he increasing asset age of installed MV cables in the UK can RELIABLE ASSESSMENT OF THE CONDITION
be explained by observing the historical installation rate (see EDF Energy’s stated aim for on-line condition monitoring is to
Figure 1 below) which shows the heaviest installation rate develop a comprehensive suite of tools that can provide a ‘reliable
having occurred in the 1950’s and 1960’s. It can be noted that, assessment of the condition of the network’. This data can then be
based on the present cable replacement rate of MV cables by UK used to direct the company’s Asset Managers as to where best to
Utilities (which is very low), it would take an average of over 700 target limited resources. As the financial and environmental cost of
years to replace the entire network! replacing all older cables is prohibitive, EDF Energy is seeking
targeted maintenance and replacement strategies that can defer
asset replacement and avoid unplanned outages. The on-line PD
MV Cables test technology presented in this paper has thus been developed
with a specific view towards the Reliable Life-Extension of MV
MV Transformers Cables up to and beyond their estimated ‘Design Life’.
EDF Energy’s longer term objectives from applying the PD Test
Technology include:
• Reducing the overall level of risk on the power system.
Figure 1: • Targeting replacement/refurbishment programs by identifying
Typical UK MV
Plant Install Rate
and locating high risk sections of cables and/or reconfiguring
(1940 to 2000) Year networks.
• Developing systems and tools that can later be applied to other
35
40
45
50
55
60
65
70
75
80
85
90
00
19
19
19
19
19
19
19
19
19
19
19
19
20
The above point can be placed into some context by considering power systems assets
Table 1 which shows the typical ‘Design Life’ ascribed by UK Utilities
for various types of MV transformers, switchgear and cables. Table TESTING OF MV CABLE NETWORKS
1 shows that these range from 40 years (Outdoor Switchgear) to 70 At a simplistic level, cables with high PD activity can be classified as
years (6.6/11kV underground cables). By comparing the historical having a greater risk of failure than cables in which no PD activity
MV Plant installation rates in Figure 1 with the Design Life Data in can be detected. Once PD activity has been identified, the defects
Table 1, it can be noted that a lot of installed MV plant in the UK is which are causing the PD need to then be located (on-line or
now approaching the end of its original life expectancy. off-line PD Mapping) and an action plan drawn up for what to do
ASSET TYPE ‘DESIGN LIFE’ (YEARS)
next (repair, replace, PD monitoring etc).
Partial Discharge testing is becoming increasingly viewed as the
Transformers best diagnostic for cable insulation, particularly for on-line
Transformers (> 11kV) 50 measurements. Clearly this applies primarily to insulation which
11kV ground mounted 45
both exhibits and is degraded by PD activity. However, even for
11kV pole mounted 45
insulation which is designed to be PD free (such as XLPE cable
Switchgear installations) the knowledge that the system is actually PD free by
Indoor Switchgear 45 testing is still a vital part of the diagnostic process. Hence PD
Outdoor Switchgear 40 measurements which are accurate and reliable will always contain
Table 1: Cables important information about the condition of the plant under test.
UK Utility 132kV cables 60 On-line PD testing can also be used as part of the commissioning
‘Design Life’ 33kV cables 60 process for new cable installations to ensure cable accessories have
of MV Plant 6.6/11kV cables 70 been made-up correctly.
Partial discharges (PD) in voids and cavities will produce very
The other main ‘business driver’ in the development of the similar pulse shapes with very fast pulse widths of a few tens or
condition assessment technologies are the UK Regulatory Incentives hundreds of picoseconds being typical. In the special case of PD in
which require all electricity utilities company to continuously cables, the cavity responsible for the PD discharges into a real
improve network performance, to operate the network ‘smarter’ impedance (the ‘surge impedance’ of the cable) which is purely
and to reduce operational costs. resistive at the point of launch. The resulting PD pulse is virtually
These drivers underpin the need for a condition-based monopolar with a fast pulse risetime and very short pulse width.
approach to the management of these ageing cable assets. In This pulse travels outward from the originating site, and arrives at
order to achieve an effective condition-based asset management the detection point (at the switchgear termination) both wider and
policy it is proposed that MV cable condition is checked both smaller due to attenuation and dispersion on its travel down the cable.
regularly and in a systematic manner. This paper describes how this As the PD pulses travelling down the cable to the termination
is being achieved in the EDF Energy MV Cable Network through a have an equal and opposite polarity on the conductor and screen
combination of three types of test equipment; 1. Online PD Cable respectively, it does not matter whether the HFCT’s are placed in the
Tester, 2. Online PD Mapping System and 3. On-Line PD Monitor. earth strap, or the conductor.
