful
air supply plant dramatically reduced the
floor space for vertical ducts.
Fresh and possibly recirculated air was design and implementation of a combustion turbine inlet
supplied to floor fan rooms at each level.
Each fan room had two fans, one to serve
each of the east and west sides of the air cooling system. This book was developed under
building. The fresh air was mixed with
air drawn back through the corridors and ASHRAE Research Project 902. Dual units of
recirculated to the offices. The interme-
diate plant room at the 21st floor also
housed water tanks and reduced maxi- measurement. Author: William E. Stewart, Jr. 1998; 96 pp.
mum pressure on the distribution pipes
at lower floor levels. These techniques
have been employed extensively in tall Code: 90385 Price: $39.00 (Member: $26.00)
buildings since.
One can speculate whether the archi-
tects, Howe and Lescaze, demanded air
conditioning to counteract the heat gain 1-800-527-4723
from the relatively large windows even
though venetian blinds were an integral
ASHRAE Customer Service
Mail to: 1791 Tullie Circle NE; Atlanta, GA 30329
element of the design concept. This would
For credit card orders: Call 1-800-5-ASHRAE (U.S./Canada)
make the PSFS building the earliest where
or 404-636-8400 (worldwide); Fax: 404-321-5478;
air conditioning was installed to allow E-mail: orders@ashrae.org; Web: www.ashrae.org
greater architectural freedom.
June 1999 ASHRAE Journal 51
HISTORY Dont let the
SIZE
of this book fool you
9. Sterling, E. et al. 1983. New health haz- 17. Le Corbusier. 1937. When the Cathedrals
ards in sealed buildings. AIA Journal. Were White. Paris. Please circle the appropriate number on the
Re a d e r S e r v i c e C a r d a t t h e b a c k o f t h e
10. Meyer, H.C. Jr. Some points regarding 18. Taylor, B.B. 1987. Le Corbusier, the City
publication.
the ventilation and the heating of tall build- of Refuge, Paris 192933. The University of
ings. ASHVE Trans. 15: 94-107. Chicago Press. Extremely Helpful ....................................................... 462
Helpful ....................................................................... 463
11. Nagengast, B.A. 1992. The first 80 years 19. Banham, R. 1969. The Architecture of the
of air conditioning. ASHRAE Journal. 34(1): Well-Tempered Environment. Architectural Somewhat Helpful ...................................................... 464
S164-75. Press. London. p. 209. Not Helpful ................................................................. 465
1-800-527-4723 1-800-527-4723
ASHRAE Customer Service ASHRAE Customer Service
Mail to: 1791 Tullie Circle NE; Atlanta, GA 30329 Mail to: 1791 Tullie Circle NE; Atlanta, GA 30329
For credit card orders: Call 1-800-5-ASHRAE (U.S./ For credit card orders: Call 1-800-5-ASHRAE (U.S./Canada)
Canada) or 404-636-8400 (worldwide); Fax: 404-321-5478; or 404-636-8400 (worldwide); Fax: 404-321-5478; E-mail:
E-mail: orders@ashrae.org; www.ashrae.org orders@ashrae.org; www.ashrae.org