The important criterion is that only one of the earth or conductor looking at the pulse magnitude (as in previous generations of on-
currents is intercepted (if they are both intercepted then they line PD test equipment) as it is much less sensitive to the effect of
effectively ‘cancel each other out’). A typical, monopolar cable PD signal attenuation along the cable from the PD source to the
pulse is shown below in Figure 2 which is shown with computer- measurement point. This is achieved in practice by digitising the PD
generated cursors to measure the risetime, falltime and other pulse pulse and then integrating the area under the current curve using
properties. the following equation:
end_ of _ pulse end_ of _ pulse
Charge = I*dt = const * V * dt
start_ of _ pulse start_ of _ pulse
This means that it is now possible to carry out On-line PD testing
of cables, without the need for an external calibrator, with the PD
levels expressed in picoCoulombs (pC’s).
• 24-hour On-line PD monitoring (see Figure 8 below) has shown Figure 11: Cable ‘Criticality’ classification for a 38 Panel substation.
that PD activity can in some cases follow the cable loading The data collected from the above automated PD Monitoring
pattern. This cable feeder had an greater load during the night process is used to select those circuits with high ‘criticality’ for the
(due to a Newspaper printing works load) but little or no PD on-line PD mapping process as a prelude to preventative
activity during the day. maintenance, replacement or repair.
ON-LINE VS OFF-LINE PD MAPPING TECHNIQUES The off-line PD maps were plotted (the pulse locations are
Off-line cable mapping such as Very Low Frequency (VLF) testing represented by crosses) and the on-line location was added on the
and oscillating wave (OWTS) techniques were developed in the same graph as well as the average magnitude of the pulses
1980’s and many utilities around the world are currently using them detected on-line.
as a diagnostic tool for their in-service cables. These technologies
have a number of practical restrictions in their widespread • Circuit 1: Bulwer St Panel 2: x
x ON-LINE
application and uptake as a routine cable condition diagnosis Length = 1115 metres x
x
x
x
LOCATION:
x
x 220m
system with the most notable being: Discussion: The location found x
x
x
x
x ON-LINE
• High Costs in terms of capital expenditure and also high on-line is the same as that x
x
x
x
MAGNITUDES:
x
100 – 500 Pc
running costs of operating a cable test van. found off-line (main PD site at x
x
x
x
x
• The application of off-line testing is in most cases limited to 220m) although the off-line x
x
x
x
x
x
circuits with no Tee junctions. result gives wider spread of x
x
• A considerable amount of bulky equipment is required and the PD’s around the main site.
cable section under test needs to be switched off and isolated. Figure 13: On-line vs.
It has been noted by the authors that the industry is now looking Off-line comparison Nº 1.
towards easier, faster and cheaper solutions for cable condition
assessment that offers on-line PD testing, mapping and monitoring • Circuit 2: Hyde Park A, Panel 10, x
x
x
x
ON-LINE
x LOCATION:
techniques which can achieve similar results to the established off- Length= 890 metres x
x
x
x 65m
x
x
line test technology. The most active site is the same x
x
x
x
ON-LINE
x MAGNITUDES:
On-line PD mapping techniques such as the Transponder for on-line and off-line testing x
x
x
x 2800 – 6300 Pc
x
technology are becoming increasingly recognised by the industry as (main site at 65m). The off-line x
x
x
x
x
the way forward as they are more portable, easier to use and testing also shows less dense x
x
x
x
x
x
cheaper to implement than the off-line techniques. areas of PD’s spread across the x
CONCLUSIONS
Following the trials carried on the EDF Energy network, it has been
concluded that the best strategy is to use a combination of the
on-line and off-line PD Mapping techniques.
On-line, remote-access PD monitors can be strategically deployed
at ‘critical’ or troublesome substations in order to observe the
Figure 12: Transponder and Off-line VLF testing equipment. evolution of any pd activity. With automatic software analysis tools,
the monitor can provide a ‘criticality rating’ of circuits at most risk
A number of EDF Energy’s MV cable feeders were tested with of failure which can be used to target mapping (on-line or off-line,
both the On-line and Off-line PD Mapping technologies to compare depending on the case).
the results obtained. Figures 13 and 14 show the location of the PD This article supplied by Lord Consulting, Agents for IPEC Engineering.
pulses detected on-line using the Transponder; and off-line, using For further information, please contact Trevor Lord: